58
UMG 508
Events
Events are threshold value violations of set
threshold values for current and voltage.
Here, threshold values are compared with the
full wave effective values for current and volta-
ge from the measurement channels. The event
record consists of a mean value, a minimum or
maximum value, a start time and an end time.
• Monitoring of the threshold values can be
switched off (Off/Manual).
• Threshold values must be set as a percentage
of the nominal value.
• Threshold values can be set for excess volta-
ge, undervoltage and overcurrent.
• An event is triggered if in the course of the pre-
run period there is an uninterrupted threshold
value violation. An event is ended if there are
no threshold value violations in the course of
the after-run period.
• If an event has occurred, the corresponding
measurement value is recorded with the set
pre-run and after-run periods (respectively
0..1000 full waves).
• Event records are configured with the GridVis
and displayed with the event browser.
Limit value
Measured
value
Vollwellen-
effektivwert
Limit value
violations
before the
lead time
End time
Limit value violations
before the follow-up time
Event
Follow-up time
Lead time
Start time event
(Trigger time)
Event record
Pre-run
After-run
Fig. Shows the full wave effective values for an
event.