Table 6: System 350 Accessories

Item

Product Code Number

Description

Outdoor Enclosure

BOX10A-600R

PVC enclosure; includes wire nuts

Wall Mount Plate

TE-6001-4

Includes sensor mounting clip

Cover

T-4000-2644

For wall mount plate

Conduit Adaptor

ADP11A-600R

1/2 in. snap-fit EMT conduit adaptor (box of 10)

Immersion Well

WEL11A-601R

For liquid sensing applications

DIN Rail Sections

BKT287-1R
BKT287-2R

12 in.( 0.3 m) long
39-1/3 in.(1.0 m ) long

DIN Rail End Clamps

PLT344-1R

Two end clamps

Cable for remote
mounting of D350 Display
Modules

WHA29A-600R*
WHA29A-603R
WHA29A-604R

3 ft (0.9 m)
25 ft (7.6 m)
50 ft (15.2 m)

* WHA29A-600R can also be used to remote mount S350 Stage Modules.

S

pecifications

Product

A350E Electronic Cooling Control

Supply Voltage

Y350R Power Module:

Input:

120/240 VAC 50/60 Hz

Output:

24 VDC, unfiltered, 10 VA, Class 2

External Source:

24 VAC, 50/60 Hz Class 2 (20-30 VAC)

Note:

Only one supply voltage source may be used.

Power Consumption

1.4 VA

Adjustment Setpoint

Range

10 to 65°F (-12 to 18°C)

Differential Adjustment

Range

1 to 30F° (0.6 to 16.7C°)

SPDT Relay Output

120V

208 to 240V

Horsepower:

1/2

1/2

Full Load:

9.8A 

4.9A

Locked Rotor:

58.8A 

29.4A

Non-Inductive:

10A at 24 to 240 VAC

Pilot Duty:

125 VA at 24 to 240 VAC

Ambient Temperatures

Operating: -30 to 150°F (-34 to 66°C)
Shipping:

-40 to 185°F (-40 to 85°C)

Humidity

0 to 95% RH non-condensing; maximum dew point: 85°F (29°C)

Sensor

Replaceable positive temperature coefficient sensor
Reference resistance: 1035 ohms at 77°F (25°C)

Material

Case and cover: NEMA 1, high-impact thermoplastic

Minimum Setpoint

Four jumper-selectable settings: 20°F (-7°C), 30°F (-1°C), 40°F (4°C), and Off

Short Circuit Detection

De-energizes the relay if the sensor shorts or opens

Agency Listings

UL Listed, CCN XAPX, File E27734
UL Listed for Canada, CCN XAPX7, File E27734

The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
specifications, consult Johnson Controls Application Engineering at (414) 274-5535. Johnson Controls, Inc. shall not be liable for damages
resulting from misapplication or misuse of its products.

Controls Group

507 E. Michigan Street
P.O. Box 423

Printed in U.S.A.

Milwaukee, WI   53201

www.johnsoncontrols.com

Summary of Contents for A350E

Page 1: ...esign provides easy plug together connections for quick installation and future expandability Figure 1 A350E Electronic Cooling Control Features and Benefits Modular Design Enables stage display and p...

Page 2: ...ity of the installer to add devices safety limit controls that protect against or systems alarm supervisory systems that warn of control failure Setpoint Adjustment Setpoint is defined as the temperat...

Page 3: ...echnical Bulletin LIT 930080 S350C Slave Stage Modules S350C Slave Stage Modules receive power and sensor input from the A350E control S350C Slave Stage Modules perform switching functions based upon...

Page 4: ...as well as other control modules Refer to Figures 5 and 6 for proper arrangement Note When mounting any System 350 module to rigid conduit attach the hub to the conduit before securing the hub to the...

Page 5: ...s Temperature Sensors and mounting hardware are available for use with the A350E Connect the sensor to the SEN terminal and one of the COM terminals on the four position terminal strip located at the...

Page 6: ...ng connections are according to job specifications before applying power Refer to Figure 7 for a sample multistage application if needed 2 Make the necessary adjustments and electrical connections 3 P...

Page 7: ...m as indicated in Table 4 replace the A350E Table 4 A350E Relay Troubleshooting LED N O Relay Status Setpoint Dial Setting On Closed Ts Differential Off Open Ts Ts is sensed temperature For example 70...

Page 8: ...Range 10 to 65 F 12 to 18 C Differential Adjustment Range 1 to 30F 0 6 to 16 7C SPDT Relay Output 120V 208 to 240V Horsepower 1 2 1 2 Full Load 9 8A 4 9A Locked Rotor 58 8A 29 4A Non Inductive 10A at...