403134-YIM-E-0311
Johnson Controls Unitary Products
21
060
(5.0)
208-1-60 28.8 145.0
45.0
2.3
7.6
0.0
None
-
-
-
45.9
60
E05
4.0
1
19.2
45.9
60
E07
5.6
1
26.9
45.9
60
E10
8.0
1
38.5
57.6
70
E15
11.9
2
57.2
81.0
90
E20
15.9
2
76.4
105.1
110
E30
22.2
2
106.7
142.9
150
230-1-60 28.8 145.0
45.0
2.3
7.6
0.0
None
-
-
-
45.9
60
E05
5.3
1
22.1
45.9
60
E07
7.5
1
31.3
48.6
60
E10
10.6
1
44.2
64.7
70
E15
15.9
2
66.3
92.3
100
E20
21.2
2
88.3
119.9
125
E30
29.6
2
123.3
163.7
175
208-3-60 17.6 123.0
27.5
2.3
7.6
0.0
None
-
-
-
31.9
40
E05
4.0
1
11.1
31.9
40
E07
5.6
1
15.5
31.9
40
E10
8.0
1
22.2
37.3
45
E15
11.9
2
33.0
50.8
60
E20
15.9
2
44.1
64.7
70
E30
22.2
2
61.6
86.5
90
230-3-60 17.6 123.0
27.5
2.3
7.6
0.0
None
-
-
-
31.9
40
E05
5.3
1
12.7
31.9
40
E07
7.5
1
18.0
32.1
40
E10
10.6
1
25.5
41.4
45
E15
15.9
2
38.2
57.3
60
E20
21.2
2
51.0
73.2
80
E30
29.6
2
71.2
98.5
100
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
ZR036-060 Without Powered Convenience Outlet (Direct Drive) (Continued)
Size
(Tons)
Volt
Compressors
(each)
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Conv
Outlet
Electric Heat Option
MCA
1
(Amps)
Max
Fuse
2
/
Breaker
3
Size
(Amps)
RLA
LRA
MCC
FLA
FLA
FLA
Model
kW
Stages
Amps