Prophi
®
15T-III
12
Section 6: PROGRAM-MODE (manual programming)
Pressing the button “Operation Mode“ one time switches from automatic operation to the
program mode.
The upper part of the display always shows the parameter, the adjustable values are
shown in the lower part. Editable values are generally given in square brackets. Changes
of these values can be done by the buttons
é
/
ê
. By pressing the “ENTER-button” the
value is stored. Pressing the “ESC”-button allows to go one step back (without storing).
1 LANGUAGE
This selects the language of the operating menu
[GERMAN, ENGLISH, SPANISH, RUSSIAN, TURKISH]
2 CONTROL-MODE
[1...16]
16 different controlling operation modes can be adjusted at the Prophi 15T-III
according the following table:
Mode Kind of measure- Number/type
Connection of
Operation mode
No. ment(number CT) of capacitors
capacitors
see page 6
1
3-phase
3x 5 single phase
L-N
Stand-alone
2
3-phase
max.3x4 1-phase
L-N
Stand-alone
+ Rest 3-phase
3-phase
MIX - MODE
3
3-phase
3x 5 single phase
L-L
Stand-alone
4
3-phase
1x 15 threephase
3-phase
Stand-alone
5
1-phase
1x 15 threephase
3-phase
Stand-alone
6
1-phase
1x 15 threephase
3-phase
Sytem current meas.
internal via L2 / L3
7
3-phase
3x 5 single phase
L-N
Hybrid mode
1x Prophi 12RS
8
3-phase
3x 5 single phase
L-N
Hybrid mode
2x Prophi 12RS
9
3-phase
3x 5 single phase
L-L
Hybrid mode
1x Prophi 12RS
10
3-phase
3x 5 single phase
L-L
Hybrid mode
2x Prophi 12RS
11
3-phase
1x 15 three phase
3-phase
Hybrid mode
1x Prophi 12RS
12
3-phase
1x 15 three phase
3-phase
Hybrid mode
2x Prophi 12RS
13
1-phase
1x 15 three phase
3-phase
Hybrid mode
1x Prophi 12RS
14
1-phase
1x 15 three phase
3-phase
Hybrid mode
2x Prophi 12RS
15
3-phase
1x 15 three phase
3-phase
Coupling mode
16
1-phase
1x 15 three phase
3-phase
Coupling mode
- 11 -
PROGRAM-MODE
1 LANGUAGE [1]
[ ENGLISH ]