background image

www.johnsonandstarley.co.uk

20

Explain how, in the event of a fault, the appliance will display a fault code, emphasising that if a fault is indicated
they should note the fault code, turn off the appliance and contact a “competent person” which in normal circum-
stances would be a CORGI registered engineer.

Explain and demonstrate the function/operation of time/temperature controls and thermostatic radiator valves,
emphasising the economic use of the appliance.

If a programmer has been fitted, hand the user instructions that were supplied with the progammer to the occupier.

Point out the water pressure guage and explain what it indicates and that if the pressure falls over a period of time
when the system is cold, a water leak should be suspected and that a “competent person” should be contacted.

Emphasise the importance of a regular service and that servicing of the appliance MUST only be carried out by a
“competent person” which in normal circumstances would be a CORGI registered engineer.

As the installer you may wish to offer a service contract yourself, or alternatively you may wish to explain to the
occupier that they can take advantage of an extended warranty scheme offered by Johnson & Starley Ltd.

Reminder: following the commissioning and handover of the appliance, complete the Benchmark Log Book and
leave it with the occupier. 
5. SERVICING SCHEDULE

To ensure that the appliance gives continued operation that is both safe and efficient, it is necessary to carry out regu-
lar service checks and whilst the period between servicing will depend on the installation condition and the demands
placed upon the appliance, it is recommended that the appliance be serviced annually. 

NOTE: it is a statutory requirement that ALL work be carried out by a “competent person” which in normal circum-
stances would be a CORGI registered engineer.

5.1 Servicing Sequence:

Light the boiler and carry out a pre-service check, noting any operational faults. 

Check the gas consumption. 

Put the appliance in test mode and connect a suitable gas analyser to the sampling point on the top of the boiler
or into the flue terminal if access is possible
(optional test). 
For correct boiler operation, the CO/CO

2

content of

the flue gas should not be greater than 0.004 ratio. 
Check that the gas input is at least 90% of the
nominal. 

Clean the main burner. 

Clean the heat exchanger. 

Check the condition of the combustion chamber
insulation. Any cracked or damaged pieces should
be replaced. 

Wherever possible, remove and clean the conden-
sate 'S' trap (refer to section 6.12) and check the
drain for blockage. 

Check that the flue terminal is unobstructed and that the flue system is sealed correctly.

Note. In order to carry out either servicing or replacement of components the boiler front panel and sealing panel must
be removed. (Refer to section 6.2)
WARNING. Always turn OFF the gas supply at the gas service cock and switch OFF and disconnect the electricity sup-
ply to the appliance before servicing.

After completing the servicing or exchange of components always test for gas soundness and carry out functional
checks as described above.  

When work is complete, the sealing panel MUST be correctly refitted, ensuring that a good seal is made. 

WARNING: Do not operate the boiler if the sealing panel is not fitted!

lf, for any reason, the condensate 'S' trap has been removed ensure the trap is refilled with water before reassembling.

Complete the service section in the Benchmark log book.

Test Mode

To put the appliance in test mode, press both the 

MODE

and 

T

buttons together for a minimum of 3 seconds.

“TEST” will be displayed in the LCD lower right hand cor-
ner and the flow and return temperatures will be displayed
along with the flame current value. The appliance will stay
in test mode for 30 minutes and the remaining time left in
test mode will be displayed. Whilst in test mode, the
appliance overrides all temperature setting and runs at
minimum rate. Pressing the 

S

button will cause the

appliance to run at maximum rate, whilst still overriding
all temperature settings. Press RESET to take the appli-
ance out of test mode.

Summary of Contents for HE25S

Page 1: ... johnsonandstarley co uk Model HE25S GC No 41 416 02 Installation Maintenance and Service Instructions Tel 01604 762 881 Publication ZZ1186 1 Product Identification No 87B 074 High Efficiency System Boiler BS EN ISO 9001 2000 ...

Page 2: ...ilding Regulations Part L Part J in Scotland the boiler MUST be fitted in accordance with the manufacturer s instructions In order to demonstrate that that the installation of this appliance complies with current Building Regulations you should complete and sign the Benchmark log book Johnson Starley Ltd Rhosili Road Brackmills Northampton NN4 7LZ Tel 01604 762881 Fax 01604 767408 Sales Fax 01604 ...

Page 3: ...uilding The appliance is controlled by fully featured microprocessor based electronics that monitor each of the operational pro cedures An LCD display indicates the operational state of the appliance which illuminates for a short period when the user control is operated This starts with the full sequence automatic ignition and continues with monitoring the demand requirements of either the central...

Page 4: ...e an additional expansion vessel 2 2 Technical Data Table 2 1 General Data Nat Gas G20 LPG G31 Maximum Minimum Maximum Minimum Offset Pascal 3 0 Minus three Burner CO2 Case off 9 3 0 5 8 4 ref only 10 2 0 5 9 4 ref only Case on 9 5 0 5 8 6 ref only 10 4 0 5 9 6 ref only Table 2 2 Performance Data Nat Gas G20 LPG G31 Maximum Minimum Maximum Minimum CH Input Qm Net kW 25 5 7 14 25 5 7 29 Gross kW 28...

Page 5: ...iance This allows conversion between Natural gas G20 and LPG G31 Their supply pressures are 20 mbar and 37 mbar respectively For natural gas to LPG conversion kit number NG30 complete with instructions is available For LPG to natural gas conversion kit number LPG30 complete with instructions is available Statutory Requirements The appliance must be installed in accordance with the current editions...

Page 6: ...m to allow complete drain down The installation should be designed to operate with a flow temperature of up to 90 deg C Expansion Vessel The integral expansion vessel is pre charged to a pressure of between 0 5 and 1 0 bar This should be checked before the water system is filled Details below show the water system volume that is acceptable for this vessel If the system water volume is larger then ...

Page 7: ...l at maximum heat input 2 7 Domestic Hot Water System Requirements Domestic hot water circuits and their components must be in accordance with the relevant standards and water sup ply regulations Further guidance and recommendations can be found in the building regulations G17 to 24 and R17 to 24 Additional Expansion Vessel if required BOILER Drain Point Bypass if required Flow Control Valve Heati...

Page 8: ...ne and lower bracket as shown and using a light hammer tap the 8 tags over so that they form a secure assembly Lift the wall fixing plumbing jig up to the wall ensuring it is level and secure it with the screws provided The gas and water connections can now be made to the appropriate posi tions on the jig Should the heating pipes be required to exit vertically upwards there is a kit available It i...

Page 9: ...r 95 84 73 50 For systems having a larger capacity multiply the total system capacity in litres gallons by the factor to obtain the total minimum expansion vessel capacity required litres 0 0833 0 09 0 109 0 156 Internal soil and vent stack Min Dia 22mm No restriction on length Invert Boiler Trap 75mm min 450mm min Siphon if not already part of appliance Min Dia 22mm No restriction on length Sink ...

Page 10: ... from outside Fit the inner wall sealing disc Using the clamp arrangement join the flue to the turret ensuring all the seals are made correctly The terminal must be installed with the flue outlet at the top Brackets are provided for extended flues to locate and fix the flue in position should they be necessary Vertical Flues Flat roof Measure the distance between the appliance top and the outer su...

Page 11: ...100 60 Concentric Flue System The appliance is supplied with a standard flue kit that includes a horizontal flue complete with terminal tur ret and fitting kit Details of optional flue components are also listed along with their resistance in Pascals in order that flue length calculations can be made Horizontal and vertical concentric flues 60 100 diam eter with balanced terminals and vertical and...

Page 12: ...ric horizontal flue length measured from the centre line of the turret to the outside of the wall is 247mm The minimum vertical flue length is 1 14 m measured from the top of the appliance case to the top of the termi nal The minimum combined 80 twin flue length is 600mm Longer flues may be fitted however the input of the appliance will be reduced accordingly Elbows may be fitted within the flue s...

Page 13: ...8 Horizontal Side Flue Can be left or right Standard Flue Kit 500 mm Extension Fig 3 9 Offset Vertical Flue may be offset to the rear left or right Standard Flue Kit 500 mm Extension 90o Elbow Vertical Appliance Adaptor Vertical Terminal Fig 3 10 Offset Horizontal Rear Flue Can be offset to left or right Standard Flue Kit 90o Elbow 1m Extension Fig 3 11 Vertical Flue 1m Extension 500 mm Extension ...

Page 14: ...e LH RH or as shown Standard 90o elbow Fig 3 14 Raised Horizontal Air Vertical Flue Outlet offset Standard 90o and 45o elbows and standard vertical terminal standard 90o elbow Fig 3 13 Horizontal Air Duct Vertical Flue Duct Standard 90o elbow and standard vertical terminal Full details of twin flue components can be found in publication ZZ1191 ...

Page 15: ... terminal 1140 mm 1 x vertical terminal assembly Vertical 1000 0018930 5 1 x support bracket Vertical Appliance Adaptor 1 x Adaptor Vertical 1000 0018990 0 90 elbow 1 x Elbow Horizontal Vertical 1000 0018980 10 45 elbow 1 x Elbow Horizontal Vertical 1000 0018970 5 Flat Roof Weather Collar 1 x Aluminium circular flat roof seal Vertical 1000 0014900 N A Pitched Roof Weather Collar 1 x Plastic lead p...

Page 16: ...l System Controls Controls are available for outside temperature compensation and room temperature sensing These should be used to improve the heating system control They must be connected to the correct terminals as described in their own instructions A room thermostat MUST NOT be used with these controls 3 11 Fitting The Case Control Module Remove the case components from their packaging Fit the...

Page 17: ...ODE IGNITION ELECTRODE OTC OTC OPEN THERM GAS VALVE MAINS SWITCH PUMP FAN SYSTEM PRESSURE SENSOR MMI CVBC pwm in from CVBC tacho from CVBC r r g y g y g y g y b br bk bk b bk y r r y b r g y E b N br L p p b br br r b b pk gy gy b br b b r r WIRE COLOUR CODE br brown p purple b blue pk pink bk black y yellow r red g y green yellow gy grey ...

Page 18: ...r r b r r b b b br br b p p r b or b br b b y b r b b g y bk br or br b br L1 L2 N L3 PUMP PC CONNECTIONS MAINS SWITCH FAN PRESSURE SENSOR OPEN THERM OTC MAINS SUPPLY 230V 50Hz SPARK ELECTRODE FLAME DETECTION ELECTRODE FLUE THERMISTOR CH FLOW THERMISTOR CH RETURN THERMISTOR CVBC gy gy g y br b br or r bkbk y b r b r br L X1 X2 X3 X5 X4 N SL bk y MMI PCB pk br or br b b or br REMOVE THIS LINK TO FI...

Page 19: ...fan speed A stylised flame will be dis played when the flame is established If ignition does not take place during the first ignition attempt there will be a further 2 attempts If the burner has still not lit a fault code will be displayed and this may be due to air being present in the gas supply Pressing the reset button will initiate a second sequence of ignition attempts When the boiler lights...

Page 20: ... Check the gas consumption Put the appliance in test mode and connect a suitable gas analyser to the sampling point on the top of the boiler or into the flue terminal if access is possible optional test For correct boiler operation the CO CO2 content of the flue gas should not be greater than 0 004 ratio Check that the gas input is at least 90 of the nominal Clean the main burner Clean the heat ex...

Page 21: ... removed and slowly withdraw the complete assembly including the gas inlet pipe and the case seal As the assembly is withdrawn disconnect the two electrical connections from the fan Inspect and clean the spark ignition and flame sensing electrode removing any debris and oxidiza tion and check the spark gap and position of the spark electrode and the position of the flame sensing electrode Refer to...

Page 22: ...llowed by a two digit error code will be displayed ATTENTION The flip door at the bottom of the boiler is held in the closed posision by a concealed latch that has a push and release mechanism and is located on the upper edge of the door in the centre To gain access to the control panel apply light pressure on the upper edge of the flip door at the centre the latch will then release allowing the d...

Page 23: ...to earth Check sensor resistance 31 Boiler flow temperature sensor open circuit Temperature sensor not connected or failed Check wiring and connections Check sensor continuity 34 Low mains supply voltage Electrical supply fault to property Faulty wiring to appliance Check incoming mains supply and wiring to appliance 35 36 Power supply fault No fault on boiler Boiler power supply should be checked...

Page 24: ...ed door by removing the two screws and easing it to the left to disengage it from the LH side of internal casing 6 3 Control Panel complete Because of the complexity and delicate nature of the control PCB it is supplied as a complete kit with the plastic facia Remove the control panel as descibed at section 6 2 and fit the new assembly in reverse order 6 4 Electrical Switch Unscrew the metal cover...

Page 25: ...e drain point on the flow valve is connected to the appliance side Drain off the water from within the appliance using the drain valve remove the LH painted case side and unscrew the flexible hose connection from the expansion vessel Unscrew the upper retaining bracket and remove the expansion vessel Replace with a new component in reverse order 6 8 Pressure Relief Valve Close the CH flow and retu...

Page 26: ...bly Replace with a new component in reverse order 6 9 Primary Water Temperature Sensors 2 off Unplug the two wires from the temperature sensor to be replaced and unclip the sensor from the pipe Replace with a new component in reverse order ensuring it is fitted in the same position 6 10 Primary Water Pressure Sensor Close the CH flow and return valves ensuring the drain point on the flow valve is ...

Page 27: ...anger Unplug the multi pin plug connections from the top of the control and the fan Remove the assembly Remove the assembly to allow the burner to be withdrawn from the heat exchanger assembly Replace with a new component in reverse order Ensure the rotational position of the burner is correct Replace with a new component in reverse order ensuring that the grommet sealing the casing is correctly p...

Page 28: ...sembly NOTE the gas valve is factory preset and a replacement valve must only be supplied by Johnson Starley Ltd Remove the complete fan assembly as shown at section 6 18 and remove the 4 fixing screws holding the gas feed flange on the gas valve Remove the 2 fixing screws securing the venturi and gas valve to the fan and remove the assembly from the fan carefully removing the gasket Replace with ...

Page 29: ...H Pressure Sensor Clip O Ring 7 1000 0019115 H23 617 Condensate Siphon O Rings 2 Locknut 8 1000 0709655 H23 618 Ignition Electrode Gasket Screws 2 Item Part No GC No Description 9 1000 0709665 H23 619 Detection Electrode Gasket Screws 2 10 1000 0709675 H23 620 Burner and Small Seal 11 1000 0522575 H23 621 Main Ignition Control PCB CVBC 12 1000 0522645 H23 622 Flue Temp Sensor 13 1000 0522635 H23 6...

Page 30: ...www johnsonandstarley co uk 30 Notes ...

Page 31: ...www johnsonandstarley co uk 31 Notes ...

Page 32: ...www johnsonandstarley co uk 32 Johnson Starley www johnsonandstarley co uk Tel 01604 762 881 ...

Reviews: