Jenn-Air 36'' ISLAND-MOUNT CANOPY RANGE HOOD Installation Instructions And Use & Care Manual Download Page 4

4

For vented installations, you will also need: 

1 wall or roof cap

Metal vent system

For non-vented (recirculating) installations, you will also 
need:

Recirculation Kit Part Number W10272065 for non-vented 
(recirculating) installations only. See “Assistance or Service” 
section to order.

Parts supplied

Remove parts from packages. Check that all parts are included.

Hood canopy assembly with ventilator and light bulbs 
installed

8 vertical supports

2  glass mounting brackets

Glass mantle

Mounting template

Upper horizontal support

Horizontal support

4 plastic brackets (for lower chimney fixings)

2 plastic brackets (for upper chimney fixings)

68 - 4 x 8 mm screws

4 - 3.5 x 9.5 mm glass mantle mounting screws

4 - 5 x 45 mm screws

Location Requirements

IMPORTANT: Observe all governing codes and ordinances.

Have a qualified technician install the range hood. It is the 
installer's responsibility to comply with installation clearances 
specified on the model/serial rating plate. The model/serial rating 
plate is located behind the left filter on the rear wall of the vent 
hood.
Canopy hood location should be away from strong draft areas, 
such as windows, doors and strong heating vents. 
Cabinet opening dimensions that are shown must be used. Given 
dimensions provide minimum clearance.
Grounded electrical outlet is required. See “Electrical 
Requirements” section.
Because of the size and weight of this island hood, the chimney 
support must be securely attached to the ceiling.

For plaster or drywall ceilings, the chimney support must be 
attached to joists. If this is not possible, you must build a 
support structure behind the plaster or drywall. The support 
structure must be able to support 80 lbs (36.6 kg).

The range hood is factory set for venting through the roof or wall.
For non-vented (recirculating) Installation see “Non-vented 
(recirculating) Installations” in “Install Range Hood” section. 
Recirculation Kit Part Number W10272065 is available from your 
dealer or an authorized parts distributor. 
All openings in ceiling and wall where range hood will be installed 
must be sealed.

For Mobile Home Installations
The installation of this range hood must conform to the 
Manufactured Home Construction Safety Standards, Title 24 
CFR, Part 328 (formerly the Federal Standard for Mobile Home 
Construction and Safety, Title 24, HUD, Part 280) or when such 
standard is not applicable, the standard for Manufactured Home 
Installation 1982 (Manufactured Home Sites, Communities and 
Setups) ANSI A225.1/NFPA 501A, or latest edition, or with local 
codes.

Product Dimensions

*Vented installations only

**Non-vented (recirculating) installations only

Installation Clearances

IMPORTANT:

Minimum distance “C”: 24" (61.0 cm) from electric cooking 
surface.
Minimum distance “C”: 27" (68.6 cm) from gas cooking 
surfaces. 
Suggested maximum distance “C”: 36" (91.4 cm)

For vented installations, the chimneys can be adjusted for 
ceilings between 8' (2.4 m) and 9' 11" (3.0 m).

For non-vented (recirculating) installations, the chimneys can 
be adjusted for ceilings between 8' (2.4 m) and 10’ 4" (3.1 m).

A. Ceiling height
B. Hood height from ceiling to bottom of the 

range hood: A-C-D=B

C. Hood height: 24" (61.0 cm) min. from 

electric cooking surface, 30" (76.2 cm) 
min. from gas cooking surface, suggested 
36" (91.4 cm) max

D. Countertop height

36" - 42" (91.4 cm to 106.7 cm)

25¼" (64.0 cm)

13

³⁄₈

" (33.8 cm)

15" (38.0 cm)

*35

³⁄₁₆

" (99.5 cm) min.

   53

³⁄₁₆

" (152.8 cm) max.

**35

³⁄₁₆

" (107.0 cm) min.

   56

³⁄₁₆

" (158.0 cm) max.

1½" (4.0 cm)

A

D

B*

C

Summary of Contents for 36'' ISLAND-MOUNT CANOPY RANGE HOOD

Page 1: ...6247 or visit our website at www jennair com In Canada call 1 800 807 6777 or visit our website at www jennair ca Instructionsd installationetGuided utilisationetd entretien Au Canada pour assistance...

Page 2: ...Installation des filtres 23 Achever l installation 23 UTILISATION DE LA HOTTE 23 Afficheur 23 clairage 24 Minuterie 24 Boutons de vitesse du ventilateur 24 ENTRETIEN DE LA HOTTE DE CUISINI RE 25 Nett...

Page 3: ...e American Society for Heating Refrigeration and Air Conditioning Engineers ASHRAE and the local code authorities When cutting or drilling into wall or ceiling do not damage electrical wiring and othe...

Page 4: ...ructure behind the plaster or drywall The support structure must be able to support 80 lbs 36 6 kg The range hood is factory set for venting through the roof or wall For non vented recirculating Insta...

Page 5: ...ide of the thermal break The break should be as close as possible to where the vent system enters the heated portion of the house Makeup Air Local building codes may require the use of makeup air syst...

Page 6: ...ge hood is installed Before making cutouts make sure there is proper clearance within the ceiling for exhaust vent Range hood is to be installed 24 61 0 cm min for electric cooking surfaces 27 68 6 cm...

Page 7: ...x 8 mm screws and tighten Connect Vent System 1 Install vent system 2 Push duct over the exhaust outlet Seal all connections with vent clamps Non Vented recirculating Installation 1 Attach the air de...

Page 8: ...er 10 Check all light bulbs are secure in their sockets 11 Reconnect power InstallDuctCovers 1 Attach the vertical duct cover supports using 4 4 x 8 mm screws 2 Slide upper duct covers into place unti...

Page 9: ...r saturation alarm press and hold the POWER INCREASE button for 5 seconds The Clean Grease Filter icon will no longer be displayed Charcoal Filter Saturation Alarm After 120 hours of fan function the...

Page 10: ...ng 5 seconds after selecting the desired time will start the timer countdown 3 The timer can be canceled at any time by pressing the Timer button again NOTE During the timer setup the Power Decrease a...

Page 11: ...he highest temperature setting To reactivate the filter the filter should be dried in an oven for 10 minutes with a maximum temperature of 210 F 100 C To Replace Charcoal Filters 1 Turn fan and lights...

Page 12: ...Power Board Electronic User Interface 1 2 3 4 5 1 2 3 4 5 6 W R GY BR Y BR Y G BR BR R R BK BR R BR Transformer PRI Y Y SEC Y Y Transformer I R P Y Y C E S M GY W R BK BU BU R W GY BK 1 Y G G Y BU W B...

Page 13: ...name address and daytime telephone number 2 Appliance model number and serial number 3 Name and address of your dealer or servicer 4 A clear description of the problem you are having 5 Proof of purcha...

Page 14: ...e service by an authorized Jenn Air servicer is not available 10 The removal and reinstallation of your major appliance if it is installed in an inaccessible location or is not installed in accordance...

Page 15: ...n cas de non respect des instructions Votre s curit et celle des autres est tr s importante Nous donnons de nombreux messages de s curit importants dans ce manuel et sur votre appareil m nager Assurez...

Page 16: ...que d incendie et vacuer ad quatement les gaz veiller acheminer l air aspir par un conduit jusqu l ext rieur ne pas d charger l air aspir dans un espace vide du b timent comme une cavit murale un plaf...

Page 17: ...i C est l installateur qu incombe la responsabilit de respecter les distances de s paration sp cifi es sur la plaque signal tique de l appareil La plaque signal tique de l appareil est situ e derri re...

Page 18: ...m pour des performances optimales Pour un fonctionnement efficace et silencieux Ne pas utiliser plus de trois coudes 90 Veiller ce qu il y ait une section droite de conduit d un minimum de 24 61 0 cm...

Page 19: ...de liaison la terre il est recommand qu un lectricien qualifi v rifie la qualit de la liaison la terre Pour obtenir un exemplaire de la norme des codes ci dessus contacter National Fire Protection As...

Page 20: ...QUE Les trous de montage devront tre perc s dans la structure de soutien du plafond Retirer le gabarit 8 Percer 4 avant trous de 4 8 mm pour le montage du support horizontal sup rieur 9 D terminer l e...

Page 21: ...ions Installation sans d charge l ext rieur recyclage 1 Fixer le d flecteur d air au support horizontal sup rieur l aide des 4 vis de montage 2 Mesurer la longueur de conduit d vacuation de 8 20 3 cm...

Page 22: ...de connexion 10 Inspecter chaque lampe v rifier que chaque lampe est bien ins r e dans sa douille 11 Reconnecter la source de courant lectrique Installationdescache conduits 1 Fixer les supports de ca...

Page 23: ...de commande Les commandes de la hotte sont situ es l avant de la hotte Afficheur Alarme de saturation du filtre graisse Apr s 30 heures de fonctionnement du ventilateur l affichage indique Clean Grea...

Page 24: ...ventilateur retourne au r glage qui avait t effectu avant que le niveau de chaleur excessif ne soit d tect clairage Fonctionnement de l clairage 1 Appuyer sur le bouton de symbole d clairage pour met...

Page 25: ...ns horaire pour le verrouiller en place Filtres charbon Installation sans d charge l ext rieur recyclage REMARQUE On doit remplacer le filtre charbon apr s environ 3 ans d utilisation Pour commander u...

Page 26: ...ilisateur lectronique 1 2 3 4 5 1 2 3 4 5 6 BL R GRIS MAR JA MAR JA VE MAR MAR R R N MAR R MAR Transformateur PRI JA JA SEC JA JA Transformateur I R P JA JA C E S M GRIS BL R N BU BU R BL GRIS N 1 VE...

Page 27: ...ez vous de conserver la preuve d achat pour v rifier les conditions de la garantie Si le marchand ou la compagnie de service ne peut pas r soudre votre probl me crivez Jenn Air Brand Home Appliances C...

Page 28: ...ou n est pas install conform ment aux instructions d installation fournies 11 Les gros appareils m nagers dont les num ros de s rie et de mod le originaux ont t enlev s modifi s ou qui ne peuvent pas...

Reviews: