background image

1.  Operating control
2.  Burner Pressure Adjuster
3.  Outlet Pressure test point

Fig. 4

Multifunctional Control

6.4

MAIN BURNER PRESSURE TEST:

NOTE: AIR HEATER BURNERS ARE FACTORY SET TO PROVIDE A NOMINAL HIGH PRESSURE OUTPUT AS
DETAILED IN SUB PARA 1.2

6.4.1

Referring to Table 2 and Fig. 4 below, ensure that the pressure test gauge indicates the correct burner pressure,
resetting if required as follows:
a.

At the Multifunctional control:
i.

Remove the Burner Pressure Adjuster cover.

ii.

Set the Burner Pressure Adjuster to provide a pressure test gauge indication for the correct burner
pressure as detailed in Table 2.

iii.

Refit the Burner Pressure Adjuster cover.

6.4.2

Apply the pressure set arrow to indicate the appropriate burner pressure on the data badge.

6.5

EXTINGUISHING OF PILOT AND MAIN BURNERS:

6.5.1

On the Multifunctional control, rotate the OPERATING CONTROL clockwise  to the ‘

l

’  position and ensure that

the OPERATING CONTROL fully resets, and both the Pilot and Main Burners are extinguished.

6.5.2

On the Multifunctional control, remove the pressure test gauge and refit the Outlet Pressure test point cover.

6.6

TEMPERATURE RISE CHECKS:

6.6.1

Ignite Pilot and Main burners and allow 15 minutes for stability before continuing.

6.6.2

Check temperature rise across heater is between 45

o

C - 55

o

C, setting fan speed as follows:

i.

SYSTEM E-T heaters:  System E-T provides a fan speed corresponding to the above temperature rise, if
the appliance is to be set to operate at the minimum rate and the ducting has been sized accordingly, set
the ‘RATE SWITCH’ to ‘

MIN

’, thus reducing the fan speed.

7

18

Sit

EV2

1

2

3

Fig. 5

SYSTEM E-T Electronic module

Diagnostic LED

MAIN BURNER NOT CYCLING

(

ROOM TEMPERATURE TOO HIGH)

REPLACE

MULTIFUNCTIONAL

CONTROL

N

Y

REPLACE

ELECTRONICS

MODULE

DISCONNECT

MULTIFUNCTIONAL

CONTROL AT

TERMINAL 15

N

DOES

BURNER

GO OUT?

DISCONNECT

THERMISTA-STAT

REPLACE

THERMISTA-STAT

Y

DOES

BURNER

GO OUT?

FAN CONTINUES TO RUN, OR CYCLES AFTER HEATING IS TURNED OFF

DISCONNECT

TERMINALS ‘17’ &’18’

Y

N

REPLACE FAN DELAY/

LIMIT CONTROL

REPLACE

ELECTRONIC

MODULE

DOES

FAN

RUN ?

Summary of Contents for HI-SPEC J25RS Series

Page 1: ...be left with the User or adjacent to the Gas Meter 1 24 1 2 3 4 5 6 7 8 9 10 11 12 10 SHORT LIST OF SPARES HI SPECJ25RS KEY G CNo MFR SNo DESCRIPTION QTY 1 232961 BOS02064 Fan Assembly 1 2 245508 R25...

Page 2: ...ctrical supplies 2 3 For service access a minimum of 300mm 12 ins is required at the front of the heater Space must also be allowed in a compartment installation to permit the removal of the heater Th...

Page 3: ...screws previously removed 5 1 7 Refit the air circulation fan front cover and air filter 5 1 8 Using suitable material manufacture a plate to cover the original return air opening in the top of the ai...

Page 4: ...screw provided Note The orifice cup must NOT be used in balanced flue applications 4 21 Fig 3 Fitting of orifice cup Fig 7a SYSTEM E T CIRCUIT DIAGRAM FRONT SIDE 1234 1234 1234 1234 1234 1234 1234 12...

Page 5: ...as a room thermostat c BASIC CONTROL MODELS A 24V room thermostat not supplied that complies with BS800 BS3955 and BS4201 is essential to ensure close control of comfort conditions An anticipator is l...

Page 6: ...n anti clockwise to the SPARK symbol Press and hold the OPERATING CONTROL and whilst observing the Pilot Burner repeatedly press the Piezo igniter button until the Pilot burner ignites 6 3 5 After 20...

Page 7: ...lly resets and both the Pilot and Main Burners are extinguished 6 5 2 On the Multifunctional control remove the pressure test gauge and refit the Outlet Pressure test point cover 6 6 TEMPERATURE RISE...

Page 8: ...witch OFF the electrical supply to the air heater 6 8 8 Reconnect the air circulation fan at the terminal block 6 8 9 Hinge up the fan chamber door taking care to avoid causing damage to wiring and se...

Page 9: ...system by opening and closing warm air outlets 7 2 6 How to obtain summer air circulation 7 2 7 That the air grilles on the heater or heater compartment grilles and ventilators in the walls windows o...

Page 10: ...nstructions applicable to the appliance 8 2 BURNER AND CONTROL ASSEMBLY REMOVAL 8 2 1 Ensure that the Gas and Electrical supplies are switched OFF 8 2 2 Remove the appliance door 8 2 3 Disconnect igni...

Page 11: ...from the capacitor b 230V mains L N and E from connection block terminals 1 and 2 and Earth stud respectively c Thermista stat connections from connection block terminals 7 and 8 d Limit switch from c...

Page 12: ...n earth stud 8 13 4 Release the 2 x 4mm screws securing the Limit switch mounting plate and withdraw the control from the appliance by drawing the conductors through the grommet in the fan chamber flo...

Page 13: ...n earth stud 8 13 4 Release the 2 x 4mm screws securing the Limit switch mounting plate and withdraw the control from the appliance by drawing the conductors through the grommet in the fan chamber flo...

Page 14: ...from the capacitor b 230V mains L N and E from connection block terminals 1 and 2 and Earth stud respectively c Thermista stat connections from connection block terminals 7 and 8 d Limit switch from c...

Page 15: ...nstructions applicable to the appliance 8 2 BURNER AND CONTROL ASSEMBLY REMOVAL 8 2 1 Ensure that the Gas and Electrical supplies are switched OFF 8 2 2 Remove the appliance door 8 2 3 Disconnect igni...

Page 16: ...system by opening and closing warm air outlets 7 2 6 How to obtain summer air circulation 7 2 7 That the air grilles on the heater or heater compartment grilles and ventilators in the walls windows o...

Page 17: ...witch OFF the electrical supply to the air heater 6 8 8 Reconnect the air circulation fan at the terminal block 6 8 9 Hinge up the fan chamber door taking care to avoid causing damage to wiring and se...

Page 18: ...lly resets and both the Pilot and Main Burners are extinguished 6 5 2 On the Multifunctional control remove the pressure test gauge and refit the Outlet Pressure test point cover 6 6 TEMPERATURE RISE...

Page 19: ...n anti clockwise to the SPARK symbol Press and hold the OPERATING CONTROL and whilst observing the Pilot Burner repeatedly press the Piezo igniter button until the Pilot burner ignites 6 3 5 After 20...

Page 20: ...as a room thermostat c BASIC CONTROL MODELS A 24V room thermostat not supplied that complies with BS800 BS3955 and BS4201 is essential to ensure close control of comfort conditions An anticipator is l...

Page 21: ...screw provided Note The orifice cup must NOT be used in balanced flue applications 4 21 Fig 3 Fitting of orifice cup Fig 7a SYSTEM E T CIRCUIT DIAGRAM FRONT SIDE 1234 1234 1234 1234 1234 1234 1234 12...

Page 22: ...screws previously removed 5 1 7 Refit the air circulation fan front cover and air filter 5 1 8 Using suitable material manufacture a plate to cover the original return air opening in the top of the ai...

Page 23: ...ctrical supplies 2 3 For service access a minimum of 300mm 12 ins is required at the front of the heater Space must also be allowed in a compartment installation to permit the removal of the heater Th...

Page 24: ...be left with the User or adjacent to the Gas Meter 1 24 1 2 3 4 5 6 7 8 9 10 11 12 10 SHORT LIST OF SPARES HI SPECJ25RS KEY G CNo MFR SNo DESCRIPTION QTY 1 232961 BOS02064 Fan Assembly 1 2 245508 R25...

Reviews: