Johnson Controls 15 SEER - YZE / HC5B / HL5B SERIES Installation Manual Download Page 4

501054-UIM-A-0909

4

Johnson Controls Unitary Products

PRECAUTIONS DURING LINE INSTALLATION

1.

Install the lines with as few bends as possible. Care must be taken
not to damage the couplings or kink the tubing. Use clean hard
drawn copper tubing where no appreciable amount of bending
around obstruction is necessary. If soft copper must be used, care
must be taken to avoid sharp bends which may cause a restriction.

2.

The lines should be installed so that they will not obstruct service
access to the coil, air handling system or filter.

3.

Care must also be taken to isolate the refrigerant lines to minimize
noise transmission from the equipment to the structure.

4.

The vapor line must be insulated with a minimum of 1/2" foam rub-
ber insulation (Armaflex or equivalent). Liquid lines that will be
exposed to direct sunlight and/or high temperatures must also be
insulated.

Tape and suspend the refrigerant lines as shown. DO NOT allow tube
metal-to-metal contact. See Figure 2.

5.

Use PVC piping as a conduit for all underground installations as
shown in Figure 3. Buried lines should be kept as short as possible
to minimize the build up of liquid refrigerant in the vapor line during
long periods of shutdown

6.

Pack fiberglass insulation and a sealing material such as perma-
gum around refrigerant lines where they penetrate a wall to reduce
vibration and to retain some flexibility.

7.

See Form 690.01-AD1V for additional piping information.

PRECAUTIONS DURING BRAZING OF LINES

All outdoor unit and evaporator coil connections are copper-to-copper
and should be brazed with a phosphorous-copper alloy material such
as Silfos-5 or equivalent. DO NOT use soft solder. The outdoor units
have reusable service valves on both the liquid and vapor connections.
The total system refrigerant charge is retained within the outdoor unit
during shipping and installation. The reusable service valves are pro-
vided to evacuate and charge per this instruction.

Serious service problems can be avoided by taking adequate precau-
tions to assure an internally clean and dry system.

PRECAUTIONS DURING BRAZING SERVICE VALVE

Precautions should be taken to prevent heat damage to service valve
by wrapping a wet rag around it as shown in Figure 4. Also, protect all
painted surfaces, insulation, and plastic base during brazing. After braz-
ing cool joint with wet rag.

Valve can be opened by removing the plunger cap and fully inserting a
hex wrench into the stem and backing out counter-clockwise until valve
stem just touches the chamfered retaining wall.

Connect the refrigerant lines using the following procedure:

1.

Remove the cap and Schrader core from both the liquid and vapor
service valve service ports at the outdoor unit. Connect low pres-
sure nitrogen to the liquid line service port.

2.

Braze the liquid line to the liquid valve at the outdoor unit. Be sure
to wrap the valve body with a wet rag. Allow the nitrogen to con-
tinue flowing. Refer to the Tabular Data Sheet for proper liquid line
sizing.

3.

Carefully remove the rubber plugs from the evaporator liquid and
vapor connections at the indoor coil.

4.

Braze the liquid line to the evaporator liquid connection. Nitrogen
should be flowing through the evaporator coil.

 FIGURE 2: 

Tubing Hanger

 FIGURE 3: 

Underground Installation

Liquid
Line

Incorrect

Correct

Tape

Sheet Metal Hanger

Insulated Vapor Line

TO INDOOR COIL

TO O UTDOOR UNIT

LIQUID LINE

CAP

PVC

CONDUIT

INSULATED

VAPOR LINE

Dry nitrogen should always be supplied through the tubing while it
is being brazed, because the temperature required is high enough
to cause oxidation of the copper unless an inert atmosphere is pro-
vided. The flow of dry nitrogen should continue until the joint has
cooled. Always use a pressure regulator and safety valve to insure
that only low pressure dry nitrogen is introduced into the tubing.
Only a small flow is necessary to displace air and prevent oxidation.

This is not a backseating valve. The service access port has a
valve core. Opening or closing valve does not close service access
port.
If the valve stem is backed out past the chamfered retaining wall,
the O-ring can be damaged causing leakage or system pressure
could force the valve stem out of the valve body possibly causing
personal injury.

 FIGURE 4: 

Heat Protection

The evaporator is pressurized.

Summary of Contents for 15 SEER - YZE / HC5B / HL5B SERIES

Page 1: ...lable with a thermal expansion valve or an orifice liquid feed sized for the most common usage The orifice size and or refrigerant charge may need to be changed for some indoor out door unit combinati...

Page 2: ...ons units must be spaced a minimum of 18 inches apart Coil face to coil face If the unit is to be installed on a hot sun exposed roof or a black topped ground area the unit should be raised sufficient...

Page 3: ...for O E M replacement driers PIPING CONNECTIONS The outdoor unit must be connected to the indoor coil using field sup plied refrigerant grade copper tubing that is internally clean and dry Units shoul...

Page 4: ...an and dry system PRECAUTIONS DURING BRAZING SERVICE VALVE Precautions should be taken to prevent heat damage to service valve by wrapping a wet rag around it as shown in Figure 4 Also protect all pai...

Page 5: ...ows a Select a location on the vapor line for insertion of the equal izer line which will not interfere with TXV bulb placement b Use an awl to punch through the suction tube and insert the awl to a d...

Page 6: ...trol wiring NEC Class 2 from the outdoor unit to the indoor unit and thermostat NOTE To eliminate erratic operation seal the hole in the wall at the thermostat with permagum or equivalent to prevent a...

Page 7: ...ded air flow settings for each size condensing unit Set the cooling speed per the instructions for the air handler or furnace by selecting the correct COOL and ADJ taps Verify the airflow using the LE...

Page 8: ...rst Stage Aux Heat W2 Second Stage Aux Heat DHM Dehumidistat HM Humidistat O Reversing Valve Energized in Cool Change FFuel jumper on the heat pump control to ON Part Numbers SAP Legacy 126768 031 091...

Page 9: ...umper to YES if humidistat is to be used PV 8 9 ID MODELS F L 8 9 V YORKGUARD VI CONTROL G L 8 9 V YZE OD MODELS YZH H 5 H 8 C 24 Volt Common R 24 Volt Hot Y1 First Stage Compressor O Reversing Valve...

Page 10: ...cy 159481 031 09157 2 COM 24 Volt Common R 24 Volt Hot W1 First Stage Aux Heat W2 Second Stage Aux Heat Y1 Single Stage Compressor Y Y2 Second or Full Stage Compressor O Reversing Valve Energized in C...

Page 11: ...em Type must be set to 12 3 Heat 2 Heat Pump Thermostat Installer Setup 0190 Changeover Valve must be set to 0 O B terminal Energized in Cooling Thermostat Installer Setup 0200 Backup Heat Source must...

Page 12: ...Stage Aux Heat DHM Dehumidistat HM Humidistat O Reversing Valve Energized in Cool C 24 Volt Common R 24 Volt Hot Y1 Single Stage Compressor VARIABLE SPEED MODULATING FURNACE CONTROL G Fan VARIABLE SPE...

Page 13: ...95 031 01996 340512 031 09178 1 PC 8 9 ID MODELS FC 8 9 C FL 8 9 C YZE OD MODELS YZH H 5 H 8 C 24 Volt Common R 24 Volt Hot Y1 First Stage Compressor O Reversing Valve Energized in Cool L Malfunction...

Page 14: ...ging is required during heating operation the unit must be evacuated and charge weighed in per the marking on the rating plate For the cooling operation the recommended subcooling is typically around...

Page 15: ...ressor is equipped with a crankcase heater to prevent the migration of refrigerant to the compressor during the OFF cycle The heater is energized only when the unit is not running If the main switch i...

Page 16: ...ished in U S A 501054 UIM A 0909 Copyright 2009 by Johnson Controls Inc All rights reserved Supersedes 361811 UIM A 0208 Johnson Controls Unitary Products 5005 York Drive Norman OK 73069 SECTION X WIR...

Reviews: