Jet 952 Installation Instructions Manual Download Page 5

UV LAMP INSTALLATION

1.  Apply dielectric grease onto the face of the  

 

four pin connector of the power cable  

 

 

to protect against moisture and corrosion.  

2.  You do not want to touch the UV lamp    

 

surface with your hands.  Use a clean, soft  

 

cloth to hold the UV lamp and insert it into. The 
four pin connector being sure to align  

 

the two red prongs on the UV lamp with the  

 

two red holes on the four pin connector.

3.  Carefully insert the UV lamp into the quartz tube 

of the UV subassembly.      

NOTE: Both the quartz tube and UV lamp are 
very fragile.  HANDLE WITH CARE.

4.  After verifying the UV lamp is seated  

 

 

properly in the UV insert and the cord is the  

 

correct length, tighten the cord grip  

 

 

that is attached to the bushing.  This must 

 

be done to ensure a watertight enclosure.  

5.  Verify the union on the lifting handle has  

 

been fastened.

6.  Fill the UV housing with water up to the    

 

outlet piping.  Be careful not to get water in  

 

the UV insert.

7.  Place excess UV lamp cable in the riser.
8.  Clean the top of the riser pipe and the ABS  

 

fitting on the bottom of the control panel.   

 

The control panel fitting should not be glued    

inside the riser.

9.  Align the “Lamp Active” port on the control panel 

cover with the LED inside the control panel and 

secure the cover on the control panel using  

 

the four screws provided.

10. 

Continue to back fill around the disinfection  

 

chamber and riser until even with the final  

 

grade being no more than 6” below the bottom 
of the control panel.

11. Turn the UV disinfection device on at the  

 

main electrical panel.

12. The “Lamp Active” light should be  

 

 

illuminated to indicate the system is  

 

 

operating.

SERVICE PROCEDURES

Jet recommends servicing the UV system at a 
minimum every six months.  

1.  Inspect condition of UV and note that “Lamp  

 

Active” indicator light is active.

      a.   If “Lamp Active” light is not lit and  

 

 

 

alarms are not working refer to  

 

 

 

troubleshooting guide 

2.  Turn off main power from alarm panel    

 

(indicator light should now be off.)

3.  Remove control panel assembly and UV  

 

Insert.

4.  Clean quartz tube with soft cloth and alcohol  

 

wipe.

5.  Inspect UV insert assembly for any damage,  

 

water infiltration, or worn components.

6.  Re-install UV Insert and control panel    

 

assembly.

7.  Turn on main power and observe that “Lamp  

 

Active” indicator light is lit and system is   

 

functioning.

      a.   If “Lamp Active” light is not lit or if     

 

 

alarms activate after service refer to   

 

 

troubleshooting guide pg.

8.  Replace the UV lamp every other year.  Refer to 

UV lamp installation section for instructions on 
replacing lamp.

WARNING: 

 Exposure to UV light 

is harmful. Immediate or prolonged 
exposure to UV light can result 
in painful eye injury, skin burn, 
premature skin aging, or skin 
cancer. Do not remove an active 
UV lamp from the UV housing or 
attempt to activate lamps which are 
not installed within the UV housing. 

JET Model 952 UV Disinfection 

Device Installation Instructions

Summary of Contents for 952

Page 1: ...g components should be supplied by the installer 1 All Purpose Cement 2 Clear Cleaner for plastics 3 Drill with Universal Bit 4 Clean soft cloth 5 Isopropyl alcohol 6 Small slotted screwdriver 7 Wire...

Page 2: ...not flow through the device correctly and the UV disinfection will not be effective See Figure 1 2 Clean the ends of the upstream and downstream piping and the hubs of the UV cross with clear plastic...

Page 3: ...of the 1 PVC pipe See figure 3 The opposite end will already be glued to the bushing on the control panel UV lamp wire 4 Glue the other end of the 1 PVC pipe into the coupler that is on the UV insert...

Page 4: ...remaining lead to the common C terminal WIRE THE CONTROL PANEL 1 The UV unit operates on 120 VAC single phase power A 15 amp circuit breaker on the main electrical panel should be used for the UV dis...

Page 5: ...the disinfection chamber and riser until even with the final grade being no more than 6 below the bottom of the control panel 11 Turn the UV disinfection device on at the main electrical panel 12 The...

Page 6: ...hose Water in Enclosure Enclosure cover not secure Conduit hub not secure Align and tighten enclosure cover Tighten conduit hub Lamp Active Light Not Lit No power from main breaker panel No power to U...

Page 7: ...ure to follow the suggestions outlined in any associated product documentation or Owners Manuals Items normally consumed in service such as fuses filter cartridges spin plates grease oil etc are not w...

Reviews: