Commissioning Procedure

Installed correctly the burner should not emit any fumes into the

room. The following procedure should be undertaken to test that

the unit is operating correctly.

1. After unit has been operating for a short period a smoke

match, smoke tube, carbon dioxide analyser or similar should be

directed at the top opening of the unit.

2. This procedure should be undertaken with the following

conditions in the room:

• Open or closed windows

• Operation of extraction/exhaust fans, range 

hoods etc

• Operation of other gas appliances

• Operation of optional appliance fan at any speed.

3. Should any spillage be detected the cause must be rectified

before allowing commissioning of unit.

User Instructions

1. WARNING NOTE: Properly installed and operated this

appliance will not leak gases. Persistent fume emission must not be

tolerated. If fume emission does exist, then the following immediate

action should be taken.

A. Open doors and windows to ventilate room.

B. Turn the fire off.

C. Check for flue blockage and clear if necessary.

D. Do not attempt to relight the burner until the cause of the

emission has been identified and rectified. Should assistance or

advice be required contact nearest agent or Jetmaster.

E. The gas grate is recommended for use in a Jetmaster firebox
which has been designed to ensure a proper draw and to eliminate
emission spillage.

2. Initially the Jetmaster log fire may burn with a slightly blue
flame. After approximately 20 minutes the fire will settle down and
burn with a yellow flame.

3. As with all gas appliances your gas log fire should be regularly
serviced. We recommend once each year. Contact your nearest
Jetmaster authorised agent to provide service. The routine for an
authorised person to follow has been set out in an attached leaflet.

4. PLEASE NOTE: Only logs provided by Jetmaster should be used
with this appliance.

5. DO NOT place articles on or against this appliance.

DO NOT use or store flammable materials near this appliance.

DO NOT spray aerosols in the vicinity of this appliance whilst

it is in operation.

Primarily a decorative appliance not certified as a space heater.

6. The appliance is a live fuel effect product designed to operate
with luminous flames and may exhibit slight carbon deposition.

Warranty

Provided the appliance has been correctly installed according to
instructions, Jetmaster guarantee the cost of replacing parts and
the labour in connection therewith for a period of 12 months
from the date of installation. Should the appliance be subject to a
service contract the replacement of the parts and the service
involved in such replacement shall be at no charge to the owner
and the Warranty shall be extended to 3 years (provided of
course the appliance had been continuously serviced by an
approved Jetmaster agent).

Installation Instructions Jetmaster 850 Gas Log 

For further information contact Jetmaster Australia

10 Martin Avenue, Arncliffe NSW 2205  T: 02 9597 7222  F: 02 9597 7622  

E: [email protected]  W: www.jetmaster.com.au

NOTES

Summary of Contents for UNIVERSAL 850

Page 1: ...Installation Instructions Jetmaster 850 Gas Log ...

Page 2: ...mum chimney flue height of 3 6 meters The installer must satisfy himself that the fireplace is functioning properly and a smoke test is recommended 3 In cases where a twin walled metal flue is used and provided such flue shall comply with the clearances specified in AS 2918 and AS5601 or manufacturer instructions in respect of clearances to combustibles 4 A space of 40mm between the side wall of t...

Page 3: ... control knob on right hand side of valve Depress and turn control knob FIG 1 to the PILOT position FIG 4 Depress the control button and ignite with piezo ignitor FIG 2 whilst keeping control knob firmly depressed for 20 seconds Check that pilot stays lit If it goes out repeat ignition procedure MAIN BURNER IGNITION Depress and turn control knob anti clockwise from PILOT position to the ON positio...

Page 4: ... the underside to position in place 3 LOCATE LOG NO S 2 3 Two front log NO S 2 3 are supplied to fit into the space between the metal frame and the ceramic base These logs do not cover the front burner ports but are designed to deflect the front flame back into the fire L O G S P O S I T I O N I N G O F A L L L O G S It is important to follow the log recommended positioning Log NO 6 10 9 and 4 mus...

Page 5: ...he centre of the burner Charred effect facing toward the left of the burner The front rests on logs 2 3 on the join LOCATE LOG NO 10 This log is located on the rear log in the position where the log reduces in height The charred end is located on the front log 3 with the charred effect facing toward the right hand side 4 LOCATE LOG NO 4 Place it on the left side of the rear log Charred end facing ...

Page 6: ... with a slightly blue flame After approximately 20 minutes the fire will settle down and burn with a yellow flame 3 As with all gas appliances your gas log fire should be regularly serviced We recommend once each year Contact your nearest Jetmaster authorised agent to provide service The routine for an authorised person to follow has been set out in an attached leaflet 4 PLEASE NOTE Only logs prov...

Reviews: