SLOW COMBUSTION FIREPLACE INSTALLATION AND OPERATION INSTRUCTIONS
Roof pitch less than 10°
IF
Then
If the flue is closer than 600mm
to the apex of the roof
The flue termination must be at
least 600mm above the roof
apex.
IF THE FLUE IS FURTHER
THAN 600MM FROM THE
APEX OF THE ROOF
The flue termination must be at
least 1000mm above the roof
level.
IF ANY BUILDING IS
CLOSER THAN 2M FROM
THE FLUE
The flue termination must be
raised until it is clear within 2m.
THE ROOF PITCH IS LESS
THAN 10°
The flue termination must be at
least 1000mm above the highest
point of the roof.
Choice of cowls
Any Jetmaster, Ø150mm. cowl can be used.
The following table illustrates the recommended cowls for specific weather conditions.
*
Chinese Cowl
*
Fixed Cowl
Low wind conditions
Rotating Cowl & Ø150mm base
Medium to High wind
conditions
*
Turbo Cowl
Medium to High wind,
With rapid changes in
wind directions
*NOTE: The Chinese, Fixed and Turbo cowls MUST NOT be used on Thatch or Timber roofs.