Johnson Controls 15 SEER - YZE / HC5B / HL5B SERIES Installation Manual Download Page 1

501054-UIM-A-0909

R-410A
OUTDOOR SPLIT-SYSTEM 
HEAT PUMP

MODELS: 15 SEER - YZE / HC5B / HL5B SERIES
2 TO 5 TONS

INSTALLATION MANUAL

LISTED

ISO 9001

Certified Quality

Management System

TABLE OF CONTENTS

GENERAL  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
SAFETY  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
UNIT INSTALLATION  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
INSTALLATIONS REQUIRING TXV  . . . . . . . . . . . . . . . . . . . . . . . . . . 5
ELECTRICAL CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

EVACUATION   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  14
SYSTEM CHARGE   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  14
SYSTEM OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  15
INSTRUCTING THE OWNER   . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  15
WIRING DIAGRAM   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  16

LIST OF FIGURES

Typical Installation with Required Clearances  . . . . . . . . . . . . . . . . . . . 3
Tubing Hanger  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Underground Installation   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Heat Protection   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Typical Field Wiring   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Communications Harness Connection  . . . . . . . . . . . . . . . . . . . . . . . . . 6
CFM Selection Board  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Communicating HP with Communicating Air Handler or Furnace  . . . . 7
Communicating HP with Non-Communicating Air Handler 
or Furnace using Communicating Interface Control . . . . . . . . . . . . . . . 7
Thermostat Wiring – Two-Stage Heat Pumps - 
Two-Stage Variable Speed Furnaces   . . . . . . . . . . . . . . . . . . . . . . . . . 8

Thermostat Wiring – Two-Stage Heat Pump - 
Two-Stage Variable Speed Furnaces . . . . . . . . . . . . . . . . . . . . . . . . .  9
Thermostat Wiring – Two-Stage Heat Pump - 
Variable Speed Air Handler   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  10
Thermostat Wiring – Two-Stage Heat Pump - 
Variable Speed Air Handler   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  11
Thermostat Wiring – Two-Stage Heat Pump - 
Variable Speed Modulating Furnace   . . . . . . . . . . . . . . . . . . . . . . . .  12
Thermostat Wiring – Two-Stage Heat Pump - 
Variable Speed Modulating Furnace   . . . . . . . . . . . . . . . . . . . . . . . .  13
Heat Pump Flow Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  14

Wiring Diagram 16

LIST OF TABLES

Defrost Initiate Curves   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15

R-410A Saturation Properties  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

SECTION I: GENERAL

The outdoor units are designed to be connected to a matching indoor
coil with sweat connect lines. Sweat connect units are factory charged
with refrigerant for a matching indoor coil plus 15 feet of field supplied
lines.

Matching indoor coils are available with a thermal expansion valve or
an orifice liquid feed sized for the most common usage. The orifice size
and/or refrigerant charge may need to be changed for some indoor-out-
door unit combinations, elevation differences or total line lengths. Refer
to Application Data covering “General Piping Recommendations and
Refrigerant Line Length” (Part Number 036-61920-001).

SECTION II: SAFETY

This is a safety alert symbol. When you see this symbol on
labels or in manuals, be alert to the potential for personal
injury.

Understand and pay particular attention to the signal words 

DANGER

,

WARNING

, or 

CAUTION

DANGER 

indicates an 

imminently

 hazardous situation, which, if not

avoided, 

will result in death or serious injury

.

WARNING 

indicates a 

potentially

 hazardous situation, which, if not

avoided, 

could result in death or serious injury

.

CAUTION 

indicates a potentially hazardous situation, which, if not

avoided 

may result in minor or moderate injury

. It is also used to

alert against unsafe practices and hazards involving only property dam-
age

Improper installation may create a condition where the operation of
the product could cause personal injury or property damage.
Improper installation, adjustment, alteration, service or mainte-
nance can cause injury or property damage. Refer to this manual
for assistance or for additional information, consult a qualified con-
tractor, installer or service agency.

This product must be installed in strict compliance with the
enclosed installation instructions and any applicable local, state,
and national codes including, but not limited to building, electrical,
and mechanical codes.

 R-410A systems operate at higher pressures than R-22 systems.
Do not use R-22 service equipment or components on R-410A
equipment. Service equipment 

Must Be Rated 

for R-410A.

Summary of Contents for 15 SEER - YZE / HC5B / HL5B SERIES

Page 1: ...lable with a thermal expansion valve or an orifice liquid feed sized for the most common usage The orifice size and or refrigerant charge may need to be changed for some indoor out door unit combinati...

Page 2: ...ons units must be spaced a minimum of 18 inches apart Coil face to coil face If the unit is to be installed on a hot sun exposed roof or a black topped ground area the unit should be raised sufficient...

Page 3: ...for O E M replacement driers PIPING CONNECTIONS The outdoor unit must be connected to the indoor coil using field sup plied refrigerant grade copper tubing that is internally clean and dry Units shoul...

Page 4: ...an and dry system PRECAUTIONS DURING BRAZING SERVICE VALVE Precautions should be taken to prevent heat damage to service valve by wrapping a wet rag around it as shown in Figure 4 Also protect all pai...

Page 5: ...ows a Select a location on the vapor line for insertion of the equal izer line which will not interfere with TXV bulb placement b Use an awl to punch through the suction tube and insert the awl to a d...

Page 6: ...trol wiring NEC Class 2 from the outdoor unit to the indoor unit and thermostat NOTE To eliminate erratic operation seal the hole in the wall at the thermostat with permagum or equivalent to prevent a...

Page 7: ...ded air flow settings for each size condensing unit Set the cooling speed per the instructions for the air handler or furnace by selecting the correct COOL and ADJ taps Verify the airflow using the LE...

Page 8: ...rst Stage Aux Heat W2 Second Stage Aux Heat DHM Dehumidistat HM Humidistat O Reversing Valve Energized in Cool Change FFuel jumper on the heat pump control to ON Part Numbers SAP Legacy 126768 031 091...

Page 9: ...umper to YES if humidistat is to be used PV 8 9 ID MODELS F L 8 9 V YORKGUARD VI CONTROL G L 8 9 V YZE OD MODELS YZH H 5 H 8 C 24 Volt Common R 24 Volt Hot Y1 First Stage Compressor O Reversing Valve...

Page 10: ...cy 159481 031 09157 2 COM 24 Volt Common R 24 Volt Hot W1 First Stage Aux Heat W2 Second Stage Aux Heat Y1 Single Stage Compressor Y Y2 Second or Full Stage Compressor O Reversing Valve Energized in C...

Page 11: ...em Type must be set to 12 3 Heat 2 Heat Pump Thermostat Installer Setup 0190 Changeover Valve must be set to 0 O B terminal Energized in Cooling Thermostat Installer Setup 0200 Backup Heat Source must...

Page 12: ...Stage Aux Heat DHM Dehumidistat HM Humidistat O Reversing Valve Energized in Cool C 24 Volt Common R 24 Volt Hot Y1 Single Stage Compressor VARIABLE SPEED MODULATING FURNACE CONTROL G Fan VARIABLE SPE...

Page 13: ...95 031 01996 340512 031 09178 1 PC 8 9 ID MODELS FC 8 9 C FL 8 9 C YZE OD MODELS YZH H 5 H 8 C 24 Volt Common R 24 Volt Hot Y1 First Stage Compressor O Reversing Valve Energized in Cool L Malfunction...

Page 14: ...ging is required during heating operation the unit must be evacuated and charge weighed in per the marking on the rating plate For the cooling operation the recommended subcooling is typically around...

Page 15: ...ressor is equipped with a crankcase heater to prevent the migration of refrigerant to the compressor during the OFF cycle The heater is energized only when the unit is not running If the main switch i...