background image

FANs 930, 930.5, 125, 121

Product/Technical Bulletin A350E

Issue Date 0899

© 1999 Johnson Controls, Inc.

1

Part No. 24-7664-400, Rev. B

www.johnsoncontrols.com

Code No. LIT-930015

System 350

A350E Electronic Cooling Control

The A350E is an on/off, electronic, cooling-only control
with Single-Pole, Double-Throw (SPDT) relay output
and Light-Emitting Diode (LED) relay status indication.
A cooling-only control, the A350E has two features that
differentiate it from the A350A/B Series Electronic
Temperature Controls: a selectable minimum setpoint
and short/open sensor detection. The A350E also has
an adjustable differential and an interchangeable
temperature sensor.

As are all System 350™ products, the A350E is
housed in a NEMA 1, high-impact plastic enclosure.
The modular design provides easy, plug-together
connections for quick installation and future
expandability.

Figure 1: A350E Electronic Cooling

Control

Features and Benefits

Modular Design

Enables stage, display, and power modules to
be purchased and installed as necessary

Minimum Setpoint
Selections

Allows the selection of a minimum setpoint at
which the equipment can be set to control

Reacts to Short or Open
Sensor Condition

Deenergizes output relay if the sensor or
sensor wiring fail

Wide Adjustable Differential
of 1 to 30F° (0.6 to 16.7C°)

Enables the user to match equipment cycle
rate and/or sequencing for a given application

Plug-together Connectors
and 35 mm DIN Rail
Mounting

Eliminates wiring between modules and
reduces installation costs

One Dual-scale Model
Covers a Temperature
Range of 10 to 65°F
(-12 to 18°C)

Supports the majority of Fahrenheit and
Celsius cooling applications

Interchangeable
Temperature Sensors

Increases versatility and serviceability

Summary of Contents for A350E

Page 1: ...esign provides easy plug together connections for quick installation and future expandability Figure 1 A350E Electronic Cooling Control Features and Benefits Modular Design Enables stage display and p...

Page 2: ...ity of the installer to add devices safety limit controls that protect against or systems alarm supervisory systems that warn of control failure Setpoint Adjustment Setpoint is defined as the temperat...

Page 3: ...echnical Bulletin LIT 930080 S350C Slave Stage Modules S350C Slave Stage Modules receive power and sensor input from the A350E control S350C Slave Stage Modules perform switching functions based upon...

Page 4: ...as well as other control modules Refer to Figures 5 and 6 for proper arrangement Note When mounting any System 350 module to rigid conduit attach the hub to the conduit before securing the hub to the...

Page 5: ...s Temperature Sensors and mounting hardware are available for use with the A350E Connect the sensor to the SEN terminal and one of the COM terminals on the four position terminal strip located at the...

Page 6: ...ng connections are according to job specifications before applying power Refer to Figure 7 for a sample multistage application if needed 2 Make the necessary adjustments and electrical connections 3 P...

Page 7: ...m as indicated in Table 4 replace the A350E Table 4 A350E Relay Troubleshooting LED N O Relay Status Setpoint Dial Setting On Closed Ts Differential Off Open Ts Ts is sensed temperature For example 70...

Page 8: ...Range 10 to 65 F 12 to 18 C Differential Adjustment Range 1 to 30F 0 6 to 16 7C SPDT Relay Output 120V 208 to 240V Horsepower 1 2 1 2 Full Load 9 8A 4 9A Locked Rotor 58 8A 29 4A Non Inductive 10A at...

Reviews: