8. Boiler Operation and Maintenance 

Prior to start-up, ensure that: 

- The boiler and 

the heating system are 

filled with water

 and circulation is working 

- The air vent is open for air escape  

- Piping connections are sealed. Check also 
the internal factory made connections in the 
boiler piping. 

- The safety relief valve is working i.e. water 
escapes from the drain pipe during valve 
testing. 

When the installation is completed, connect 
the main switch of the unit, rotate the control 
switch to position 1=heating, and set desired 
temperatures at the printed circuit board (see 
section 9); now the unit is ready for operation. 

After the above start-up procedure, monitor 
the system functioning and ensure that the 
connections are tight, the safety relief valves 
function properly, and the heating system 
pressure is high enough.  

As the heating system can contain air after 
installation it should be deaerated several 
times.

 After deaeration check the pressure 

and add water if necessary. The protective 
hood of the air vent should be open. The 
system pressure should be approx. 1 to 1.5 bar 
(check pressure gauge at section 4.1.). 

Expansion tank pre-pressure must be 
checked every couple of years. 

PW operation is fully automated, thus 
ensuring easy service and maintenance. 
However, every user should be familiar with 
the boiler service instruments: pressure gauge, 

regulating and safety devices, switches, and 
automatic controls.  

Check the safety relief valves of the heating 
unit at least twice a year. The safety valve is 
activated by turning it anti-clockwise, and 
water flows through the safety valve pipe. If 
this does not happen, the valve is faulted and 
must be replaced. Do not discharge over ½ 
litre of water per check-up. Carefully add 
some water after check-ups and adjust system 
pressure at 1 to 1,5 bar. 

The pressure of the system’s water space 
should remain stable and unchanged unless 
temperature varies. Variations depend on the 
expansion tank and its water space. If the 
amount of water in the system constantly 
decreases, i.e. you have to add water all the 
time, find and repair the leak point as soon as 
possible. Constantly adding fresh water 
contributes to corrosion in the piping. 

During summertime when no heating is 
required, the electric boiler can be switched 
off with the main switch of the unit.  

At the beginning of the heating period, ensure 
that the circulation pump functions properly 
and the system pressure is correct. Normal 
pump speed is III. To deaerate the pump, 
loosen the pump air screw holding the cap 
over the outlet as it can discharge water. If the 
pump has been out of use for a long while 
troubles can occur during start-up; if this is 
the case, use auxiliary start by turning the 
pump shaft next to the deaeration screw 
manually with a screwdriver (see picture 2.). 
Pump malfunction is avoided by switching 
pump on for a while once a month.

    

    

 

Picture 2. Circulation pump activation.                                                                                                              

1

. Open plug.

  

2

. Turn pump’s axle with e.g. a screwdriver.  

3

. Close plug

 

Summary of Contents for PW

Page 1: ...ELECTRIC BOILER PW INSTALLATION AND OPERATION MANUAL J SPI KNOWS HOW TO CREATE WARMTH AND COMFORT JASPI UK www northmangroup co uk Telephone 01392 247340 Email info northmangroup co uk...

Page 2: ...ture Decrease 9 5 Maintenance Menu 10 Troubleshooting 10 1 Insufficient Heat 10 2 Empty Automatic Control Screen 10 3 If the Cause of the Trouble Is Not Found 10 4 Resistance Values of Boiler Sensors...

Page 3: ...eating water temperatures maintains suitable user defined temperature in the heating system The boiler also functions without outdoor temperature control with a so called set temperature control PW is...

Page 4: ...3 1 Function Diagram...

Page 5: ...12 l Circulation pump 180 mm 25 40 R3 4 Safety relief valve DN 15 1 5 bar Automatic deaeration Shutoff drain R1 2 Max temperature 100 C Min temperature 0 C Supply Outdoor temperature sensor 1 current...

Page 6: ...olation 6 Water level switch 7 Circulation pump 8 Pressure gauge 9 Wall bracket 10 Sensor probe 11 Safety valve pipe R20 12 Drain and filling valve R15 13 Return Inlet R20 14 Outlet R20 15 Electric le...

Page 7: ...of the boiler back side and detach the bracket 2 Mount the bracket to a reinforced wall with four screws 3 Hang the boiler on the bracket hooks 4 Attach the two screws pulled out on phase 1 on top of...

Page 8: ...e equipped with a valve BY PASS valve which ensures the circulation between pump and boiler 6 Electric Wiring Only an authorized and qualified wiring company can install electric wiring Unit s interna...

Page 9: ...re that melt water and icing will not cause damage to the sensor If the outdoor sensor is installed near the wall inlet make sure that the inlet is insulated properly 10 11 Connection of current trans...

Page 10: ...7 Electrical Diagram...

Page 11: ...tches and automatic controls Check the safety relief valves of the heating unit at least twice a year The safety valve is activated by turning it anti clockwise and water flows through the safety valv...

Page 12: ...ature is 0 C The curve can be steeper in houses with radiator heating system Recommended starting curve is 35 With this curve heating system water temperature is approx 35 c when outdoor temperature i...

Page 13: ...9 1 Front Panel...

Page 14: ...control unit screens Normally the screen visible is basic screen state but when the timer is set or the unit receives power limitation or trouble messages the screen varies between basic screen state...

Page 15: ...9 3 Settings Heating control basic settings heating curve selecting fine adjusting and temperature limits...

Page 16: ...9 4 Temperature Decrease This screen state is for selecting if a lower or higher heating setting is being used at a certain time of day...

Page 17: ...9 5 Maintenance Menu For the installer only The service menu is for setting main fuse size of the property and max power of the unit...

Page 18: ...oor boiler sensor troubles the Error NOT CONNECTED message will be displayed on the screen When the outdoor sensor fails the automatic system will assume the outdoor temperature to be 0 C When the boi...

Page 19: ...set temperature according to set value 10 80 C When the boiler sensor is removed the regulator will switch power off 10 5 Current Transformer Check Current values applied to the main fuses of the hous...

Page 20: ...ower of the boiler stage limitation 1 6 See table at section 6 and 6 3 kW Step 6 12 2 kW Set value corresponding to the main fuse of the house 16 70 A A 63 A Temperature decrease 0 20 C C 0 C Selected...

Reviews: