13 / 17
5
Electrical connection
WARNING
CAN line - Interferences
Faulty communication due to
unshielded CAN lines resulting in
extreme cases in personal injury due to
malfunction of the device.
● Connect termination resistors of 120
ohms at both ends of the CAN bus.
● Alternatively wire the internal
NOTICE
Improving electromagnetic
compatibility
Improper implementation of the wiring
harness may impair electromagnetic
compatibility.
● Keep the cables as short as
possible.
● Lay power lines and signal lines
separated from each other.