114
UMG 509
Function parameters
• Measurement via current transformer ../5A
• Measurements with 50/60 Hz
Function
Symbol
Precision class
Metering range
Display range
Total effective power
P
0.2
5)
(IEC61557-12)
0 to 15.3kW
0 W to 9999 GW *
Total reactive power
QA
6)
, Qv
6)
1 (IEC61557-12)
0 to 15.3 kvar
0 varh .. 9999 Gvar *
Total apparent power
SA, Sv
6)
0.2
5)
(IEC61557-12)
0 to 15.3 kVA
0 VA to 9999 GVA *
Total effective energy
Ea
0.2S
5) 7)
(IEC61557-12)
0 to 15.3 kWh
0 Wh to 9999 GWh *
Total reactive energy
ErA
6)
, ErV
6)
1 (IEC61557-12)
0 to 15.3 kvarh
0 varh .. 9999 Gvarh *
Total apparent energy
EapA,EapV
6)
0.2
5)
(IEC61557-12)
0 to 15.3 kVAh
0 VAh to 9999 GVAh *
Frequency
f
0.05 (IEC61557-12)
40 to 70 Hz
40 Hz to 70 Hz
Phase current
I
0.2 (IEC61557-12)
0.001 to 7 Arms
0 A to 9999 kA
Measured neutral conductor current
IN
0.2 (IEC61557-12)
0.001 to 7 Arms
0 A to 9999 kA
Residual currents I5, I6
IDIFF
1 (IEC61557-12)
0 to 40 mArms
0 A to 9999 kA
Computed neutral conductor current
INc
0.5 (IEC61557-12)
0.001 to 22.2 A
0 A to 9999 kA
Voltage
U L-N
0.1 (IEC61557-12)
10 to 600 Vrms
0 V to 9999 kV
Voltage
U L-L
0.1 (IEC61557-12)
18 to 1000 Vrms
0 V to 9999 kV
Power factor
PFA, PFV
0.5 (IEC61557-12)
0.00 to 1.00
0 to 1
Short-term flicker, long-term flicker
Pst, Plt
-
-
-
-
Voltage drops
Udip
0.2 (IEC61557-12)
10 to 600 Vrms
0 V to 9999 kV
Voltage increases
Uswl
0.2 (IEC61557-12)
10 to 600 Vrms
0 V to 9999 kV
Transient overvoltages
Utr
0.2 (IEC61557-12)
10 to 600 Vrms
0 V to 9999 kV
Voltage interruptions
Uint
- -
-
-
Voltage unbalance
1)
Unba
0.2 (IEC61557-12)
10 to 600 Vrms
0 V to 9999 kV
Voltage unbalance
2)
Unb
0.2 (IEC61557-12)
10 to 600 Vrms
0 V to 9999 kV
Voltage harmonics
Uh
Cl. 1
(IEC61000-4-7)
up to 2.5 kHz
0 V to 9999 kV