VENUS BA MS 24- 34
25
EN
cod. 3541I710 - Rev. 00 - 06/2016
Notes:
1.
Parameters with more than one description vary their function and/or range in rela-
tion to the setting of the parameter given in brackets.
2.
Parameters with more than one description are reset to the default value if the pa-
rameter given in brackets is modified.
3.
The Maximum Heating Power parameter can also be modified in Test Mode.
Press the Reset button to return to the Service Menu. Press the Reset button for 20 sec-
onds to exit the card Service Menu, or exiting occurs automatically after 15 minutes.
P10
Pump deactivation tempera-
ture during Post-Circulation
(b02=1)
0-100°C
50°C
Pump deactivation tempera-
ture during Post-Circulation
(b02=2)
0-100°C
20°C
Pump deactivation tempera-
ture during Post-Circulation
(b02=3)
0-100°C
33°C
33°C
33°C
Pump deactivation tempera-
ture during Post-Circulation
(b02=4)
0-100°C
20°C
P11
Pump activation hysteresis
temperature during Post-Cir-
culation (b02=1)
0-100°C
10°C
Pump activation hysteresis
temperature during Post-Cir-
culation (b02=2)
0-100°C
5°C
Pump activation hysteresis
temperature during Post-Cir-
culation (b02=3)
0-100°C
47°C
47°C
47°C
Pump activation hysteresis
temperature during Post-Cir-
culation (b02=4)
0-100°C
5°C
P12
Heating user max. set point
20-90°C
80°C
80°C
80°C
P13
Max. output in heating
0-100%
80%
80%
80%
P14
Burner shutdown in hot water
production (b02=1)
0=Fixed
0=Fixed
1=Linked to set point
2=Solar (5)
3=Solar (10)
4=Solar (20)
Legionella protection (b02=2) 0-7=Activation days
0=No prot.
Burner shutdown in DHW
(b02=3)
0=Fixed
0=Fixed
0=Fixed
0=Fixed
1=Linked to set point
2=Solar (5)
3=Solar (10)
4=Solar (20)
Legionella protection (b02=4) 0-7=Activation days
0=No prot.
P15
Comfort activation tempera-
ture (b02=1)
0-50°C
40°C
Hot water tank hysteresis
(b02=2)
0-60°C
2°C
Comfort activation tempera-
ture (b02=3)
0-80°C
40°C
40°C
40°C
Hot water tank hysteresis
(b02=4)
0-60°C
2°C
P16
Not used (b02=1)
Do not modify
7
Primary set point (b02=2)
70-85°C
80°C
Comfort deactivation hystere-
sis (b02=3)
0-20°C
20°C
20°C
20°C
Primary set point (b02=4)
70-85°C
80°C
P17
DHW standby time (b02=1)
30-255seconds
120seconds
No effect on adjustment
(b02=2)
30-255seconds
120seconds
DHW standby time (b02=3)
30-255seconds
120seconds
120seconds
120seconds
No effect on adjustment
(b02=4)
30-255seconds
120seconds
P18
DHW user max. set point
(b02=1)
40-70°C
55°C
DHW user max. set point
(b02=2)
40-70°C
65°C
DHW user max. set point
(b02=3)
40-70°C
55°C
55°C
55°C
DHW user max. set point
(b02=4)
40-70°C
65°C
P19
DHW pump Post-Circulation
(b02=1)
0-255seconds
0seconds
DHW pump Post-Circulation
(b02=2)
0-255seconds
30seconds
DHW pump Post-Circulation
(b02=3)
0-255seconds
30seconds
30seconds
30seconds
DHW pump Post-Circulation
(b02=4)
0-255seconds
30seconds
P20
Max. output in DHW
0-100%
100%
100%
100%
Contents Description
Range
Default
VENUS BA
MS 24
VENUS BA
MS 34
P21
Comfort1 standby time
(b02=1)
0-100minutes
20minutes
Not implemented (b02=2)
--
--
Not implemented (b02=3)
--
--
--
--
Not implemented (b02=4)
--
--
P22
Comfort2 standby time
(b02=1)
0-100minutes
42minutes
Not implemented (b02=2)
--
--
Not implemented (b02=3)
--
--
--
--
Not implemented (b02=4)
--
--
P23
Fan frequency in standby
mode
0-70Hz
0Hz
0Hz
0Hz
P24
Post-Ventilation
0-120seconds
30seconds
30seconds
30seconds
P25
Modulating pump adjustment
temperature (b02=1)
0-60°C
18°C
Modulating pump adjustment
temperature (b02=2)
0-60°C
18°C
Modulating pump adjustment
temperature (b02=3)
0-60°C
18°C
18°C
18°C
Modulating pump adjustment
temperature (b02=4)
0-60°C
18°C
P26
Primary exchanger protec-
tion temperature (b02=1)
0-150°C
35°C
Primary exchanger protec-
tion temperature (b02=2)
0-150°C
150°C
Primary exchanger protec-
tion temperature (b02=3)
0-150°C
35°C
150°C
150°C
Primary exchanger protec-
tion temperature (b02=4)
0-150°C
35°C
P27
System min. pressure value 0-8 bar/10
4 bar/10
4 bar/10
4 bar/10
P28
System nominal pressure
value
5-20bar/10
7 bar/10
7 bar/10
7 bar/10
P29
Exchanger protection inter-
vention (b02=1)
0=No F43
10°C/second
1-15=1-15°C/second
Not implemented (b02=2)
--
--
Exchanger protection inter-
vention (b02=3)
0=No F43
10°C/second 10°C/second 10°C/second
1-15=1-15°C/second
Not implemented (b02=4)
--
--
P30
Heating hysteresis after igni-
tion
60-30°C
10°C
10°C
10°C
P31
Timer for heating hysteresis
after ignition
60-180seconds
60seconds
60seconds
60seconds
Contents Description
Range
Default
VENUS BA
MS 24
VENUS BA