![Jetter JX3-PS1 User Manual Download Page 12](http://html1.mh-extra.com/html/jetter/jx3-ps1/jx3-ps1_user-manual_3903389012.webp)
Jetter AG
Technical specifications | 4
JX3-PS1 User Manual
12 / 24
Category
Description
Standards
Degree of protection
Degree of protection
IP20
DIN EN 60529
Tab. 1:
Mechanical specifications
4.3 Electrical properties
Power supply input
(terminal X10)
Category
Description
Rated voltage
DC 24 V
Permissible voltage range -15 % ... +20 %
Input current
1.0 A max.
Power consumption
24 W max.
Tab. 2:
Power supply input (terminal X10)
Power supply of
JX3 system bus
Category
Description
Logic voltage supply of
JX3 system bus
DC +5 V (-15 % … +10 %)
I
SV
= 1.200 mA max.
P = 6 W max.
Supplementary supply
DC +24 V (+15 % … +20 %)
I
24V
= 1,000 mA max.
P = 24 W max.
Maximum power output
P
max
= 24 W
Tab. 3:
Power supply of JX3 system bus
Electrical
safety
Category
Description
Standards
Class of protection
III
DIN EN 61131-2
Dielectric test voltage
Functional ground is con-
nected to chassis ground
internally.
Protective connection
0
Overvoltage category
II
Tab. 4:
Electrical safety
4.4 Environmental conditions
Category
Description
Standards
Operating temperature
0 °C … +50 °C
DIN EN 61131-2
Storage temperature
-40 °C … +70 °C
DIN EN 60068-2-1
Air humidity
10 … 95 %
non-condensing
DIN EN 60068-2-2
Max. operating altitude:
2,000 m above sea level
Corrosion immunity and
chemical resistance
No special protection against corrosion. Ambient air
must be free from higher concentrations of acids, al-
caline solutions, corrosive agents, salts, metal va-
pors, and other corrosive or electroconductive con-
taminants.