5.1 Cable Preparation

TÜV, TÜV/UL

Connector configuration in combination with TÜV, TÜV/UL

TÜV

TÜV/UL

Choose the suitable configuration in Tab. 1 by using TÜV, TÜV/UL (dual) certified cables:

5.2 Crimping

5.2.1 Manual Tools Crimping

JKT-02

When crimping with specified Crimping tools

e.g. JKT-0

2

,Insert striped cable into contact 

barrel and insure all conductor strands are captured in the contact barrel. Crimp contact 

barrel by using the corresponding crimping die, See below pictures from Fig.3 to Fig.7. 

Check whether the crimping is firm after the crimping is completed. (Fig. 8). The pull-out 

force has to meet below table-2.

Do not use untreated cables. Tinned wires are recommended. L=7-9mm

When stripping the cable insulation “L”, 7mm to 9mm in length should be removed on the 

end of cable.  

Do not cut the copper wire inside.

7-9mm “L”

Fix the stripping tool, cutting length to 7mm to 9mm (the length of L should be fixed).

Take the cable one hand and take the stripping tool-JKT-01 the other hand.

Insert cables until the end touches fixed block. (Fig. 1)

Squeeze the handle of the stripping tool by hand, then cut and remove the cable insulation. 

(Fig. 2).

Figure 1

Figure 3

Figure 4

Figure 5

Figure 2

5.Installation Instruction

Conductor cross section

Ø-range of the cable (mm)

Chose Cable Gland

Connector configuration

mm

2

AWG

2.5

4

6

10

14

12

10

8

4.7~6.4

4.7~6.4

6.4~8.0

6.4~8.0

Black

Black

Red

Red

PV-JK03M2/xB

PV-JK03M2/xB

PV-JK03M2/xC

PV-JK03M2/xC

No.

Cable Size

Cable Crimping Pull-Out Force

1

2

3

4

2.5mm²/14AWG

4.0mm²/12AWG

6.0mm²/10AWG

10.0mm²/8AWG

≥223 N 

Min.223 N

≥310 N 

Min.310 N

≥360 N 

Min.360 N

≥400 N 

Min.400 N

Table-1

Table-2

Open the crimping tool and press the clip. Insert the male/female terminal into appropri

-

ate groove until fully seated. To make the opening of the male/female terminal face up. 

(Fig. 3 & 4).

Squeeze the crimping tool gradually until the male/female terminal touches the lower half 

of the crimping mold. (Fig.5).

 Installation Manual for PV-JK03M2/xy Series Cable Connector | 09

08

Summary of Contents for PV-JK03M2 Series

Page 1: ... Freisinger Straße 9 85716 Unterschleißheim GERMANY Fax 49 89 1433246 29 JinkoSolar Enerji Teknolojilero A Ş NİDA KULE İş Merkezi Göztepe Merdivenköy Mah Bora Sk No 1 Kat 7 34732 Kadıköy Istanbul TURKEY www jinkosolar eu Technical Support cs eu jinkosolar com Installation Manual for PV JK03M2 xy Series Cable Connector ...

Page 2: ...03 1 Products Overview 2 Tools and Parts Overview 3 Technical Data 4 Tools Instruction 5 Installation Instruction 5 1 Cable Preparation 5 2 Crimping 5 3 Male Female Terminals Installation 5 4 Disconnecting Cable Connector 5 5 Installation Warning 04 05 06 07 08 08 09 12 13 14 02 ...

Page 3: ... Terminal 6 Female Housing 7 Male Terminal Item Tool Type Tool Name Pic Stripping Tool 1 2 3 4 5 Crimping Tool Assembly Tool Open end Wrench Universal Tool Dust plug JKT 01 JKT 02 JKT 06 JKT 04 4JB03M31005 4JB03M31007 6 Torque wrench JKT 08 Installation Manual for PV JK03M2 xy Series Cable Connector 05 04 ...

Page 4: ...I 2 Ambient Temperature 40 to 85 Upper Limit Temperature 115 Over Voltage Category CAT III Flammability Class Degree of Protection mated unmated UL94 V 0 Rewireable No Cable Diameter 4 7mm to 8 0mm Contact Resistance 0 2 m Ω Contact material Copper tin plated Insulation Material PA Existence of an enclosure Enclosed connector Certification Standard IEC 62852 Edition 1 0 2014 11 UL6703 IP65 IP68 1m...

Page 5: ...f L should be fixed Take the cable one hand and take the stripping tool JKT 01 the other hand Insert cables until the end touches fixed block Fig 1 Squeeze the handle of the stripping tool by hand then cut and remove the cable insulation Fig 2 Figure 1 Figure 3 Figure 4 Figure 5 Figure 2 5 Installation Instruction Conductor cross section Ø range of the cable mm Chose Cable Gland Connector configur...

Page 6: ...alysis Cross Sectional NO Spec 1 2 3 4 5 6 7 8 9 CH CB CBm D GH GB CH CB C R P Crimp Height Crimp Width Measurable Crimp Width Crimp face Ends Burr Height Burr Width Crimp Height Crimp Width Compression Ratio Void Ratio 12AWG 4mm 2 30 0 05mm 4 00 0 10mm 1 0 CB CBm 1 1 CB D 0 35mm GH 0 7mm GB 0 5mm 50 CH CW 70 75 C R 85 1 00 10AWG 6mm 2 60 0 05mm 4 25 0 10mm 1 0 CB CBm 1 1 CB D 0 35mm GH 0 7mm GB 0...

Page 7: ...o the solar cables used in each specific case Table 4 Tighten the gland nut clockwise by using a tool or a torque wrench refer to the torque values in the table below and ensure that the nut is screwed to the anti loosing position and can be buckled Take consideration of the production process of different wire man ufacturers and the softness and hardness of insulation sheath material To avoid dam...

Page 8: ...must not be carried out on live or load carrying part Connectors must not be disconnected under load Plugging and unplugging when volt age is permitted The dust plug 4JB03M31005 4JB03M31007 should be placed to avoid exposing the dust and water when disconnected or disconnected after connected The plug connectors are watertight in accordance with IP68 protection class However they are not suitable ...

Reviews: