![janitza Prophi Operating Instructions Manual Download Page 54](http://html1.mh-extra.com/html/janitza/prophi/prophi_operating-instructions-manual_3322416054.webp)
Page 54
Reactive Power Controller
= Key 1
= Key 2
= Key 3
Technical data
Weight
: 1kg
Combustion value
:ca. 700J (190Wh)
Ambient conditions
Overvoltage class
: III
Pollution degree
: 2
Operating temperature
: -10°C .. +55°C
Storing temperature
: -20°C .. +60°C
Spurious radiation (residential areas):
DIN EN61326-1:2006, class B
IEC61326-1:2005
Sensibility to disturb. (industrial areas) :
DIN EN61326-1:2006, class A
IEC61326-1:2005
Sensibility to disturb. (industrial areas) :
DIN EN61326-1:2006, table 2
IEC61326-1:2005
Safety guidelines
:EN61010-1 08.2002
IEC61010-1:2001
Mounting position
: any
Operating height
: 0 .. 2000m over NN
Humidity class
: 15% to 95% without dew
Protection class
: I =Device with protective wire
Protection class
Front
: IP65 according to IEC60529
Back
: IP20 according to IEC60529
Inputs and outputs
Tariff changeover
Current consumption
: about 2,5mA .. 10mA
Switching outputs
Testvoltage against ground
: 2200V AC
Relay outputs
Switching voltage
: max. 250VAC
Switching power
: max. 1000W
Max. switching frequency
: 0,25Hz
Mechanical life expectancy
: >30x106 switchings
Electrical life expectancy
: >7x106 switchings
(Load = 200VA, cosphi=0,4)
transistor outputs
Switching voltage
: 15 .. 30VDC
Switching current
: max. 50mA
Max. switching frequency : 10Hz
Measurement
Measurement and supply voltage U: see type plate
Range for U
: +10% , -15%
Prefuse
: 2A .. 10 A
Power consumption
: max. 7VA
Rated pulse voltage
: 4kV
Tested voltage against ground
: 2200V AC
Frequency of fundamental
: 45Hz .. 65Hz
Current measurement
Signal frequency
: 45Hz .. 1200Hz
Power consumption
: about 0,2 VA
Rated current at../5A (/1A)
: 5A (1A)
Minimum working current : 10mA
Maximum current
: 5,3A (sinus shape)
Overload
: 180A for 2 Sec.
Measuring rate
: 30(50) Measurement/Sec.
Actualization of indication : 1 / second
Zero voltage release
: < 15ms
Measurement accuracy
Voltage
: +- 0,5% omr
Current
: +- 0,5% omr
cos(phi)
: +- 1,0% omv
1)2)
Power
: +- 1,0% omr
Frequency
: +- 0,5% omv
2)
Those specifications presuppose a yearly calibration and a preheating
of 10 minutes.
omr = of measuring range
omv = of measured value
1) Valid for current inputs >0.2A and in cos(phi) range 0,85 up to 1,00.
2) In the range of -10..18°C and 28..55°C an additional inaccuracy of +-0,2‰ of measured value per K must be respected.
3) Devices with option "RS485 interface" are only suitable for an ambient temperature of -10°C .. +50°C.