Jetter AG
59
JVM-407B
Mounting and installation of the JVM-407B
CANopen® bus connection in the case of a mounted support arm
The pin assignment is as follows:
Pin
Description
1
IN_CAN_1_H
4
OUT_CAN_1_L
6
IN_CAN_2_L
2
IN_CAN_1_L
3
OUT_CAN_1_H
5
IN_CAN_2_H
9
Shield
10
Shield
Terminate CAN 2 on the connector for JVM-407B (jumper between pin 6 and
8).
Type
AMP Junior-Power-Timer (male)
Number of pins
10
Compatible mating part of 10-pin AMP Junior-Power-Timer connector:
Manufacturer
AMP
Product description
Female connector,
10 circuits, dual-row
version, 5 mm pitch
Item name
Junior-Power-Timer
Manufacturer's item no.
929504-4
Wire size:
0.5 ... 1.0 mm
2
(AWG 20 ... 16)
Pin assignment
Connector specifications
Mating part