Section 4 Automatic operation - display of network parameter
The device is set to automatic operation as standard (not AUTO-INIT). Capacitor stages
are then automatically connected in or out in order to reach the target power factor. This
happens if the required reactive power is approx. 1/3 higher than the value of the
smallest capacitor step.
In automatic operation, various network parameters can be displayed by repeatedly
pressing the "ENTER” key:
Action
Display
ENTER
1 LINE VOLTAGE in V
/%
ENTER
2 APPARENT CURRENT in A
/%
ENTER
3 REACTIVE POWER in kvar /%
ENTER
4 ACTIVE POWER in kW
/%
ENTER
5 APPARENT POWER in kVA
/%
ENTER
6 DIFF. kVAR TO TARGET COS
ENTER
7 FREQUENCY in Hz /min / max
ENTER
8 TEMPERATURE in °C / °F
ENTER
9 HARMONICS
V / %, I / %
Selection via arrow-keys
ENTER
10 HARMONICS THD-V/%, THD-I/%
11 Compensation power in kvar
ENTER
12 ENERGY
(kWh, kvarh, consumption, delivery)
reset in: service / max.value reset
ENTER
Software version
ENTER
Return to: 1
The power value specifies the total power (3-phase) assuming symmetrical load. If no
key is pressed for 120 seconds, the display automatically returns to the operating status!
Under “13 Date-Time” the date format 12h/24h setting can be changed by the arrow
buttons (only version /RS).
ENTER
ENTER
13 DATE - TIME
Repeated pressing of the "Operating Mode” key takes the user to the various menus:
- 8 -
Auto operation
Programming
Expert Mode 2
Manual operat.
Display-Editor
back to 1
Service
Expert Mode 1
AUTO-MODE
------------------
AUTO-MODE
------------------
3 REACTIVE POWER
118 kvar
10 HARMONICS THD rel.
V 1.7% I 0.8%
INTERFACE