36
UMG 509
RS485 interface
In the UMG 509, the RS485 interface is designed
as a 3-pin plug contact, which communicates via
the Modbus RTU protocol.
A B
RS485 Bus
Correct
Incorrect
Termination resistors
The cable is terminated with resistors (120Ohm, 1/4W)
at the beginning and at the end of a segment.
Termination within the device is possible via the S1 DIP
switch of the UMG 509.
Terminal strip in the cabinet.
Device with RS485 interface.
(without termination resistor)
Device with RS485 interface.
(with termination resistor on the device)
Summary of Contents for UMG 509
Page 15: ...15 UMG 509...
Page 27: ...27 UMG 509...
Page 101: ...101 UMG 509...
Page 113: ...113 UMG 509...
Page 117: ...117 UMG 509...
Page 118: ...118 UMG 509 Dimension diagrams Cut out size 138 0 8 x 138 0 8 mm Rear side Patch cable...