Jetter AG
Product Description | 3
User Manual – JetControl 365MC
13 / 148
LED
Status
Color
Description
D1
OFF
---
Normal operating condition.
Blinking at 1
Hz
Red
Automatic IP configuration; AutoCopy function
is completed, or first half of start delay is being
executed.
Blinking at
4 Hz
Red
Reset; fatal error, or second half of start delay
is being executed.
ON
Red
autocopy.ini
file is being executed.
D2
OFF
---
Boot loader is not running.
Blinking at 1
Hz
Red
Boot loader: Automatic IP configuration.
Blinking at
4 Hz
Red
Reset or fatal error.
ON
Red
Boot loader is being executed.
3.4.2 LED states during the boot process
If the following requirements are met, the bus nodes goes through the normal
boot process without errors:
■
Mode selector S11 is in
RUN
position.
■
There is a valid OS.
■
There must be a valid application program.
The LED flashing patterns indicate the different stages of the boot process.
LEDs
R
E
D1
D2
State
Phase 1
Reset
Color
Green
Red
Red
Red
Reset
Blinking
pattern
4 Hz
4 Hz
4 Hz
4 Hz
Phase 2
Operating system
Color
Green
-
-
Red
The device is initializing the
operating system.
Blinking
pattern
1 Hz
OFF
OFF
ON
Phase 3
Parser
Color
Green
-
-
-
The OS reads the settings of
the DIP switch on the back-
plane module and checks
whether an Ethernet switch
exists.
Blinking
pattern
1 Hz
OFF
OFF
OFF
Phase 4
Interfaces and programs
Color
Green
Red
-
-
The OS initializes realtime
clock, Ethernet interface and
file system.
Blinking
pattern
1 Hz
ON
OFF
OFF
Phase 5a
Start delay
The controller only executes phases
5a
and
5b
only if a time value is entered in
R 202971
Start delay
.
Color
Green
Red
Red
-
The first half of the start de-
lay is in progress.
Blinking
pattern
1 Hz
ON
1 Hz
OFF