66
UMG 104
Temperature measurement input
Update time
: approx 200 ms
Connectable sensors
: PT100, PT1000, KTY83, KTY84
Total burden ( cable)
: max 4 kohm
Sensor type
Temperature range
Resistance range
Measurement
uncertainty
KTY83
-55 ° .. +175 °C
500 ohm .. 2.6 kohm
± 1.5% rng
KTY84
-40 ° .. +300 °C
350 ohm .. 2.6 kohm
± 1.5% rng
PT100
-99 ° .. +500 °C
60 ohm .. 180 ohm
± 1.5% rng
PT1000
-99 ° .. +500 °C
600 ohm .. 1,8 kohm
± 1.5% rng
rng = measuring range
Cable length
: up to 30 m unshielded
: greater than 30 m shielded
Connectable conductors
Solid core, multi-core, flexible core
: 0.08 - 1.5 mm2
Pin-end connector, wire end ferrules
: 1 mm2, only one conductor may be connected
per terminal connection!