71
UMG 104
Current measurement
Nominal current
: 5A
Rated current
: 6A
Fuse protection for direct measurement
(without current transformer)
: 6A Char. B (approved i.a.w. UL/IEC)
Resolution in the display
: 10mA
Measurement range
: 0.001 .. 8.5Arms
Crest-faktor
: 2 (referring to 6 Arms)
Measurement category
: 300 V CAT III
Specified impulse withstand voltage
: 4 kV
Power input
: approx 0.2 VA (Ri=5 mohm)
Overload for 1 sec
: 100 A (sinusoidal)
Scanning frequency
: 20 kHz
Summary of Contents for UMG 104
Page 69: ...69 UMG 104...