JOB detectomat HDv 300X TS Operation And Installation Manual Download Page 4

 

 

Heat detector 

HDv 300X TS

 

Operation- and installation manual 

 

 

 

V1.0  18.08.2011 

Ba.-Nr.: 53854 

Seite 4 von 4 

 

 Function test 

 

1.

 

Carry out a visual inspection. Check: 

 

If the device exists 

 

That the heat detector is not polluted by paint, any cover or dust for 

  

example 

 

If the heat detector is in a correct condition (nothing broken off) 

 

If there are any claims of the above, replace the heat detector immediately.  

 

2.

 

Carry out a sounder test. Therefore press the LED conductor pole for about 

one second. A warning alarm sounds if the heat detector is operational. 
 

3.

 

Replace all heat detectors after 10 years for new ones! 

Please do not dispose the heat detector in the domestic waste. 

⑦ 

Alarm muting 

The alarm muting can be activated by pressing the test LED conductor pole of the 

heat detector (1). The heat detector will mute for approx. 10 minutes and then reset 

itself to the normal operation sensitivity level. 

 Alarm Memory 

A registrated alarm will be stored in the heat detector for 24 hours. This is indicated 

 

by 3 short flashes every 43 seconds. Press the “Alarm-Mute-Test-Button” (LED 

 

conductor pole  6.2) to reset the alarm memory latch. 

  

 

 

Operation- and alarm signals 

 

 

 

 

 

 
 

 

 

 
 

 

 
 

 

 

 Serial and production number

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 Batterie change 

1.

 

Detach the heat detector by turning it counter clockwise. 

2.

 

Connect the new battery to the heat detector (watch the polarity) and place it 
into the intended bracket of the heat detector. 

3.

 

Replace the heat detector back into the base and turn clockwise. 

4.

 

Check if the LED conductor pole flashes. 

5.

 

Carry out a sounder test. Press therefore the LED conductor pole for about 
one second. 

6.

 

A warning beep sounds if the heat detector is operational. If no alarm sounds 

then the device is not functional. In this case check the battery and replace it. 
If still no alarm sounds after pressing the test LED conductor pole again, then 

the heat detector is defect and needs to be replaced.

 

 

 

 

Battery types 

 

(We recommend a Lithium battery if using radio modules)

)

 

 

Recommended battery types: FDK CP-V9J, Ultralife U9 VL-J / -P, Panasonic Power 
Alkaline 9V, Varta 4022 Alkaline 9V, Alkaline Xtreme 6LR61 9V. 

 

Battery type 

Alkaline: 

Lithium: 

*   under normal conditions  

**   typical at 15°C – 20°C 
 

Ø Lifetime ca. 

typical 5 years 

10 Years* 

With radio module 

868/433 MHz ca. 

not 

recommended 

2 Years ** 

Ø Lifetime 

 

 

 

 

 

 

 

 

 

 

Accessories: Radio module & Radio control panel 

 

A)   Wireless linking of the heat detector via radio module

 

 

The heat detector 

HDv 300X TS

 can be equipped with a wireless network module 

 

868 MHz (Order No. 30933) for a wireless linking between each other and smoke 

 

alarms. With a wireless module 433 MHz (Order No. 32488) it is possible to transmit 

 

alarm signals to a radio control panel (SRC 3000, Order No.: 32487). These radio 

 

modules are simple to install and can be also be installed after initial installation.  For 

 

further details see the corresponding manual. 

 

B)  Connection to the Instabus EIB or connection to external signaller  

 

The heat detector 

HDv 300X TS

  can be connected to an EIB by a relay-module 

  

(Order No. 30942). These radio modules are simple to install and can be also be 

 

installed supplementary. For further details see the corresponding manual. 

 

Manufacturer warranty  

We provide warranty according to legal requirements. In case of fault functions, please 

return the heat detector with a short fault description and your address to:  

 

 

detectomat GmbH 

An der Strusbek 5 

           

 

D-22926 Ahrensburg (Germany) 

Tel.: 04102 2114 60 

Fax: 04102 2114 670 

 

 

 Technical data 

 

Detection method: ............................................................................................. Thermal 
Alarm indication: ................ optical (LED red) and acoustically signal tone >85 dB(A)/3m  

Operating voltage (Direct current): ............................................................................. 9 V 

Operating temperature range: ............................................................... -10°C  to +60°C 
Humidity: .................................................................................................. max. 95% RH  

Max. monitored area:....................................................................... 60 m² to 6 m height 

Responsively:  ..................................................... Designed to comply EN 54-5 class A1 

Protection class: ..................................................................................................... IP 30 
Shelf life: .................................................................................................... max. 2 years 

Weight: .................................................................................................................. 114 g 

Dimension incl. base (Ø x H): ......................................................... max. 110 x 62,0 mm 

Housing material: ...................................................................................................  ABS 

 

 

 

 
 

 

 
 

Thank you for your purchase and confidence in our products! 

 

Function / Meaning 

Signal tone  

Red LED 

Regular operation mode 

No tone 

Flashes every 40 seconds 

Alarm condition 

Loud interval tone in 

0,5 second rhythm 

Flashes every 0,5 second 

Indication for low battery 

Short interval tone 

every 40 seconds 

Flashes every 40 seconds 

simultaneously with signal 

tone 

Alarm muting 

No tone 

Flashes every 10 seconds 

Alarm memory active, an alarm 

condition in the last 24 hours 

No tone 

Flashes 3x every 43 sec. 

Sounder test, 

No test of the measuring section 

Loud interval tone 

Flashes every 0.5 seconds 

as long as the conductor 

pole is pressed. 

 

 

Summary of Contents for detectomat HDv 300X TS

Page 1: ...erhafte Trag und Klebefähigkeit 2 Überprüfen Sie dass am Montageort keine Stromleitung verläuft Halten Sie einen Mindestabstand von 50 cm zu stromführenden Leitungen ein 3 Stellen Sie sicher dass der Thermowarnmelder durch den Bohrstaub nicht verschmutzt werden kann 4 Bohren Sie mit einem 6 mm Bohrer entsprechende Löcher mit einem Lochabstand von 67 mm bei Zwei Schrauben Montage verwenden Sie das ...

Page 2: ... 6LR61 9V Batterietyp Alkaline Lithium Ø Lebensdauer ca typisch 5 Jahre 10 Jahre unter normalen Voraussetzungen typisch bei 15 C 20 C mit Funkmodul 868 433 MHz ca Nicht empfohlen 2 Jahre Ø Lebensd 1 2 3 4 5 6 Zubehör Funkmodule Funkzentrale A Drahtlose Vernetzung des Thermowarnmelders mit Funkmodul Die Thermowarnmelder sind durch Einsetzen des Funkmoduls 868 MHz Best Nr 30933 auch untereinander dr...

Page 3: ...inimum distance of 50 cm from all conducting electrical cables Make sure that there are no electricity cables at location 3 Make sure not to pollute the heat detector when drilling the holes if installing the heat detector with an adhesive pad see chapter 13 Optional Accessories 4 Drill two 6 mm holes with a gap of 67 mm if using two screws You can use the detectors base as a hole template 5 Place...

Page 4: ...itions typical at 15 C 20 C Ø Lifetime ca typical 5 years 10 Years With radio module 868 433 MHz ca not recommended 2 Years Ø Lifetime 1 2 3 4 5 6 Accessories Radio module Radio control panel A Wireless linking of the heat detector via radio module The heat detector HDv 300X TS can be equipped with a wireless network module 868 MHz Order No 30933 for a wireless linking between each other and smoke...

Reviews: