Type of fault
Possible cause
Recommended action
Cylinder iced.
Delivery rate too high.
Max. 1% of cylinder filling per hour is permitted.
Install flow limiter, increase room temperature.
Cylinders are
not emptied
uniformly.
Conditions for simultaneous delivery
not provided.
See section INSTALLATION.
Chlorination plant designed for
much higher metering capacities
than actually required. As a result
the delivery rate per cylinder is
reduced.
Connect only as many cylinders as really needed.
Fix remaining vacuum regulators to PVC wall
holder using flat gasket.
Incorrect adjustment of simultane-
ous delivery.
Readjust units as described in section MAINTE-
NANCE.
11 Accessories
Article
Part.-No.
PE tubing d 8/12
97124
PVC tubing d 8/12 (only as blow-off line)
97561
PE d tubing 12/16
97176
ammonia bottle k (50 ml)
13514
set accessories (5 m PE tubing, mounting brackets, ammonia)
22412
PVC wall holder W1“ incl. mounting material
28380
PVC wall holder G 5/8 incl. mounting material
29752
PVC wall holder G 3/4 incl. mounting material
28360
PVC wall holder 1.030“-14NGO incl. mounting material
38320
safety shutoff valve d 8/12
20401009
safety shutoff valve d 12/16
20401010
activated-carbon cartridge incl. mounting material
12032301
Activated-carbon cartridge refill
35057
back stop, tubing d 8/12
20435060
back stop, tubing d 12/16
20435061
back stop, PVC d 16i
20435118
set open end-spanners for exchanging cylinders (SW 32 + 13)
35559
tool kit for maintenance of the vacuum regulator
35280
Tab.: 4: Accessories
Wall holder
A PVC wall holder is used to receive the chlorinator while cylinder is exchanged and closes the pressure
connection at the same time. Thus the entry of humid air is avoided effectively also during replacement of the
cylinder.
Activated-carbon cartridge
In almost any installation incl. vacuum systems, temporary shock pressures may occur, which cause the
extremely sensitive safety blowdown valve to respond briefly so that gas warning device is activated. In order