background image

The Clark Reliance Corporation 

16633 Foltz Industrial Parkway | Strongsville, OH 44149 | Tel1 (440) 572-1500 Facsimile: +1 (440)-238-8828 

Email: 

[email protected]

 | Web Site:  

www.clark-reliance.com

 

 
 

4. ELECTRICAL CONNECTIONS AND WIRING PROCEDURES 

Electrical Connections 

Connect the 24 VDC power supply to the electronics module using the screw terminal block on the electronics module.  A 
typical wiring arrangement is shown in Figure 3. 
 
Figure 3 Wiring Diagram 

 

For explosion-proof installations, wiring shall be in accordance with the National Electric Code ANSI/NFPA 70, Article 501-
30. 
 
Shielded cable, twisted pair of 24 AWG or heavier should be used.  Cable capacitance shall be less than 30 pF per foot. 

 
4.1 Cable Specifications 
 

Parameter Specification 

Minimum Cable Size: 24 AWG or heavier (0.51 mm diameter) 
Cable Type: Single pair shielded or multiple pair with overall shield 
Maximum Cable Length: Twisted Pair: 10,000 ft. (3,048 m) 
Multiple Twisted-Pair: 5,000 ft. (1,524 m) 
 

4.2 Safety Recommendations for MTII4200 Transmitter 

 

Always follow applicable local and national electrical codes and observe polarity when making electrical connections. 
Never make electrical connections to the MTII4200 transmitter with power turned on. Make sure that no wire strands are 
loose or sticking out of the terminal block connection which could short and cause a problem. Make sure that no wire 
strands, including shield, are in contact with the electronic module enclosure. The electronics module enclosure is 
grounded through internal circuitry and electrically isolated from the explosion-proof enclosure. 
 

5. SYSTEM CHECK 

After completing the MTII4200 wiring, the system is ready to be checked out. Apply power to the unit. Using a DC volt-
meter, measure the voltage at loop #1 connections. The voltage must be 10.5V.  If the voltage levels are too low, shut 
down the system. Check for shorts, power supply voltage, and excessive loop resistance.  

5.1 Loop #1 Test 

To test loop #1 on a bench, move the float along the operational range of the MTII4200 transmitter. If functioning properly, 
the output current will change as the float moves.  

An output current of less than 4 mA or greater than 20 mA could indicate a problem with the MTII4200 transmitter. 
 
 
 
 
 

Summary of Contents for MTII4200 Series

Page 1: ...D B TOP RIGHT HAND C BOTTOM RIGHT HAND D BOTTOM LEFT HAND ALARM SETTING L 3 85 mA DEFAULT H 22 5 mA MAX SENSING LENGTH IN INCHES ON 6 INCH INCREMENTS LCD DISPLAY M mA OUTPUT DEFAULT I INCHES P PERCENT...

Page 2: ...II4200 transmitters are available in a single cavity explosion proof enclosure 2 1 MTII4200 Transmitter Specifications PARAMETER SPECIFICATIONS LEVEL OUTPUT Measured Variable Liquid level interface le...

Page 3: ...f Operation The MTII4200 transmitters precisely sense the position of an external float by applying an interrogation pulse to a waveguide medium This current pulse causes a magnetic field to instantly...

Page 4: ...Transmitter Always follow applicable local and national electrical codes and observe polarity when making electrical connections Never make electrical connections to the MTII4200 transmitter with powe...

Page 5: ...how the HART protocol is applied to the MTII4200 level transmitter only Using the HART interface allows for calibration without having to remove the transmitter from the process and position the float...

Page 6: ...to exit the program mode replace the calibration jumper to the ON position and return your controllers to automatic To set high value You should now be in the Range Values screen To set the 20 mA Upp...

Page 7: ...n until it is Press the enter button to set the low level of the range At this time position the float magnet at the desired low level point and keep it there while pressing the Enter button and holdi...

Reviews: