background image

Installation, Operation, & Maintenance Instructions

IOM JS500.03

2016.04

Vertical Float Switches 

Putting the Switch into Service

1. Check the tag to ensure that the operating conditions of the application are within the ratings of the switch.
2. Check that any and all valves, plugs, etc. are securely closed. Check torque values for bolting of process connections 
and/or switch head flange, if either apply.  Values shall be in accordance with manufacturers recommendation based on 
bolting, gasket materials, etc.  Reference page 14.
3. Slowly bring the switch up to pressure by opening the upper block/isolation valve, or by similar means.  Take caution not 
to damage the switch if fluid is available to the upper block/isolation valve, or other.  As fluid under pressure can be 
extremely dangerous.
4. If available, slowly introduce & equalize a liquid level to the switch by opening the lower block/isolation valve, or by 
similar means.

Taking the Switch out of Service

1. Isolate the switch from any pressure and/or fluid by closing both the upper and lower block/isolation valves, or by similar 
means.
2. Slowly open a vent valve, vent plug, or similar connection to relieve pressure on the switch. If the vent valve or 
connection is available to the fluid, take caution as fluid exiting the switch under pressure can be extremely dangerous.
3. Remove any remaining fluid from the chamber using a drain valve, drain plug, or the lowest connection.

Maintenance of the Jerguson

®

Vertical Float Switch

Inspection and maintenance shall be carried out by suitably trained personnel in accordance with all local and 
national codes.

1.

Isolate electrical circuits to switch and disconnect wiring as necessary.

a.

Series JB_ _F switches: Continue with step 9.

b.

Series JX_ _F & JD_ _F switches: Continue with step 2.

2.

Take switch out of service, according to the respective section above.

3.

Remove top flange nuts holding switch to chamber/vessel and carefully withdraw switch head and float assembly, 
taking care not to bend the float rod.

4.

Separate float assembly from pressure tube by pinching & removing stop clip. (Note: The stop tube, which sits on the 
stop clip, may prevent you from pinching the stop clip sufficiently to remove it.  Stop tube may have to be moved into 
the pressure tube in order to remove.)

5.

Check float, float rod, magnet, sealing surface and gasket for excessive wear and/or damage.  Clean and/or replace as 
necessary.

6.

Inspect the chamber and remove any deposits.

7.

Fit replacement joint and reassemble, taking care not to bend the float rod. Firmly tighten nuts on top flange, using bolt 
torque values given in tables on page 14.

8.

Bring switch into service, according to the respective section above.

9.

Remove the switch head cover and examine the switch mechanism body for any damage. Ensure that wiring is in good 
order and that all the screws are tight. 

Dismantling of switch mechanism is not recommended and replacement of 

the complete switch mechanism will be found to offer the quickest and most economical solution in event of 
faulty operation.

See page 15.

10. Check sealing gasket / “O” ring and replace if necessary.
11. Check the cover seals are present and in good condition, and then replace the cover.

a.

Explosion-proof models

Before energizing

, ensure the cover locking safety grub screw is replaced and 

tightened. Do not energize if the cover locking safety grub screw is missing.

b.

Weatherproof models: 

Before energizing,

ensure that the fiber sealing washer and hexagon bolt were 

reinstalled at the top of the cover.

www.Jerguson.com

 ●

JergusonApp@clark

reliance.com

 ●

+1.440.572.1500

11

Summary of Contents for JB**F Series

Page 1: ...04 Vertical Float Switches Vertical Float Switch Installation Operation Maintenance Manual Series JB_ _ F Series JX_ _ F Series JD_ _ F Section JS500 Bulletin JS500 03 Date 2016 04 Supersedes March 20...

Page 2: ...ch Ratings 6 Switch Mechanisms Simple Apparatus 7 Installation Part 1 Switch Assembly 8 Installation Part 2 Spare Enclosure Pressure Tube 9 Installation Part 3 Conversion Kits 9 Installation Specific...

Page 3: ...F Diagrammatic detail of Tri Magnet system Series JX_ _F Series JD_ _F Switch Assembly Identification This manual covers the three series of switches JB JX and JD as shown opposite Also covered in thi...

Page 4: ...gn Style 2 Side Side B or X Chamber Design Style D Top Mount D Chamber Design Style Omitted Head Ass y Only Less Chamber X Chamber Design Style 0 50 DN15 1 75 DN20 2 1 00 DN25 3 1 25 DN32 4 1 50 DN40...

Page 5: ...Long 1 3 Switches J4 Jerguson for SA4 Weatherproof NEMA 4 IP66 Std 1 2 Switches J7 Jerguson for SA7 Ex Proof FM Std Al Alloy 1 2 Switches JI Jerguson for SI7 Ex Proof FM Std Cast Iron 1 2 Switches JR...

Page 6: ...ged if the mechanisms are used to switch circuits with values greater than those shown above Important wiring notes 1 To minimize electrical shock hazard before energizing it is essential that the equ...

Page 7: ...NS N10276 or Alloy 625 UNS N06625 or Alloy 825 UNS N08825 If the equipment is likely to come into contact with aggressive substances it is the responsibility of the user to take suitable precautions t...

Page 8: ...enclosure type refer to model code on pages 4 5 5 Check torque values for all bolted connection s if applicable Values shall be in accordance with manufacturers recommendation based on bolting gasket...

Page 9: ...be in order to remove 9 On the original units pressure tube mark the location of each switch then remove each switch Each switch mechanism is mounted on the pressure tube by a locking screw and nut Th...

Page 10: ...ls or solvents that may affect polymeric materials iii Suitable precautions e g regular checks as part of routine inspections or establishing from the material s data sheet that it is resistant to spe...

Page 11: ...es JB_ _F switches Continue with step 9 b Series JX_ _F JD_ _F switches Continue with step 2 2 Take switch out of service according to the respective section above 3 Remove top flange nuts holding swi...

Page 12: ...ance between the switch trip and reset G Enclosure Height See table on page 13 Default trip locations at minimum operating SG See Switching Point Adjustment section page 13 1F 2F 3F 4F JB_5F JX_5F 6F...

Page 13: ...ecured on the pressure tube by a locking screw and lock nut These can be loosened allowing the bracket and therefore the switch trip point elevation to be adjusted up or down as required Always ensure...

Page 14: ...8 20 27 47 64 47 64 100 136 100 136 0 75 20 40 54 27 37 60 81 51 69 34 46 84 114 84 114 100 136 100 136 1 00 25 53 72 35 47 60 81 67 91 45 61 115 156 115 156 160 217 160 217 1 50 40 60 81 60 81 60 81...

Page 15: ...en the liquid level in the chamber should be raised such that the primary float magnet passes through the switching point Lowering the liquid level will then cause the float magnet to fall back throug...

Page 16: ...n Maintenance Instructions IOM JS500 03 2016 04 Vertical Float Switches 16633 Foltz Parkway Strongsville OH 44149 USA 1 440 572 1500 www clarkreliance com www Jerguson com JergusonApp clark reliance c...

Reviews: