63
UMG 604
Power supply voltage
The power supply voltage must be connected to the UMG604 via a UL listed fuse.
Line circuit breaker
: 6A, type C (approved to UL / IEC)
Cylindrical fuses
: 0.6A, tripping characteristics M (medium time lag)
Cylindrical fuses
: 0.75A, tripping characteristics F (fast acting)
Installation overvoltage category
: II
Option 230V
Nominal range
: 95V .. 240V (45-65 Hz) or DC 135V .. 340V
Operating range
: +-10% of nominal range
Power consumption
: max 3.2W, max 9VA
Option 90V
Nominal range
: 50V .. 110V (45-65 Hz) or DC 50V .. 155V
Operating range
: +-10% of nominal range
Power consumption
: max 3.2W, max 9VA
Option 24V
Nominal range
: 20V .. 55V (45-65 Hz) or DC 20V .. 77V
Operating range
: +-10% of nominal range
Power consumption
: max 4W, max 9VA
Connectable conductors
Only one conductor may be connected per terminal connection!
Solid core, multi-core, flexible core
: 0.08 - 2,5 mm2, AWG 28 - 12
Pin-end connector, wire end ferrules
: 1.5 mm2, AWG 16