Heat detector
HDv 300X TS
Operation- and installation manual
V1.0 18.08.2011
Ba.-Nr.: 53854
Seite 4 von 4
⑥
Function test
1.
Carry out a visual inspection. Check:
•
If the device exists
•
That the heat detector is not polluted by paint, any cover or dust for
example
•
If the heat detector is in a correct condition (nothing broken off)
If there are any claims of the above, replace the heat detector immediately.
2.
Carry out a sounder test. Therefore press the LED conductor pole for about
one second. A warning alarm sounds if the heat detector is operational.
3.
Replace all heat detectors after 10 years for new ones!
Please do not dispose the heat detector in the domestic waste.
⑦
Alarm muting
The alarm muting can be activated by pressing the test LED conductor pole of the
heat detector (1). The heat detector will mute for approx. 10 minutes and then reset
itself to the normal operation sensitivity level.
⑧
Alarm Memory
A registrated alarm will be stored in the heat detector for 24 hours. This is indicated
by 3 short flashes every 43 seconds. Press the “Alarm-Mute-Test-Button” (LED
conductor pole 6.2) to reset the alarm memory latch.
⑪
Operation- and alarm signals
⑫
Serial and production number
⑥
1
2
3
3
⑦
1
⑨
Batterie change
1.
Detach the heat detector by turning it counter clockwise.
2.
Connect the new battery to the heat detector (watch the polarity) and place it
into the intended bracket of the heat detector.
3.
Replace the heat detector back into the base and turn clockwise.
4.
Check if the LED conductor pole flashes.
5.
Carry out a sounder test. Press therefore the LED conductor pole for about
one second.
6.
A warning beep sounds if the heat detector is operational. If no alarm sounds
then the device is not functional. In this case check the battery and replace it.
If still no alarm sounds after pressing the test LED conductor pole again, then
the heat detector is defect and needs to be replaced.
⑬
Battery types
(We recommend a Lithium battery if using radio modules)
)
Recommended battery types: FDK CP-V9J, Ultralife U9 VL-J / -P, Panasonic Power
Alkaline 9V, Varta 4022 Alkaline 9V, Alkaline Xtreme 6LR61 9V.
Battery type
Alkaline:
Lithium:
* under normal conditions
** typical at 15°C – 20°C
Ø Lifetime ca.
typical 5 years
10 Years*
With radio module
868/433 MHz ca.
not
recommended
2 Years **
Ø Lifetime
⑨
1
2
3
4
5
6
⑩
Accessories: Radio module & Radio control panel
A) Wireless linking of the heat detector via radio module
The heat detector
HDv 300X TS
can be equipped with a wireless network module
868 MHz (Order No. 30933) for a wireless linking between each other and smoke
alarms. With a wireless module 433 MHz (Order No. 32488) it is possible to transmit
alarm signals to a radio control panel (SRC 3000, Order No.: 32487). These radio
modules are simple to install and can be also be installed after initial installation. For
further details see the corresponding manual.
B) Connection to the Instabus EIB or connection to external signaller
The heat detector
HDv 300X TS
can be connected to an EIB by a relay-module
(Order No. 30942). These radio modules are simple to install and can be also be
installed supplementary. For further details see the corresponding manual.
Manufacturer warranty
We provide warranty according to legal requirements. In case of fault functions, please
return the heat detector with a short fault description and your address to:
detectomat GmbH
An der Strusbek 5
D-22926 Ahrensburg (Germany)
Tel.: 04102 2114 60
Fax: 04102 2114 670
⑭
Technical data
Detection method: ............................................................................................. Thermal
Alarm indication: ................ optical (LED red) and acoustically signal tone >85 dB(A)/3m
Operating voltage (Direct current): ............................................................................. 9 V
Operating temperature range: ............................................................... -10°C to +60°C
Humidity: .................................................................................................. max. 95% RH
Max. monitored area:....................................................................... 60 m² to 6 m height
Responsively: ..................................................... Designed to comply EN 54-5 class A1
Protection class: ..................................................................................................... IP 30
Shelf life: .................................................................................................... max. 2 years
Weight: .................................................................................................................. 114 g
Dimension incl. base (Ø x H): ......................................................... max. 110 x 62,0 mm
Housing material: ................................................................................................... ABS
Thank you for your purchase and confidence in our products!
Function / Meaning
Signal tone
Red LED
Regular operation mode
No tone
Flashes every 40 seconds
Alarm condition
Loud interval tone in
0,5 second rhythm
Flashes every 0,5 second
Indication for low battery
Short interval tone
every 40 seconds
Flashes every 40 seconds
simultaneously with signal
tone
Alarm muting
No tone
Flashes every 10 seconds
Alarm memory active, an alarm
condition in the last 24 hours
No tone
Flashes 3x every 43 sec.
Sounder test,
No test of the measuring section
Loud interval tone
Flashes every 0.5 seconds
as long as the conductor
pole is pressed.