Jetmaster UNIVERSAL Installation & Operation Instructions Download Page 7

10

11

Construction Specifications - Jetmaster Traditional Edwardian On Stud Wall

Construction Specifications - Jetmaster Free Standing Metal Casing “A”

Typical installation with exposed “flue” and or one length 

heat shield, refer to decro mesh diagram for firebox and 

flue clearances to combustibles.

Hearth Thickness

Hearth Thickness

Models 400 to 850 26mm

Models 400 to 850 26mm

Model 1050 100mm

Model 1050 100mm

* Hearth extends 100mm behind firebox

* Hearth extends 100mm behind firebox

DIMENSIONS IN MILLIMETRES

MODEL

A

B

C

D

E

F

G

600

1000 390 810

40

600 600 200

700S

1050 390 810

40

700 600 175

700D

1100 440 119

40

700 650 200

850

1200 490 983

40

850 700 175

1050

1400 550 1050 40 1050 750 175

Summary of Contents for UNIVERSAL

Page 1: ...ATION INSTRUCTIONS JETMASTER VIC PTY LTD ACN 005 872 159 ABN13 659 821 337 444 Swan St Richmond VIC 3121 PO Box 5051 Burnley 3121 Phone 03 9429 5573 Fax 03 9427 0031 Website www jetmaster com au Email...

Page 2: ...0 500 800 300 240 220 1200 1250 1300 605 1020 250 400 300 1500 1550 1600 605 1020 300 400 350 Tested to 15Kw at maximum burning Requires 2 flue outlets single flue option also available JETMASTER DOUB...

Page 3: ...uter can either be left exposed or enclosed with stud walls and sheet plaster or timber A minimum of 50mm clearance must be maintained between the outer flue and any combustibles If using double skin...

Page 4: ...nd free from obstructions From the measurements taken select the size of your Jetmaster Step 3 Any cracks or cavities in the recess must be repaired and sealed Step 4 Tape the insulation to the back a...

Page 5: ...ls 400 to 700D 26mm Models 850 to 1500 100mm Models 850 to 1500 100mm FREE ROTATING COWL FREE ROTATING COWL Construction Specifications Jetmaster Traditional Victorian Construction Specifications Jetm...

Page 6: ...ebel Construction Specifications Jetmaster Traditional Space Saver Models 400 to 700D 26mm Models 400 to 700D 26mm Models 850 to 1500 100mm Models 850 to 1500 100mm Models 400 to 700D 26mm Models 400...

Page 7: ...or firebox and flue clearances to combustibles Hearth Thickness Hearth Thickness Models 400 to 850 26mm Models 400 to 850 26mm Model 1050 100mm Model 1050 100mm Hearth extends 100mm behind firebox Hea...

Page 8: ...nds 100mm behind firebox Hearth extends 100mm behind firebox Typical installation with decro mesh heat shield to ceiling FIREBOX AND FLUE CLEARANCES TO COMBUSTABLES Jetmaster 600 700S 700D 850 Freesta...

Page 9: ...appliance or otherwise adversely affect the operation of the appliance Do not block or restrict chimney or flue opening After installing the appliance check that the chimney flue system draws well Je...

Page 10: ...e pressure test points Refer to diagram in installation manual If the gas pressure is not checked it can lead to sooting delayed ignition or performance issues Proper gas outlet pressure ensures that...

Page 11: ...f use and quality of wood this skimming procedure should not be required more than once or twice a Season 2 To prevent chimney fires as well as enabling the chimney to draw properly the chimney flue s...

Page 12: ...ave 50 moisture which results in a very poor heat emission Box woods e g Grey Box and Yellow Box are highly recommended as they produce fine coals Burning well seasoned medium density wood is the most...