background image

Air Flow

Air Flow

Air Flow

Air Flow

Air Flow

Air Flow

Air flow this

direction NOT
recommended

Air flow this

direction NOT

recommended

6" to

3 1/4" x 10"

90° Elbow

3 1/4" x 10"

 to 6"

90° Elbow

6" to

3 1/4" x 10"

Transition

5" to 6"

Transition

3 1/4" x 10"

 to 6"

Transition

5" to

3 1/4" x 10"

90° Elbow

1 foot

5 feet

9 feet

1 foot

4 1/2 feet

6 feet

5 feet

12 feet

0 feet

0 feet

0 feet

2 feet

5": A405
6": A406

A463

A495

A496

A496

A456

A463

5 feet

6"

45° Elbow

2 1/2 feet

Equivalent

Length

Duct

Fitting

Equivalent

Length

Part

Number

Part

Number

Duct Equivalents

should be at least 18".  The farther the better.  Closer distance
promotes turbulence which reduces airflow.
5.  The number of downstream elbows or transitions should be
limited to three.  The initial 5" to 6" straight transition, if used, need
not be counted in this number.
6.  Handmade crimps are likely to cause restrictions.
7.  If an alternate wall or roof cap is used, be certain duct size is not
reduced, and there is a backdraft damper.  It is best to use listed caps
to be certain of proper performance.
8.  Thermal breaks:  In areas of extreme cold weather, it may be
necessary to provide a short length of nonmetallic duct as close to
the wall as possible, to prevent conduction along the metal duct.
9.  High altitude installations:  It is advisable to reduce allowable duct
run by 20%.
10.  In Canada, the installation must conform with local codes.
11.  Elbows, wall caps and other fittings are shown below with their
equivalent straight duct length.  Each fitting value must be added to
the amount of straight duct length used, to determine overall straight
duct equivalent length (60 feet maximum).
12.  When using flexible duct multiply length of flexible duct by 2.

Unit is rated at a maximum of 60 feet of straight duct, 300CFM of
"make-up" is required.  The blower has 2 range settings; Low range
is used when equivalent duct length is up to 30 feet and high range
is used when equivalent duct length is between 31 and 60 feet.

1.  Use 6" diameter round or 3 1/4" x 10" rectangular only, except
for equivalent duct lengths of 10 feet or less that vent straight out
the back of the cooktop and directly through the wall. Equivalent
duct lengths of 10 feet or less can use 5" round duct.  A transition
from 5" round duct  is necessary when connecting to 6" round or
3 1/4" x 10" duct.
2.  Do not use 5" elbows except in a 5" system.  Instead use a 5" to
6" transition followed by a 6" elbow, or a 5" to 3 1/4" x 10" elbow
transition.
3.  Use quality metal duct of at least 26 gauge galvanized or 24 gauge
aluminum.  Inferior quality pipe fittings can cause up to twice the
restriction and is a poor value.  6" diameter PVC sewer pipe can be
used for under slab installations.  Local codes may require a heavier
gauge material or restrict PVC.  Check your local codes.
4.  Distance between adjacent fittings (elbows, transitions etc.)

Ducting Installation Guidelines

3 1/4" x 10"

Elbow

5"  and 6"

Thermal

Break

3 1/4" x 10"

Flat Elbow

5" and 6"

Wall Caps

3 1/4" x 10"

Wall Cap

10" x 10"

Roof Jack

6"

90° Elbow

Duct

Fitting

5": 708786
6": 715557

Legh: 5950
JA: 701943

A403

Additional Information:

Subject to change without notice.  This system is designed to be updated daily if necessary.  Dimension Express is not responsible for use of superseded, voided, or
outdated data sheets.  Because of the difficulty or impracticability of determining actual damages, liability of Dimension Express shall not exceed $50.00.
Copyright ©  Dimension Express, 2002.

www.dexpress.com

DIMENSION EXPRESS

Fax on Demand (775) 833-3600

• NEVER reuse Data Sheets.  Data Sheets are subject to change without                          • Call Dimension Express if you have any questions at (775) 833-3633 •
notice.  Dimension Express is a FREE service bureau and is updated daily,                     • Always refer to a current Code at a Glance or manufacturer directory •
it makes far more sense to spend the time necessary to request new Data                    • Data Sheet codes change on the first of odd numbered months at 12:01am •
Sheets for each project, as opposed to the problems, time, costs, and risks
associated with reusing old Data Sheets.

30"  Convertible Cooktops:

JGD8130ADW, JGD8130ADS and JGD8130ADB

•                           Product Model Number (s):                            •

This Data Sheet Includes Information On