 2 

 

These instructions should be read in conjunction with the 

relevant 

IS500

 details in the full 

Jayline

 installation and 

operating manual supplied with the fire 

 

Following these instructions allows for the 

IS500

 to be safely  

installed in a timber frame wall, without the need for further heat 
protection beyond that supplied as part of the cabinet and flue  
system. 

 

WARNING: 

It is critical that these instructions are followed fully and 

that no substitute parts are used. 
 
For floor protector and mantle extension details, refer to the full 

manual, for approved clearances. 
 

INSTALLATION NOTES 

 

1. 

  IS500

 zero clearance cabinet is approved to sit directly into a 

timber frame. 

 
2.  Combustible materials can be in contact with the 25mm standoffs 

fitted to the outside of the cabinet, but we recommend an  

 

additional clearance o

f

 25mm beyond the standoffs for ease of 

 

moving into position without becoming jammed in the wall cavity 

 

provided for the appliance. 

 
3.  Timber framing can be in contact with the 250mm diameter outer 
 

casing where the 200mm diameter inner casing is at the height 

 

also. 

 
4.  Timber framing must be 25mm clear of the 250mm diameter 
 

outer casing if the 200mm diameter inner casing is not present 

 

at that height. 

 
5.  The floor protector extension in front of the door shall be a  
 

minimum of 8mm ceramic tiles if the floor is a heat sensitive  

 

material. 

 