background image

 

4 (8) 

2.   OPERATING PRINCIPLE 

 
Firewood (coal, briquets) is burnt on the ceramic grate on the basis of the rotary / 
lower combustion principle. Combustion air flows precisely where needed: to the 
furnace top, onto the fire bar, and down the bar into the firing throat for the final 
combustion phase to occur. 

 
 
3.   BOILER INSTALLATION 

 
Always  connect  the  burner  to  an  energy  storage  battery  of  500  to  2000  l  as 
appropriate for the application. For example, one fill of the furnace with dry birch 
wood  heats  1000  l  of  water  /  nonfreeze  medium  up  to  approximately  45ºC.  For 
equipment connection examples see Fig. 3 and 4. 

 

Connect a 1.5 bar relief valve to the boiler nozzle ensuring that the steam blow 
capacity of the valve matches the power of the boiler.  

 

The pre-pressure of the membrane expansion tank must be e.g. 0.5 bar and the 
volume of the tank must be at least 7 % of the entire water volume of the system.  
Mount a deaeration valve onto the top of the system pipework. 

 

The  cooling  coil  provides  even  more  safety.  While  installing  the  boiler,  connect 
the anti-boil thermal valve to the coil (optional supply). 
For the valve connection see Fig. 2. 

 

After  filling  the  pipework  connection,  take  care  to  ensure  that  potential  leakage 
could not damage the boiler.  

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Fig. 2  Anti-boil thermal valve 
connection to the cooling coil. 
 

Terminen venttiili – thermal valve 
Kylmä vesi – cold water 
Anturi - sensor 

Summary of Contents for ECOWOOD 25

Page 1: ...INSTALLATION AND OPERATION MANUAL ECOWOOD 25 JASPI KNOWS HEATING WWW JASPI CO UK...

Page 2: ...s specified in Chapters 2 10 2 11 3 4 and Subparagraphs and d Chapter 5 Appendix 1 of the directive becomes evident from the entire unit installation and operation instructions The entire unit is manu...

Page 3: ...12 Side brick 2 pcs 13 Rear fire plate 14 Front fire bar brick 15 Rear fire bar 16 Firing throat 17 Coal grate 18 Upper turbulators 19 Lower turbulators PARTS 20 Thermometer 21 Pressure gauge 22 Clea...

Page 4: ...see Fig 3 and 4 Connect a 1 5 bar relief valve to the boiler nozzle ensuring that the steam blow capacity of the valve matches the power of the boiler The pre pressure of the membrane expansion tank...

Page 5: ...arge pump UPS 25 60 9 Boiler cooling coil 2 Energy storage battery J SPI OVALI 6 Expansion tank 10 Boiler thermal valve 3 Hot water supply mixing valve 7 J SPI 6 kW tubular electric heater 11 1 5 bar...

Page 6: ...ank 14 Thermostatic charge valve 3 Energy storage battery J SPI OVALI 9 J SPI 6 kW tubular electric heater 13 Wood boiler thermal valve 4 Hot water supply mixing valve 10 Boiler filling valve 15 Diese...

Page 7: ...h Fig 5 between the front edge of the adjusting plate 30 of the firing throat and the brick of the fire bar 14 must be 12 mm Ajust the top air damper 24 to approx 55 mm clearance While firing keep the...

Page 8: ...Identification code 10 Background brick extension P02030 11 Background vertical brick M01650 12 Side brick M01651 13 Rear fire plate P01321 14 Front fire bar brick M01649 15 Rear fire bar P01320 16 Fi...

Reviews: