JUNE 2018
page 5
REDUCING CLEARANCES TO COMBUSTIBLE WALLS
In the event it is necessary to reduce the clearances to combustible surfaces, it must always be
done in accordance with the safety standard AS/NZS2918:2001 Section 3, Tables 3.1 and 3.2
The shielding shall be constructed from a heat resistant material. The shield must be fi xed to the
surface that requires protection and NOT the heater.
The standard allows three options to reduce the stated clearances:
Single Layer of continuous material with minimum Air Gap of 12mm to achieve a clearance factor
of 0.40
Single layer of continuous material with minimum Air Gap of 25mm to achieve a clearance factor
of 0.30
Two spaced Layers of continuous material with minimum Air Gap of 12mm + 12mm to achieve a
clearance factor of 0.20
The shielding must be open at the top and bottom (vented) to allow a continuous air fl ow. It is
this fl ow that keeps the surface requiring protection cool. Fixings should not impede this air fl ow.
The shielding needs to go far enough along and up the wall so that the original side and rear
required clearances are not compromised. As the fl ue is now closer to the wall the shielding
should also protect the wall from the fl ue pipe.
Example:
• Side wall clearance for the Jayline FR300 is 290mm
• A 12mm gapped shield on the wall with a factor of 0.40
• Calculate: 290mm x 0.40 = 116mm (This is the new sidewall minimum clearance)
• The shielding needs to be large enough that none of the original clearances of 290mm are
compromised.
Summary of Contents for RU
Page 1: ...JUNE 2018...
Page 2: ...JUNE 2018 page 2...
Page 3: ...JUNE 2018 page 3...
Page 4: ...JUNE 2018 page 4...
Page 6: ...JUNE 2018 page 6...
Page 7: ...JUNE 2018 page 7...
Page 8: ...JUNE 2018 page 8...
Page 9: ...JUNE 2018 page 9...
Page 10: ...JUNE 2018 page 10...
Page 11: ...JUNE 2018 page 11...
Page 12: ...JUNE 2018 page 12...
Page 13: ...JUNE 2018 page 13...
Page 14: ...JUNE 2018 page 14...
Page 15: ...JUNE 2018 page 15...
Page 16: ...JUNE 2018 page 16...