Johnson Controls Unitary Products

COOLING OPERATION

First-Stage Cooling Operation

During first-stage cooling operation, the control will receive a thermostat
signal at the Y1 terminal.  The control will energize the M compressor
output terminal.  This signal energizes the coil on the compressor con-
tactor causing the compressor to run.

Second Stage Cooling Operation

During second-stage cooling operation, the control will receive a ther-
mostat signal from Y1 and Y2 inputs.  The control will energize both the
M and M2 compressor output terminals.  The M signal energizes the
compressor contactor causing the compressor to run.  The M2 signal
applies 24VAC to the rectifier plug for the compressor solenoid allowing
the compressor to operate in second stage.

HIGH-PRESSURE SWITCH FAULT

The AC Unit is equipped with a high-pressure switch that is connected
to the control at the HPS terminals.  If the high-pressure switch opens
for more than 40 milliseconds, the control will de-energize the compres-
sor and store and display the appropriate fault code.  If the pressure
switch closes and a thermostat call for compressor operation is present,
the control will apply the five-minute anti-short cycle delay timer and
start the compressor when the timer expires.  The control will ignore the
high pressure switch for 10 seconds following a call for compressor
operation to avoid nuisance errors.  If a call for compressor operation is
initiated while the high-pressure switch is open, the control will use the
logic associated with a high-pressure switch opening during a call for
compressor operation.

When the compressor is started following a high-pressure switch fault,
the control will start a six-hour timer based on accumulated compressor
run time.  If the control senses another opening of the high-pressure
switch before the timer expires, it will cause a soft lockout condition.
The second opening of the high-pressure switch must be greater than
160 milliseconds for the lockout to occur.  If the second opening is
between 40 and 160 milliseconds, the control will de-energize the com-
pressor but not cause a soft lockout condition.  If the control does not
sense a second high-pressure switch opening before the six-hour timer
expires, the timer and counter will be reset.

LOW-PRESSURE SWITCH FAULT

The AC unit is equipped with a low-pressure switch which is connected
to the control at the LPS terminals.  If the low-pressure switch opens for
more than five seconds, the control will cause a soft lockout condition
and display the appropriate fault codes.  If the control experiences mul-
tiple soft lockouts the control will enter a hard lockout as described in
another section of this document.  However, the control will ignore the
low pressure switch input and not cause a soft lockout condition if it
opens during the following conditions.

First two minutes of compressor operation.

While TEST input pins are shorted while any thermostat input Y1
or Y2 signal is being received.

OUTDOOR AMBIENT TEMPERATURE SENSOR

Ambient temperature sensor is used in communication applications
only. It is used to display outdoor temperature to the home owner via
the communicating thermostat.

Has no effect on operation.

Not required for operation, but a fault code will be displayed when
sensor is not connected or if sensor is shorted.

Summary of Contents for 18 SEER - AC8B

Page 1: ...expansion valve or an orifice liquid feed sized for the most common usage The orifice size and or refrigerant charge may need to be changed for some system combinations elevation differences or total line lengths See Tabular Data Sheet provided in unit literature packet for charge requirements Refer to Application Data covering General Piping Recommendations and Refrigerant Line Length Part Number...

Page 2: ... both the indoor and outdoor unit Observe all limitations and clearance requirements The outdoor unit must have sufficient clearance for air entrance to the condenser coil for air discharge and for service access See Figure 1 NOTE For multiple unit installations units must be spaced a minimum of 18 inches apart coil face to coil face If the unit is to be installed on a hot sun exposed roof or a bl...

Page 3: ... 61920 000 for installing tubing of longer lengths and elevation differences NOTE Using a larger than specified line size could result in oil return problems Using too small a line will result in loss of capacity and other problems caused by insufficient refrigerant flow Slope horizontal vapor lines at least 1 every 20 feet toward the outdoor unit to facilitate proper oil return PRECAUTIONS DURING...

Page 4: ...em just touches the chamfered retaining wall Connect the refrigerant lines using the following procedure 1 Remove the cap and Schrader core from both the liquid and vapor service valve service ports at the outdoor unit Connect low pres sure nitrogen to the liquid line service port 2 Braze the liquid line to the liquid valve at the outdoor unit Be sure to wrap the valve body with a wet rag Allow th...

Page 5: ...hraeder fitting and an additional 1 3 turn to seal 7 Install the TXV bulb to the vapor line near the equalizer line using the bulb clamp s furnished with the TXV assembly Ensure the bulb is making maximum contact a Bulb should be installed on a horizontal run of the vapor line if possible The bulb should be installed on top of the line b If bulb installation is made on a vertical run the bulb shou...

Page 6: ...n seal the hole in the wall at the thermostat with permagum or equivalent to prevent air drafts affecting the operation of in the thermostat FIELD CONNECTIONS CONTROL WIRING SERIAL COMMUNICATION 1 The Communications Harness is provided with the communicating thermostat 2 Route low voltage four conductor shielded thermostat communica tions harness into junction box and connect to communications por...

Page 7: ...thermostat owner s manual for this procedure Manual setting of the airflow jumpers on the ID equipment is not necessary with the communicating thermostat FIGURE 7 CFM Selection Board HEAT DELAY COOL ADJUST A B C D A B C D LED 2 FIGURE 8 Communicating AC with Communicating Air Handler or Furnace FIGURE 9 Communicating AC with Non Communicating Air Handler or Furnace using Communicating Interface Co...

Page 8: ...mpressor Y2 Second Stage Compressor External Humidistat Optional Open on Humidity Rise 2 Connection of the C terminal 24 Volt common is optional when used with batteries Thermostat Installer Setup 0170 System Type must be set to 8 2 Heat 2 Cool Multistage Conventional Connection of the C terminal 24 volt common is optional when used with batteries Thermostat Installer Setup 1 System Type must be s...

Page 9: ...DHUM jumper to YES if humidistat is to be used G L 8 9 V F L 8 9 V PV 8 9 ID MODELS TWO STAGE AIR CONDITIONER C 24 Volt Common R 24 Volt Hot Y1 First Stage Compressor Y2 Second Stage Compressor External Humidistat Optional Open on Humidity Rise 24VAC Humidifier Optional External Humidistat Optional Open on Humidity Rise 2 2 Part Number S1 2HU16700124 2 C 24 Volt Common R 24 Volt Hot Y First Stage ...

Page 10: ... Stage Compressor VARIABLE SPEED MODULATING FURNACE CONTROL G Fan VARIABLE SPEED MODULATING FURNACE Y Y2 Second or Full Stage Compressor HUM Dehumidification Open on Humidity Rise W Modulating Heat Part Numbers SAP Legacy 171334 031 09153 1 1 Move HUMIDISTAT jumper to YES if humidistat is to be used FL9C FC9C PC9 ID MODELS External Humidistat Optional Open on Humidity Rise 24VAC Humidifier Optiona...

Page 11: ... 1 Move HUMIDISTAT jumper to YES if humidistat is to be used FL9C FC9C PC9 ID MODELS External Humidistat Optional Open on Humidity Rise 24VAC Humidifier Optional External Humidistat Optional Open on Humidity Rise 2 2 Part Number S1 2HU16700124 2 C 24 Volt Common R 24 Volt Hot Y First Stage Compressor Y2 Second Stage Compressor G Fan DN22C00124 THERMOSTAT W2 Second Stage Heat C 24 Volt Common R 24 ...

Page 12: ...with batteries Thermostat Installer Setup 1 System Type must be set to 6 2 Heat 2 Cool Multistage Conventional COM 24 Volt Common R 24 Volt Hot W1 First Stage Heat W2 Second Stage Heat Y1 Single Stage Compressor Y Y2 Second or Full Stage Compressor O Reversing Valve Energized in Cool X L Malfunction Light HUM Humidity Switch Open on Humidity Rise VARIABLE SPEED AIR HANDLER CONTROL G Fan VARIABLE S...

Page 13: ...t Common is optional when used with batteries COM 24 Volt Common R 24 Volt Hot W1 First Stage Heat W2 Second Stage Heat Y1 Single Stage Compressor Y Y2 Second or Full Stage Compressor O Reversing Valve Energized in Cool X L Malfunction Light HUM Humidity Switch Open on Humidity Rise VARIABLE SPEED AIR HANDLER CONTROL G Fan VARIABLE SPEED AIR HANDLER 1 AV ID MODELS SV MV EAC 24VAC out Electronic Ai...

Page 14: ... line charge using the tabular data sheet if line length is greater than 15 feet 4 Total system charge item 1 item 2 item 3 5 Permanently stamp the unit data plate with the total amount of refrigerant in the system Use the following subcooling charging method whenever additional refrigerant is required for the system charge A superheat charging method is not suitable for TXV equipped systems Measu...

Page 15: ... for three seconds while the thermostat is calling for compressor opera tion Y1 input signal energized LOW VOLTAGE DETECTION The control monitors the transformer secondary 24 VAC voltage and provides low voltage protection for the AC unit and its components In particular the control prevents contactor chatter during low voltage con ditions If the voltage drops below approximately 19 VAC the contro...

Page 16: ... present Control behavior with system master signals present 2 No response No response 2 Display compressor type TS Ultratech or single stage compressor Ignore LPS Bypass ASCD Reduce timer to zero immediately If Y1 thermostat or communication is present and the high pressure switch is closed contactors will be energized Clear soft lockout Clear soft lockout Clear hard lockout Clear hard lockout Re...

Page 17: ...to be reset when the thermostat is satis fied or when the thermostat is set to SYSTEM OFF and back to HEAT or COOL mode 2 The TEST terminals are shorted for more than two seconds When the soft lockout condition is reset the control will stop displaying the fault code and will respond to thermostat inputs normally Hard Lockout If four soft lockouts occur within a twelve hour period the control will...

Page 18: ...pening during a call for compressor operation When the compressor is started following a high pressure switch fault the control will start a six hour timer based on accumulated compressor run time If the control senses another opening of the high pressure switch before the timer expires it will cause a soft lockout condition The second opening of the high pressure switch must be greater than 160 m...

Page 19: ...501562 UIM A 0909 Johnson Controls Unitary Products 19 SECTION IX WIRING DIAGRAM FIGURE 16 Wiring Diagram ...

Page 20: ...nge without notice Published in U S A 501562 UIM A 0909 Copyright 2009 by Johnson Controls Inc All rights reserved Supersedes 347269 UIM A 0108 Johnson Controls Unitary Products 5005 York Drive Norman OK 73069 NOTES ...

Reviews: