Current measuring module
for the UMG 801
Installation instructions
Module 800-CT8-A - current measuring module 5 A
Deutsche V
ersion:
siehe V
or
derseite
2
Safety
Safety instructions
The installation instructions do not include a
complete list of all safety measures necessary for
operating the device.
Special operating conditions may require
additional measures. The installation instructions
contain notes that must be observed for your
personal safety and to prevent property damage.
Symbols used on the device:
The additional symbol on the
device itself indicates an electrical
danger that can result in serious
injuries or death.
The general warning symbol calls
attention to possible risks of injury.
Observe all the instructions listed
under this symbol in order to
prevent injuries or even death.
Safety measures
When operating electrical devices, specific parts
of these devices and their components inevitably
carry dangerous voltage. As a result, serious
personal injuries or property damage can occur if
they are not handled correctly:
• Before connection, ground the device and its
components at the ground wire connection, if
available.
• Dangerous voltages may be present in all
circuit parts connected to the voltage supply.
• There may still be dangerous voltages present
in the device or the components even after
disconnection of the supply voltage (capacitor
storage).
• Do not operate equipment with open current
transformer circuits.
• Do not exceed the threshold values specified
in the user manual and on the rating
plate. This must also be observed during
inspections and commissioning.
• Observe the safety instructions and
warning notices in the usage information
that accompanies the devices and their
components!
Qualified personnel
To prevent personal injuries and property damage,
only qualified personnel with electrical engineering
training may work on the base unit and its
components. They must also have knowledge
• of the national accident prevention regulations.
• of safety technology standards.
• in the installation, commissioning and
operation of the device and the components.
Intended use
The modules/components
• are intended for
industrial control usage
only.
• are intended as expansion or transfer modules
for the UMG 801 base unit in switch cabinets
and small distribution boards. (Please observe
the usage information associated with the
base unit).
• may only be mounted to base units that are
disconnected from the power supply (see
“Assembly” step).
• are not intended for installation in vehicles!
Use of the base unit with modules in
stationary equipment is considered an
unusual environmental condition and is only
permissible by special agreement.
• are not intended for installation in areas
exposed to harmful oils, acids, gases, vapors,
dust and radiation, etc.
Disclaimer
Observing the usage information for the devices is
a prerequisite for safe operation and for achieving the
specified performance characteristics and product
features. Janitza electronics GmbH assumes no
liability for personal injuries, property damage and
financial losses resulting from the failure to observe
the usage information. Make sure that your usage
information is legible and accessible.
Further usage information, such as e.g. the
installation instructions or user manual for the
base unit, can be found on our web site
www.janitza.com under Support > Downloads.
Copyright notice
© 2019 - Janitza electronics GmbH - Lahnau.
All rights reserved. Any duplication, processing,
distribution and any other kind of use, even in
part, is prohibited.
Subject to technical changes.
• Make sure that the installation instructions
match your device.
• Make sure you have first read and understood
the usage information accompanying the
product.
• Keep the usage information accompanying
the product accessible through its service life
and hand it over to the subsequent owner
where applicable.
• Please refer to www.janitza.de for information
concerning device revisions and the
associated adjustments to the usage
information accompanying the product.
Disposal
Please observe the national regulations. Dispose
of individual parts, where necessary, depending
on the properties and existing country-specific
regulations, e.g. as:
• Electronic waste
• Batteries and accumulators
• Plastic
• Metals
or commission a certified
disposal company with the scrapping.
Relevant laws,
applied standards and directives
Please refer to the Declaration of Conformity
on our web site (www.janitza.com) for the laws,
standards and directives applied by Janitza
electronics GmbH for the device.
3
7
WARNING
Risk of injury due to electric voltage or electrical
current!
When handling electrical currents or voltages,
serious personal injuries or death can occur due to:
· Touching live exposed or stripped cores.
· Device inputs that are dangerous to touch.
Before starting work on your system:
·
Disconnect it from the power supply!
·
Secure it against being switched back on!
·
Verify disconnection from power!
·
Ground and short circuit!
·
Cover or block off neighboring parts that are
under voltage!
Incoming goods inspection
The prerequisites for trouble-free and safe
operation of the devices and their components
include proper transport, storage, setup and
assembly, as well as careful operation and
maintenance.
Exercise caution when unpacking and packing
the device, without using force and only using
suitable tools.
Check:
• Devices and components by performing
a visual inspection to ensure a flawless
mechanical condition.
• The scope of delivery (see user manual) for
completeness before beginning the installation
of your devices and components.
If you assume that safe operation is no longer
possible, shut down your device with the
components immediately and secure it from being
unintentionally started back up again.
It can be assumed that safe operation is
impossible if, for example, the device with
components:
• Has visible damage.
• No longer functions despite an intact power
supply.
• Was subjected to extended periods of
unfavorable conditions (e.g. storage outside
of the permissible climate thresholds without
adjustment to the room climate, condensation,
etc.) or transport stress (e.g. falling from an
elevated position, even without visible external
damage, etc.).
User manual:
WARNING
Danger due to noncompliance with warning
and safety instructions.
Noncompliance with warning and safety
instructions on the device itself and in the
information on using the device and its
components can lead to injury or even death.
Observe safety instructions and warning notices
on the device itself and in the usage information
associated with the devices and their components,
such as:
· Installation instructions.
· User manual.
· Safety instructions supplement.
The current measuring module
· enhances the scope of functions of the base
unit with additional current measuring channels
(2 blocks á 4 current measuring channels).
· is suitable for current transformers with trans-
former ratios of ../1 A or ../5 A.
Device short description and assembly - current measuring module
Safety instructions in the installation instructions
are highlighted with a warning triangle and are
presented as follows depending on the level of risk:
ATTENTION
Warns of an imminently dangerous situation that
can result in property damage or environmental
damage in the event of noncompliance.
DANGER
Warns of an imminent danger that will result
in serious or fatal injuries in the event of
noncompliance.
CAUTION
Warns of an imminently dangerous situation that
can result in minor or moderate injuries in the event
of noncompliance.
INFORMATION
Points out procedures in which there are
no
dangers
of personal injuries or property damage.
WARNING
Warns of a potentially dangerous situation that can
result in serious injuries or death in the event of
noncompliance.
INFORMATION
· The scope of delivery of the module includes
the appropriate bus connector (JanBus
interface) for connection to the base unit or
additional modules!
· In addition to the current measuring module,
also observe the usage information for your
base unit!
CAUTION
Non-observance of the assembly instructions
may result in property damage or cause
personal injury!
Noncompliance with the assembly instructions may
cause damage to your base unit with modules or
destroy it and may also result in personal injury.
·
Observe the assembly instructions of your
base unit.
·
Before assembly of the modules:
-
Disconnect the system from the power
supply! Secure it against being switched
back on! Verify disconnection from power!
Ground and short circuit! Cover or block off
neighboring parts that are under voltage!
·
Ensure sufficient air circulation in your
installation environment and, where applicable,
sufficient cooling.
·
Return defective modules to the manufacturer.
DIN rail
1.
2.
Bus connector
Module 800-CT8-A
UMG 801 (base unit)
Module 800-CT8-A
Bottom latch
Taking into consideration the assembly
instructions for your base unit (check bus
connection assembly, among other things!),
assemble the modules when the system is
disconnected from the power supply as follows:
1. If not already done, insert the bus connector
(JanBus interface) included in the respective
scope of delivery in the socket on the bottom
of your module.
2. Press your module with bus connector onto
the DIN rail until the bottom latches engages.
3. Slide the contacts of your module bus connector
into the sockets of the base unit bus connector
(or in the sockets of the connected module) so
that the bus connectors (devices) are linked.
Then wire your module and apply voltage to the
base unit (system). The base unit recognizes the
module automatically.
The base unit (UMG 801)
· with current measuring module measures current
exclusively via a current transformer. The current
transformers require basic insulation according to
IEC 61010-1:2010 for the rated voltage of the circuit.
· permits assembly of up to 10 modules.
ATTENTION
During the start-up process, the base unit does
not recognize the module!
If there is no communication to the module, the
module functions are not supported (current
measurements).
· Disconnect your system from the power supply
and check the condition of the bus connector
and the connection of the module to the base unit
(JanBus interface). If necessary, slide the contacts
of the module bus connector into the sockets of
the base unit bus connector (or the connected
module) so that the bus connectors (devices) are
linked.
· If necessary, restart the base unit.
· If the specified measures are unsuccessful, please
contact our support team - www.janitza.com
3.
Figure Assembly example:
UMG 801 (base unit) with module 800-CT8-A
Bus connector
contacts
DIN rail
“Current measurement” with terminal assignment connection variant
UMG 801
(Basisgerät)
JanBus-Schnittstelle
S1
S2
S1
S2
S1
S2
9
10
11 12
13 14
I
5
I
6
I
7
S1
S2
15 16
I
8
S1
S2
S1
S2
S1
S2
1
2
3
4
5
6
I
1
I
2
I
3
S1
S2
7
8
I
4
S1
S2
Verbraucher
L1
L2
L3
N
S1
S2
S1
S2
S1
S2
Verbraucher
L1
L2
L3
N
S2
S1
S2
S1
S2
S1
S2
S1
JanBus-Schnittstelle
JanBus-Schnittstelle
Modul 800-CT8-A
Strommessung
Strommessung
4
ATTENTION
Improper handling may cause damage to the
module and result in property damage!
The contacts of the bus connector (JanBus
interface) can bend or break and destroy the bus
connector!
· Never touch or manipulate the contacts of the bus
connector.
· Never use force to press the module with bus
connector contacts into the bus connector
sockets!
· When handling, transporting and storing the
module, protect the contacts of the bus connector.
Bottom latch
Bottom latch
Bus connector
sockets
Fig. “Base unit with module” assembly on DIN rail.
Fig. Module 800-CT8-A connection variant
Bus connector
sockets
JanBus
interface
JanBus inter-
face for additional
modules
End angle
End angle
5
6
Current measurement
The
module 800-CT8-A
· measures current exclusively via a current transformer.
· permits connection of current transformers with
secondary currents of ../1 and ../5 A for current
measurement inputs I1 to I8
· has a current transformer ratio of 5/5 A as the
standard setting (I1 to I8).
· does not measure DC currents.
WARNING
Risk of injury due to high currents and high
electrical voltages!
Serious personal injuries or death can occur due
to:
· Touching live exposed or stripped cores.
· Inputs of the devices, components and modules
that are dangerous to touch.
Therefore, please observe the following for your
system:
·
Before starting work, disconnect it from the
power supply!
·
Secure it against being switched back on!
·
Verify disconnection from power!
·
Ground and short circuit! Use the ground
connection points with the ground symbol for
grounding!
·
Cover or block off neighboring parts that are
under voltage!
WARNING
Electrical currents and voltages!
Open current transformers that are operated on the
secondary side (high voltage spikes) can result in
serious personal injuries or even death.
Avoid the open operation of the current trans-
formers and short-circuit unloaded transform-
ers.
INFORMATION
Recommendation:
The current transformer ratios are configured
self-explanatorily in the “device configuration”
function of the GridVis
®
software.
Dismantling
Bus connector
contacts
Screwdriver for
unlatching
Bus connector
sockets
Bottom latch
Bottom latch
ATTENTION
Handling your module too roughly may cause
damage to the module and result in property
damage!
The bus connector contacts and the bottom latches
can be damaged or broken off during dismantling of
your module.
·
Never wrench the module from the DIN rail
using force.
·
Decouple the bus connector (JanBus interface)
beforehand and carefully unlatch the bottom
latch of the module using a screwdriver!
Dismantling the module:
1. Disconnect the system from the power supply!
Secure it against being switched back on! Verify
disconnection from power! Ground and short
circuit! Cover or block off neighboring parts that
are under voltage!
2. Disconnect the wiring of your module.
3. Decouple the bus connector (JanBus interface)
of your module from the base unit and/or the
connected modules by pulling out your module.
4. Unlatch all bottom latches of your module.
Recommendation:
Use a screwdriver for this
(carefully!).
5. Remove the DIN rail from your module without
touching or damaging the bus connector
contacts.
Bus
connector
sockets
JanBus
interface
DIN rail
JanBus
interface for
additional
modules
ATTENTION
Property damage due to dismantling or decoupling
the module during operation!
Dismantling or decoupling the module while it is
communicating with the base unit can lead to damage
to your devices!
·
Disconnect your system from the power supply
before dismantling or decoupling the module!
Secure it against being turned back on! Verify
disconnection from power! Ground and short
circuit! Cover or block off neighboring parts that
are under voltage!
Technical data
General information
Net weight
(with plug terminals)
Approx. 220 g (0.49 lb)
Device dimensions
approx. w = 73 mm (2.87 in),
h = 90 mm (3.54 in),
d = 76 mm (2.99 in)
Installation position
discretionary
Mounting/assembly -
suitable DIN rails -
35 mm (1.38 in)
· TS 35/7.5 according to EN 60715
· TS 35/10
· TS 35/15 x 1.5
Protection class
IP20
Operating temperature
-10 °C (14 °F) .. +55 °C (131 °F)
Impact resistance
IK07 according to IEC 62262
Current measurement
module 800-CT8-A
Rated current
5 A
Channels
8 (2x4)
· 2 systems (L1, L2, L3, N)
· Individual channels
Metering range
0 .. 6 Arms
Crest factor
2 (based on 6 Arms)
Overload for 1 s
120 A (sinusoidal)
Resolution
0.1 mA (color graphic display 0.01A)
Overvoltage category
300 V CATII
Rated surge voltage
2,5 kV
Power consumption
approx. 0.2 VA (Ri = 5 m
Ω
)
Sampling frequency
8.3 kHz
Frequency of the
power frequency
40 Hz .. 70 Hz
Harmonics
1 .. 9. (only odd)
Transport and storage
The following information applies to devices which are
transported and stored in the original packaging
Free fall
1 m (39.37 in)
Temperature
K55
-25 °C (-13 °F) up to +70 °C (158 °F)
Relative humidity
5 to 95% at 25 °C (77 °F)
without condensation
Ambient conditions during operation, see base unit
Interface and energy supply
JanBus (proprietary)
Via bus connector
Item no. 33.03.378
Fig.: Module 800-CT8-A
INFORMATION
· Detailed technical data for the module
can be found in the user manual.
· Technical data for the base unit and
information on the procedure in the event
of errors can be found in the usage infor-
mation for your base unit.
Terminal connection capacity - Module 800-CT8-A
Connectable conductors.
Only one conductor can be connected per terminal.
Single core, multi-core,
fine-stranded
0.2 - 2.5 mm
2
, AWG 26-12
Cable end sleeve (not insulated)
· recommended stripping length
0.2 - 2.5 mm
2
, AWG 26-12
· 10 mm (0.3937 in)
Cable end sleeve (insulated) *
· recommended stripping
length **
0.2 - 2.5 mm
2
, AWG 26-12
· 12 mm
(≤1,5 mm
2
), 10 mm (>1.5 mm
2
) /
0.47 in (≤1.5 mm
2
), 0.39 in (>1.5 mm
2
)
Cable end sleeve
Length of the contact sleeve ** 8 - 12 mm (0.31 - 0.47 in)
Tightening torque screw
flange
0.2 Nm (1.77 lbf in)
*
... Applies to wire end sleeves with a maximum outer diameter of the
plastic collar up to 4.5 mm (0.18 in).
**
.. Depending on the type of cable end sleeves used (cable end sleeve
manufacturer).
General information
1
2
Janitza electronics GmbH
Vor dem Polstück 6
35633 Lahnau, Germany
Support tel. +49 6441 9642-22
E-mail: [email protected]
www.janitza.com
www
.janitza.com
Doc no. 2.053.007.1.g Status: 11/2022
Current measuring module
for the UMG 801
Installation instructions
Module 800-CT8-A - current measuring module 5 A
Deutsche V
ersion:
siehe V
or
derseite
2
Safety
Safety instructions
The installation instructions do not include a
complete list of all safety measures necessary for
operating the device.
Special operating conditions may require
additional measures. The installation instructions
contain notes that must be observed for your
personal safety and to prevent property damage.
Symbols used on the device:
The additional symbol on the
device itself indicates an electrical
danger that can result in serious
injuries or death.
The general warning symbol calls
attention to possible risks of injury.
Observe all the instructions listed
under this symbol in order to
prevent injuries or even death.
Safety measures
When operating electrical devices, specific parts
of these devices and their components inevitably
carry dangerous voltage. As a result, serious
personal injuries or property damage can occur if
they are not handled correctly:
• Before connection, ground the device and its
components at the ground wire connection, if
available.
• Dangerous voltages may be present in all
circuit parts connected to the voltage supply.
• There may still be dangerous voltages present
in the device or the components even after
disconnection of the supply voltage (capacitor
storage).
• Do not operate equipment with open current
transformer circuits.
• Do not exceed the threshold values specified
in the user manual and on the rating
plate. This must also be observed during
inspections and commissioning.
• Observe the safety instructions and
warning notices in the usage information
that accompanies the devices and their
components!
Qualified personnel
To prevent personal injuries and property damage,
only qualified personnel with electrical engineering
training may work on the base unit and its
components. They must also have knowledge
• of the national accident prevention regulations.
• of safety technology standards.
• in the installation, commissioning and
operation of the device and the components.
Intended use
The modules/components
• are intended for
industrial control usage
only.
• are intended as expansion or transfer modules
for the UMG 801 base unit in switch cabinets
and small distribution boards. (Please observe
the usage information associated with the
base unit).
• may only be mounted to base units that are
disconnected from the power supply (see
“Assembly” step).
• are not intended for installation in vehicles!
Use of the base unit with modules in
stationary equipment is considered an
unusual environmental condition and is only
permissible by special agreement.
• are not intended for installation in areas
exposed to harmful oils, acids, gases, vapors,
dust and radiation, etc.
Disclaimer
Observing the usage information for the devices is
a prerequisite for safe operation and for achieving the
specified performance characteristics and product
features. Janitza electronics GmbH assumes no
liability for personal injuries, property damage and
financial losses resulting from the failure to observe
the usage information. Make sure that your usage
information is legible and accessible.
Further usage information, such as e.g. the
installation instructions or user manual for the
base unit, can be found on our web site
www.janitza.com under Support > Downloads.
Copyright notice
© 2019 - Janitza electronics GmbH - Lahnau.
All rights reserved. Any duplication, processing,
distribution and any other kind of use, even in
part, is prohibited.
Subject to technical changes.
• Make sure that the installation instructions
match your device.
• Make sure you have first read and understood
the usage information accompanying the
product.
• Keep the usage information accompanying
the product accessible through its service life
and hand it over to the subsequent owner
where applicable.
• Please refer to www.janitza.de for information
concerning device revisions and the
associated adjustments to the usage
information accompanying the product.
Disposal
Please observe the national regulations. Dispose
of individual parts, where necessary, depending
on the properties and existing country-specific
regulations, e.g. as:
• Electronic waste
• Batteries and accumulators
• Plastic
• Metals
or commission a certified
disposal company with the scrapping.
Relevant laws,
applied standards and directives
Please refer to the Declaration of Conformity
on our web site (www.janitza.com) for the laws,
standards and directives applied by Janitza
electronics GmbH for the device.
3
7
WARNING
Risk of injury due to electric voltage or electrical
current!
When handling electrical currents or voltages,
serious personal injuries or death can occur due to:
· Touching live exposed or stripped cores.
· Device inputs that are dangerous to touch.
Before starting work on your system:
·
Disconnect it from the power supply!
·
Secure it against being switched back on!
·
Verify disconnection from power!
·
Ground and short circuit!
·
Cover or block off neighboring parts that are
under voltage!
Incoming goods inspection
The prerequisites for trouble-free and safe
operation of the devices and their components
include proper transport, storage, setup and
assembly, as well as careful operation and
maintenance.
Exercise caution when unpacking and packing
the device, without using force and only using
suitable tools.
Check:
• Devices and components by performing
a visual inspection to ensure a flawless
mechanical condition.
• The scope of delivery (see user manual) for
completeness before beginning the installation
of your devices and components.
If you assume that safe operation is no longer
possible, shut down your device with the
components immediately and secure it from being
unintentionally started back up again.
It can be assumed that safe operation is
impossible if, for example, the device with
components:
• Has visible damage.
• No longer functions despite an intact power
supply.
• Was subjected to extended periods of
unfavorable conditions (e.g. storage outside
of the permissible climate thresholds without
adjustment to the room climate, condensation,
etc.) or transport stress (e.g. falling from an
elevated position, even without visible external
damage, etc.).
User manual:
WARNING
Danger due to noncompliance with warning
and safety instructions.
Noncompliance with warning and safety
instructions on the device itself and in the
information on using the device and its
components can lead to injury or even death.
Observe safety instructions and warning notices
on the device itself and in the usage information
associated with the devices and their components,
such as:
· Installation instructions.
· User manual.
· Safety instructions supplement.
The current measuring module
· enhances the scope of functions of the base
unit with additional current measuring channels
(2 blocks á 4 current measuring channels).
· is suitable for current transformers with trans-
former ratios of ../1 A or ../5 A.
Device short description and assembly - current measuring module
Safety instructions in the installation instructions
are highlighted with a warning triangle and are
presented as follows depending on the level of risk:
ATTENTION
Warns of an imminently dangerous situation that
can result in property damage or environmental
damage in the event of noncompliance.
DANGER
Warns of an imminent danger that will result
in serious or fatal injuries in the event of
noncompliance.
CAUTION
Warns of an imminently dangerous situation that
can result in minor or moderate injuries in the event
of noncompliance.
INFORMATION
Points out procedures in which there are
no
dangers
of personal injuries or property damage.
WARNING
Warns of a potentially dangerous situation that can
result in serious injuries or death in the event of
noncompliance.
INFORMATION
· The scope of delivery of the module includes
the appropriate bus connector (JanBus
interface) for connection to the base unit or
additional modules!
· In addition to the current measuring module,
also observe the usage information for your
base unit!
CAUTION
Non-observance of the assembly instructions
may result in property damage or cause
personal injury!
Noncompliance with the assembly instructions may
cause damage to your base unit with modules or
destroy it and may also result in personal injury.
·
Observe the assembly instructions of your
base unit.
·
Before assembly of the modules:
-
Disconnect the system from the power
supply! Secure it against being switched
back on! Verify disconnection from power!
Ground and short circuit! Cover or block off
neighboring parts that are under voltage!
·
Ensure sufficient air circulation in your
installation environment and, where applicable,
sufficient cooling.
·
Return defective modules to the manufacturer.
DIN rail
1.
2.
Bus connector
Module 800-CT8-A
UMG 801 (base unit)
Module 800-CT8-A
Bottom latch
Taking into consideration the assembly
instructions for your base unit (check bus
connection assembly, among other things!),
assemble the modules when the system is
disconnected from the power supply as follows:
1. If not already done, insert the bus connector
(JanBus interface) included in the respective
scope of delivery in the socket on the bottom
of your module.
2. Press your module with bus connector onto
the DIN rail until the bottom latches engages.
3. Slide the contacts of your module bus connector
into the sockets of the base unit bus connector
(or in the sockets of the connected module) so
that the bus connectors (devices) are linked.
Then wire your module and apply voltage to the
base unit (system). The base unit recognizes the
module automatically.
The base unit (UMG 801)
· with current measuring module measures current
exclusively via a current transformer. The current
transformers require basic insulation according to
IEC 61010-1:2010 for the rated voltage of the circuit.
· permits assembly of up to 10 modules.
ATTENTION
During the start-up process, the base unit does
not recognize the module!
If there is no communication to the module, the
module functions are not supported (current
measurements).
· Disconnect your system from the power supply
and check the condition of the bus connector
and the connection of the module to the base unit
(JanBus interface). If necessary, slide the contacts
of the module bus connector into the sockets of
the base unit bus connector (or the connected
module) so that the bus connectors (devices) are
linked.
· If necessary, restart the base unit.
· If the specified measures are unsuccessful, please
contact our support team - www.janitza.com
3.
Figure Assembly example:
UMG 801 (base unit) with module 800-CT8-A
Bus connector
contacts
DIN rail
“Current measurement” with terminal assignment connection variant
UMG 801
(Basisgerät)
JanBus-Schnittstelle
S1
S2
S1
S2
S1
S2
9
10
11 12
13 14
I
5
I
6
I
7
S1
S2
15 16
I
8
S1
S2
S1
S2
S1
S2
1
2
3
4
5
6
I
1
I
2
I
3
S1
S2
7
8
I
4
S1
S2
Verbraucher
L1
L2
L3
N
S1
S2
S1
S2
S1
S2
Verbraucher
L1
L2
L3
N
S2
S1
S2
S1
S2
S1
S2
S1
JanBus-Schnittstelle
JanBus-Schnittstelle
Modul 800-CT8-A
Strommessung
Strommessung
4
ATTENTION
Improper handling may cause damage to the
module and result in property damage!
The contacts of the bus connector (JanBus
interface) can bend or break and destroy the bus
connector!
· Never touch or manipulate the contacts of the bus
connector.
· Never use force to press the module with bus
connector contacts into the bus connector
sockets!
· When handling, transporting and storing the
module, protect the contacts of the bus connector.
Bottom latch
Bottom latch
Bus connector
sockets
Fig. “Base unit with module” assembly on DIN rail.
Fig. Module 800-CT8-A connection variant
Bus connector
sockets
JanBus
interface
JanBus inter-
face for additional
modules
End angle
End angle
5
6
Current measurement
The
module 800-CT8-A
· measures current exclusively via a current transformer.
· permits connection of current transformers with
secondary currents of ../1 and ../5 A for current
measurement inputs I1 to I8
· has a current transformer ratio of 5/5 A as the
standard setting (I1 to I8).
· does not measure DC currents.
WARNING
Risk of injury due to high currents and high
electrical voltages!
Serious personal injuries or death can occur due
to:
· Touching live exposed or stripped cores.
· Inputs of the devices, components and modules
that are dangerous to touch.
Therefore, please observe the following for your
system:
·
Before starting work, disconnect it from the
power supply!
·
Secure it against being switched back on!
·
Verify disconnection from power!
·
Ground and short circuit! Use the ground
connection points with the ground symbol for
grounding!
·
Cover or block off neighboring parts that are
under voltage!
WARNING
Electrical currents and voltages!
Open current transformers that are operated on the
secondary side (high voltage spikes) can result in
serious personal injuries or even death.
Avoid the open operation of the current trans-
formers and short-circuit unloaded transform-
ers.
INFORMATION
Recommendation:
The current transformer ratios are configured
self-explanatorily in the “device configuration”
function of the GridVis
®
software.
Dismantling
Bus connector
contacts
Screwdriver for
unlatching
Bus connector
sockets
Bottom latch
Bottom latch
ATTENTION
Handling your module too roughly may cause
damage to the module and result in property
damage!
The bus connector contacts and the bottom latches
can be damaged or broken off during dismantling of
your module.
·
Never wrench the module from the DIN rail
using force.
·
Decouple the bus connector (JanBus interface)
beforehand and carefully unlatch the bottom
latch of the module using a screwdriver!
Dismantling the module:
1. Disconnect the system from the power supply!
Secure it against being switched back on! Verify
disconnection from power! Ground and short
circuit! Cover or block off neighboring parts that
are under voltage!
2. Disconnect the wiring of your module.
3. Decouple the bus connector (JanBus interface)
of your module from the base unit and/or the
connected modules by pulling out your module.
4. Unlatch all bottom latches of your module.
Recommendation:
Use a screwdriver for this
(carefully!).
5. Remove the DIN rail from your module without
touching or damaging the bus connector
contacts.
Bus
connector
sockets
JanBus
interface
DIN rail
JanBus
interface for
additional
modules
ATTENTION
Property damage due to dismantling or decoupling
the module during operation!
Dismantling or decoupling the module while it is
communicating with the base unit can lead to damage
to your devices!
·
Disconnect your system from the power supply
before dismantling or decoupling the module!
Secure it against being turned back on! Verify
disconnection from power! Ground and short
circuit! Cover or block off neighboring parts that
are under voltage!
Technical data
General information
Net weight
(with plug terminals)
Approx. 220 g (0.49 lb)
Device dimensions
approx. w = 73 mm (2.87 in),
h = 90 mm (3.54 in),
d = 76 mm (2.99 in)
Installation position
discretionary
Mounting/assembly -
suitable DIN rails -
35 mm (1.38 in)
· TS 35/7.5 according to EN 60715
· TS 35/10
· TS 35/15 x 1.5
Protection class
IP20
Operating temperature
-10 °C (14 °F) .. +55 °C (131 °F)
Impact resistance
IK07 according to IEC 62262
Current measurement
module 800-CT8-A
Rated current
5 A
Channels
8 (2x4)
· 2 systems (L1, L2, L3, N)
· Individual channels
Metering range
0 .. 6 Arms
Crest factor
2 (based on 6 Arms)
Overload for 1 s
120 A (sinusoidal)
Resolution
0.1 mA (color graphic display 0.01A)
Overvoltage category
300 V CATII
Rated surge voltage
2,5 kV
Power consumption
approx. 0.2 VA (Ri = 5 m
Ω
)
Sampling frequency
8.3 kHz
Frequency of the
power frequency
40 Hz .. 70 Hz
Harmonics
1 .. 9. (only odd)
Transport and storage
The following information applies to devices which are
transported and stored in the original packaging
Free fall
1 m (39.37 in)
Temperature
K55
-25 °C (-13 °F) up to +70 °C (158 °F)
Relative humidity
5 to 95% at 25 °C (77 °F)
without condensation
Ambient conditions during operation, see base unit
Interface and energy supply
JanBus (proprietary)
Via bus connector
Item no. 33.03.378
Fig.: Module 800-CT8-A
INFORMATION
· Detailed technical data for the module
can be found in the user manual.
· Technical data for the base unit and
information on the procedure in the event
of errors can be found in the usage infor-
mation for your base unit.
Terminal connection capacity - Module 800-CT8-A
Connectable conductors.
Only one conductor can be connected per terminal.
Single core, multi-core,
fine-stranded
0.2 - 2.5 mm
2
, AWG 26-12
Cable end sleeve (not insulated)
· recommended stripping length
0.2 - 2.5 mm
2
, AWG 26-12
· 10 mm (0.3937 in)
Cable end sleeve (insulated) *
· recommended stripping
length **
0.2 - 2.5 mm
2
, AWG 26-12
· 12 mm
(≤1,5 mm
2
), 10 mm (>1.5 mm
2
) /
0.47 in (≤1.5 mm
2
), 0.39 in (>1.5 mm
2
)
Cable end sleeve
Length of the contact sleeve ** 8 - 12 mm (0.31 - 0.47 in)
Tightening torque screw
flange
0.2 Nm (1.77 lbf in)
*
... Applies to wire end sleeves with a maximum outer diameter of the
plastic collar up to 4.5 mm (0.18 in).
**
.. Depending on the type of cable end sleeves used (cable end sleeve
manufacturer).
General information
1
2
Janitza electronics GmbH
Vor dem Polstück 6
35633 Lahnau, Germany
Support tel. +49 6441 9642-22
E-mail: [email protected]
www.janitza.com
www
.janitza.com
Doc no. 2.053.007.1.g Status: 11/2022
Current measuring module
for the UMG 801
Installation instructions
Module 800-CT8-A - current measuring module 5 A
Deutsche V
ersion:
siehe V
or
derseite
2
Safety
Safety instructions
The installation instructions do not include a
complete list of all safety measures necessary for
operating the device.
Special operating conditions may require
additional measures. The installation instructions
contain notes that must be observed for your
personal safety and to prevent property damage.
Symbols used on the device:
The additional symbol on the
device itself indicates an electrical
danger that can result in serious
injuries or death.
The general warning symbol calls
attention to possible risks of injury.
Observe all the instructions listed
under this symbol in order to
prevent injuries or even death.
Safety measures
When operating electrical devices, specific parts
of these devices and their components inevitably
carry dangerous voltage. As a result, serious
personal injuries or property damage can occur if
they are not handled correctly:
• Before connection, ground the device and its
components at the ground wire connection, if
available.
• Dangerous voltages may be present in all
circuit parts connected to the voltage supply.
• There may still be dangerous voltages present
in the device or the components even after
disconnection of the supply voltage (capacitor
storage).
• Do not operate equipment with open current
transformer circuits.
• Do not exceed the threshold values specified
in the user manual and on the rating
plate. This must also be observed during
inspections and commissioning.
• Observe the safety instructions and
warning notices in the usage information
that accompanies the devices and their
components!
Qualified personnel
To prevent personal injuries and property damage,
only qualified personnel with electrical engineering
training may work on the base unit and its
components. They must also have knowledge
• of the national accident prevention regulations.
• of safety technology standards.
• in the installation, commissioning and
operation of the device and the components.
Intended use
The modules/components
• are intended for
industrial control usage
only.
• are intended as expansion or transfer modules
for the UMG 801 base unit in switch cabinets
and small distribution boards. (Please observe
the usage information associated with the
base unit).
• may only be mounted to base units that are
disconnected from the power supply (see
“Assembly” step).
• are not intended for installation in vehicles!
Use of the base unit with modules in
stationary equipment is considered an
unusual environmental condition and is only
permissible by special agreement.
• are not intended for installation in areas
exposed to harmful oils, acids, gases, vapors,
dust and radiation, etc.
Disclaimer
Observing the usage information for the devices is
a prerequisite for safe operation and for achieving the
specified performance characteristics and product
features. Janitza electronics GmbH assumes no
liability for personal injuries, property damage and
financial losses resulting from the failure to observe
the usage information. Make sure that your usage
information is legible and accessible.
Further usage information, such as e.g. the
installation instructions or user manual for the
base unit, can be found on our web site
www.janitza.com under Support > Downloads.
Copyright notice
© 2019 - Janitza electronics GmbH - Lahnau.
All rights reserved. Any duplication, processing,
distribution and any other kind of use, even in
part, is prohibited.
Subject to technical changes.
• Make sure that the installation instructions
match your device.
• Make sure you have first read and understood
the usage information accompanying the
product.
• Keep the usage information accompanying
the product accessible through its service life
and hand it over to the subsequent owner
where applicable.
• Please refer to www.janitza.de for information
concerning device revisions and the
associated adjustments to the usage
information accompanying the product.
Disposal
Please observe the national regulations. Dispose
of individual parts, where necessary, depending
on the properties and existing country-specific
regulations, e.g. as:
• Electronic waste
• Batteries and accumulators
• Plastic
• Metals
or commission a certified
disposal company with the scrapping.
Relevant laws,
applied standards and directives
Please refer to the Declaration of Conformity
on our web site (www.janitza.com) for the laws,
standards and directives applied by Janitza
electronics GmbH for the device.
3
7
WARNING
Risk of injury due to electric voltage or electrical
current!
When handling electrical currents or voltages,
serious personal injuries or death can occur due to:
· Touching live exposed or stripped cores.
· Device inputs that are dangerous to touch.
Before starting work on your system:
·
Disconnect it from the power supply!
·
Secure it against being switched back on!
·
Verify disconnection from power!
·
Ground and short circuit!
·
Cover or block off neighboring parts that are
under voltage!
Incoming goods inspection
The prerequisites for trouble-free and safe
operation of the devices and their components
include proper transport, storage, setup and
assembly, as well as careful operation and
maintenance.
Exercise caution when unpacking and packing
the device, without using force and only using
suitable tools.
Check:
• Devices and components by performing
a visual inspection to ensure a flawless
mechanical condition.
• The scope of delivery (see user manual) for
completeness before beginning the installation
of your devices and components.
If you assume that safe operation is no longer
possible, shut down your device with the
components immediately and secure it from being
unintentionally started back up again.
It can be assumed that safe operation is
impossible if, for example, the device with
components:
• Has visible damage.
• No longer functions despite an intact power
supply.
• Was subjected to extended periods of
unfavorable conditions (e.g. storage outside
of the permissible climate thresholds without
adjustment to the room climate, condensation,
etc.) or transport stress (e.g. falling from an
elevated position, even without visible external
damage, etc.).
User manual:
WARNING
Danger due to noncompliance with warning
and safety instructions.
Noncompliance with warning and safety
instructions on the device itself and in the
information on using the device and its
components can lead to injury or even death.
Observe safety instructions and warning notices
on the device itself and in the usage information
associated with the devices and their components,
such as:
· Installation instructions.
· User manual.
· Safety instructions supplement.
The current measuring module
· enhances the scope of functions of the base
unit with additional current measuring channels
(2 blocks á 4 current measuring channels).
· is suitable for current transformers with trans-
former ratios of ../1 A or ../5 A.
Device short description and assembly - current measuring module
Safety instructions in the installation instructions
are highlighted with a warning triangle and are
presented as follows depending on the level of risk:
ATTENTION
Warns of an imminently dangerous situation that
can result in property damage or environmental
damage in the event of noncompliance.
DANGER
Warns of an imminent danger that will result
in serious or fatal injuries in the event of
noncompliance.
CAUTION
Warns of an imminently dangerous situation that
can result in minor or moderate injuries in the event
of noncompliance.
INFORMATION
Points out procedures in which there are
no
dangers
of personal injuries or property damage.
WARNING
Warns of a potentially dangerous situation that can
result in serious injuries or death in the event of
noncompliance.
INFORMATION
· The scope of delivery of the module includes
the appropriate bus connector (JanBus
interface) for connection to the base unit or
additional modules!
· In addition to the current measuring module,
also observe the usage information for your
base unit!
CAUTION
Non-observance of the assembly instructions
may result in property damage or cause
personal injury!
Noncompliance with the assembly instructions may
cause damage to your base unit with modules or
destroy it and may also result in personal injury.
·
Observe the assembly instructions of your
base unit.
·
Before assembly of the modules:
-
Disconnect the system from the power
supply! Secure it against being switched
back on! Verify disconnection from power!
Ground and short circuit! Cover or block off
neighboring parts that are under voltage!
·
Ensure sufficient air circulation in your
installation environment and, where applicable,
sufficient cooling.
·
Return defective modules to the manufacturer.
DIN rail
1.
2.
Bus connector
Module 800-CT8-A
UMG 801 (base unit)
Module 800-CT8-A
Bottom latch
Taking into consideration the assembly
instructions for your base unit (check bus
connection assembly, among other things!),
assemble the modules when the system is
disconnected from the power supply as follows:
1. If not already done, insert the bus connector
(JanBus interface) included in the respective
scope of delivery in the socket on the bottom
of your module.
2. Press your module with bus connector onto
the DIN rail until the bottom latches engages.
3. Slide the contacts of your module bus connector
into the sockets of the base unit bus connector
(or in the sockets of the connected module) so
that the bus connectors (devices) are linked.
Then wire your module and apply voltage to the
base unit (system). The base unit recognizes the
module automatically.
The base unit (UMG 801)
· with current measuring module measures current
exclusively via a current transformer. The current
transformers require basic insulation according to
IEC 61010-1:2010 for the rated voltage of the circuit.
· permits assembly of up to 10 modules.
ATTENTION
During the start-up process, the base unit does
not recognize the module!
If there is no communication to the module, the
module functions are not supported (current
measurements).
· Disconnect your system from the power supply
and check the condition of the bus connector
and the connection of the module to the base unit
(JanBus interface). If necessary, slide the contacts
of the module bus connector into the sockets of
the base unit bus connector (or the connected
module) so that the bus connectors (devices) are
linked.
· If necessary, restart the base unit.
· If the specified measures are unsuccessful, please
contact our support team - www.janitza.com
3.
Figure Assembly example:
UMG 801 (base unit) with module 800-CT8-A
Bus connector
contacts
DIN rail
“Current measurement” with terminal assignment connection variant
UMG 801
(Basisgerät)
JanBus-Schnittstelle
S1
S2
S1
S2
S1
S2
9
10
11 12
13 14
I
5
I
6
I
7
S1
S2
15 16
I
8
S1
S2
S1
S2
S1
S2
1
2
3
4
5
6
I
1
I
2
I
3
S1
S2
7
8
I
4
S1
S2
Verbraucher
L1
L2
L3
N
S1
S2
S1
S2
S1
S2
Verbraucher
L1
L2
L3
N
S2
S1
S2
S1
S2
S1
S2
S1
JanBus-Schnittstelle
JanBus-Schnittstelle
Modul 800-CT8-A
Strommessung
Strommessung
4
ATTENTION
Improper handling may cause damage to the
module and result in property damage!
The contacts of the bus connector (JanBus
interface) can bend or break and destroy the bus
connector!
· Never touch or manipulate the contacts of the bus
connector.
· Never use force to press the module with bus
connector contacts into the bus connector
sockets!
· When handling, transporting and storing the
module, protect the contacts of the bus connector.
Bottom latch
Bottom latch
Bus connector
sockets
Fig. “Base unit with module” assembly on DIN rail.
Fig. Module 800-CT8-A connection variant
Bus connector
sockets
JanBus
interface
JanBus inter-
face for additional
modules
End angle
End angle
5
6
Current measurement
The
module 800-CT8-A
· measures current exclusively via a current transformer.
· permits connection of current transformers with
secondary currents of ../1 and ../5 A for current
measurement inputs I1 to I8
· has a current transformer ratio of 5/5 A as the
standard setting (I1 to I8).
· does not measure DC currents.
WARNING
Risk of injury due to high currents and high
electrical voltages!
Serious personal injuries or death can occur due
to:
· Touching live exposed or stripped cores.
· Inputs of the devices, components and modules
that are dangerous to touch.
Therefore, please observe the following for your
system:
·
Before starting work, disconnect it from the
power supply!
·
Secure it against being switched back on!
·
Verify disconnection from power!
·
Ground and short circuit! Use the ground
connection points with the ground symbol for
grounding!
·
Cover or block off neighboring parts that are
under voltage!
WARNING
Electrical currents and voltages!
Open current transformers that are operated on the
secondary side (high voltage spikes) can result in
serious personal injuries or even death.
Avoid the open operation of the current trans-
formers and short-circuit unloaded transform-
ers.
INFORMATION
Recommendation:
The current transformer ratios are configured
self-explanatorily in the “device configuration”
function of the GridVis
®
software.
Dismantling
Bus connector
contacts
Screwdriver for
unlatching
Bus connector
sockets
Bottom latch
Bottom latch
ATTENTION
Handling your module too roughly may cause
damage to the module and result in property
damage!
The bus connector contacts and the bottom latches
can be damaged or broken off during dismantling of
your module.
·
Never wrench the module from the DIN rail
using force.
·
Decouple the bus connector (JanBus interface)
beforehand and carefully unlatch the bottom
latch of the module using a screwdriver!
Dismantling the module:
1. Disconnect the system from the power supply!
Secure it against being switched back on! Verify
disconnection from power! Ground and short
circuit! Cover or block off neighboring parts that
are under voltage!
2. Disconnect the wiring of your module.
3. Decouple the bus connector (JanBus interface)
of your module from the base unit and/or the
connected modules by pulling out your module.
4. Unlatch all bottom latches of your module.
Recommendation:
Use a screwdriver for this
(carefully!).
5. Remove the DIN rail from your module without
touching or damaging the bus connector
contacts.
Bus
connector
sockets
JanBus
interface
DIN rail
JanBus
interface for
additional
modules
ATTENTION
Property damage due to dismantling or decoupling
the module during operation!
Dismantling or decoupling the module while it is
communicating with the base unit can lead to damage
to your devices!
·
Disconnect your system from the power supply
before dismantling or decoupling the module!
Secure it against being turned back on! Verify
disconnection from power! Ground and short
circuit! Cover or block off neighboring parts that
are under voltage!
Technical data
General information
Net weight
(with plug terminals)
Approx. 220 g (0.49 lb)
Device dimensions
approx. w = 73 mm (2.87 in),
h = 90 mm (3.54 in),
d = 76 mm (2.99 in)
Installation position
discretionary
Mounting/assembly -
suitable DIN rails -
35 mm (1.38 in)
· TS 35/7.5 according to EN 60715
· TS 35/10
· TS 35/15 x 1.5
Protection class
IP20
Operating temperature
-10 °C (14 °F) .. +55 °C (131 °F)
Impact resistance
IK07 according to IEC 62262
Current measurement
module 800-CT8-A
Rated current
5 A
Channels
8 (2x4)
· 2 systems (L1, L2, L3, N)
· Individual channels
Metering range
0 .. 6 Arms
Crest factor
2 (based on 6 Arms)
Overload for 1 s
120 A (sinusoidal)
Resolution
0.1 mA (color graphic display 0.01A)
Overvoltage category
300 V CATII
Rated surge voltage
2,5 kV
Power consumption
approx. 0.2 VA (Ri = 5 m
Ω
)
Sampling frequency
8.3 kHz
Frequency of the
power frequency
40 Hz .. 70 Hz
Harmonics
1 .. 9. (only odd)
Transport and storage
The following information applies to devices which are
transported and stored in the original packaging
Free fall
1 m (39.37 in)
Temperature
K55
-25 °C (-13 °F) up to +70 °C (158 °F)
Relative humidity
5 to 95% at 25 °C (77 °F)
without condensation
Ambient conditions during operation, see base unit
Interface and energy supply
JanBus (proprietary)
Via bus connector
Item no. 33.03.378
Fig.: Module 800-CT8-A
INFORMATION
· Detailed technical data for the module
can be found in the user manual.
· Technical data for the base unit and
information on the procedure in the event
of errors can be found in the usage infor-
mation for your base unit.
Terminal connection capacity - Module 800-CT8-A
Connectable conductors.
Only one conductor can be connected per terminal.
Single core, multi-core,
fine-stranded
0.2 - 2.5 mm
2
, AWG 26-12
Cable end sleeve (not insulated)
· recommended stripping length
0.2 - 2.5 mm
2
, AWG 26-12
· 10 mm (0.3937 in)
Cable end sleeve (insulated) *
· recommended stripping
length **
0.2 - 2.5 mm
2
, AWG 26-12
· 12 mm
(≤1,5 mm
2
), 10 mm (>1.5 mm
2
) /
0.47 in (≤1.5 mm
2
), 0.39 in (>1.5 mm
2
)
Cable end sleeve
Length of the contact sleeve ** 8 - 12 mm (0.31 - 0.47 in)
Tightening torque screw
flange
0.2 Nm (1.77 lbf in)
*
... Applies to wire end sleeves with a maximum outer diameter of the
plastic collar up to 4.5 mm (0.18 in).
**
.. Depending on the type of cable end sleeves used (cable end sleeve
manufacturer).
General information
1
2
Janitza electronics GmbH
Vor dem Polstück 6
35633 Lahnau, Germany
Support tel. +49 6441 9642-22
E-mail: [email protected]
www.janitza.com
www
.janitza.com
Doc no. 2.053.007.1.g Status: 11/2022
Current measuring module
for the UMG 801
Installation instructions
Module 800-CT8-A - current measuring module 5 A
Deutsche V
ersion:
siehe V
or
derseite
2
Safety
Safety instructions
The installation instructions do not include a
complete list of all safety measures necessary for
operating the device.
Special operating conditions may require
additional measures. The installation instructions
contain notes that must be observed for your
personal safety and to prevent property damage.
Symbols used on the device:
The additional symbol on the
device itself indicates an electrical
danger that can result in serious
injuries or death.
The general warning symbol calls
attention to possible risks of injury.
Observe all the instructions listed
under this symbol in order to
prevent injuries or even death.
Safety measures
When operating electrical devices, specific parts
of these devices and their components inevitably
carry dangerous voltage. As a result, serious
personal injuries or property damage can occur if
they are not handled correctly:
• Before connection, ground the device and its
components at the ground wire connection, if
available.
• Dangerous voltages may be present in all
circuit parts connected to the voltage supply.
• There may still be dangerous voltages present
in the device or the components even after
disconnection of the supply voltage (capacitor
storage).
• Do not operate equipment with open current
transformer circuits.
• Do not exceed the threshold values specified
in the user manual and on the rating
plate. This must also be observed during
inspections and commissioning.
• Observe the safety instructions and
warning notices in the usage information
that accompanies the devices and their
components!
Qualified personnel
To prevent personal injuries and property damage,
only qualified personnel with electrical engineering
training may work on the base unit and its
components. They must also have knowledge
• of the national accident prevention regulations.
• of safety technology standards.
• in the installation, commissioning and
operation of the device and the components.
Intended use
The modules/components
• are intended for
industrial control usage
only.
• are intended as expansion or transfer modules
for the UMG 801 base unit in switch cabinets
and small distribution boards. (Please observe
the usage information associated with the
base unit).
• may only be mounted to base units that are
disconnected from the power supply (see
“Assembly” step).
• are not intended for installation in vehicles!
Use of the base unit with modules in
stationary equipment is considered an
unusual environmental condition and is only
permissible by special agreement.
• are not intended for installation in areas
exposed to harmful oils, acids, gases, vapors,
dust and radiation, etc.
Disclaimer
Observing the usage information for the devices is
a prerequisite for safe operation and for achieving the
specified performance characteristics and product
features. Janitza electronics GmbH assumes no
liability for personal injuries, property damage and
financial losses resulting from the failure to observe
the usage information. Make sure that your usage
information is legible and accessible.
Further usage information, such as e.g. the
installation instructions or user manual for the
base unit, can be found on our web site
www.janitza.com under Support > Downloads.
Copyright notice
© 2019 - Janitza electronics GmbH - Lahnau.
All rights reserved. Any duplication, processing,
distribution and any other kind of use, even in
part, is prohibited.
Subject to technical changes.
• Make sure that the installation instructions
match your device.
• Make sure you have first read and understood
the usage information accompanying the
product.
• Keep the usage information accompanying
the product accessible through its service life
and hand it over to the subsequent owner
where applicable.
• Please refer to www.janitza.de for information
concerning device revisions and the
associated adjustments to the usage
information accompanying the product.
Disposal
Please observe the national regulations. Dispose
of individual parts, where necessary, depending
on the properties and existing country-specific
regulations, e.g. as:
• Electronic waste
• Batteries and accumulators
• Plastic
• Metals
or commission a certified
disposal company with the scrapping.
Relevant laws,
applied standards and directives
Please refer to the Declaration of Conformity
on our web site (www.janitza.com) for the laws,
standards and directives applied by Janitza
electronics GmbH for the device.
3
7
WARNING
Risk of injury due to electric voltage or electrical
current!
When handling electrical currents or voltages,
serious personal injuries or death can occur due to:
· Touching live exposed or stripped cores.
· Device inputs that are dangerous to touch.
Before starting work on your system:
·
Disconnect it from the power supply!
·
Secure it against being switched back on!
·
Verify disconnection from power!
·
Ground and short circuit!
·
Cover or block off neighboring parts that are
under voltage!
Incoming goods inspection
The prerequisites for trouble-free and safe
operation of the devices and their components
include proper transport, storage, setup and
assembly, as well as careful operation and
maintenance.
Exercise caution when unpacking and packing
the device, without using force and only using
suitable tools.
Check:
• Devices and components by performing
a visual inspection to ensure a flawless
mechanical condition.
• The scope of delivery (see user manual) for
completeness before beginning the installation
of your devices and components.
If you assume that safe operation is no longer
possible, shut down your device with the
components immediately and secure it from being
unintentionally started back up again.
It can be assumed that safe operation is
impossible if, for example, the device with
components:
• Has visible damage.
• No longer functions despite an intact power
supply.
• Was subjected to extended periods of
unfavorable conditions (e.g. storage outside
of the permissible climate thresholds without
adjustment to the room climate, condensation,
etc.) or transport stress (e.g. falling from an
elevated position, even without visible external
damage, etc.).
User manual:
WARNING
Danger due to noncompliance with warning
and safety instructions.
Noncompliance with warning and safety
instructions on the device itself and in the
information on using the device and its
components can lead to injury or even death.
Observe safety instructions and warning notices
on the device itself and in the usage information
associated with the devices and their components,
such as:
· Installation instructions.
· User manual.
· Safety instructions supplement.
The current measuring module
· enhances the scope of functions of the base
unit with additional current measuring channels
(2 blocks á 4 current measuring channels).
· is suitable for current transformers with trans-
former ratios of ../1 A or ../5 A.
Device short description and assembly - current measuring module
Safety instructions in the installation instructions
are highlighted with a warning triangle and are
presented as follows depending on the level of risk:
ATTENTION
Warns of an imminently dangerous situation that
can result in property damage or environmental
damage in the event of noncompliance.
DANGER
Warns of an imminent danger that will result
in serious or fatal injuries in the event of
noncompliance.
CAUTION
Warns of an imminently dangerous situation that
can result in minor or moderate injuries in the event
of noncompliance.
INFORMATION
Points out procedures in which there are
no
dangers
of personal injuries or property damage.
WARNING
Warns of a potentially dangerous situation that can
result in serious injuries or death in the event of
noncompliance.
INFORMATION
· The scope of delivery of the module includes
the appropriate bus connector (JanBus
interface) for connection to the base unit or
additional modules!
· In addition to the current measuring module,
also observe the usage information for your
base unit!
CAUTION
Non-observance of the assembly instructions
may result in property damage or cause
personal injury!
Noncompliance with the assembly instructions may
cause damage to your base unit with modules or
destroy it and may also result in personal injury.
·
Observe the assembly instructions of your
base unit.
·
Before assembly of the modules:
-
Disconnect the system from the power
supply! Secure it against being switched
back on! Verify disconnection from power!
Ground and short circuit! Cover or block off
neighboring parts that are under voltage!
·
Ensure sufficient air circulation in your
installation environment and, where applicable,
sufficient cooling.
·
Return defective modules to the manufacturer.
DIN rail
1.
2.
Bus connector
Module 800-CT8-A
UMG 801 (base unit)
Module 800-CT8-A
Bottom latch
Taking into consideration the assembly
instructions for your base unit (check bus
connection assembly, among other things!),
assemble the modules when the system is
disconnected from the power supply as follows:
1. If not already done, insert the bus connector
(JanBus interface) included in the respective
scope of delivery in the socket on the bottom
of your module.
2. Press your module with bus connector onto
the DIN rail until the bottom latches engages.
3. Slide the contacts of your module bus connector
into the sockets of the base unit bus connector
(or in the sockets of the connected module) so
that the bus connectors (devices) are linked.
Then wire your module and apply voltage to the
base unit (system). The base unit recognizes the
module automatically.
The base unit (UMG 801)
· with current measuring module measures current
exclusively via a current transformer. The current
transformers require basic insulation according to
IEC 61010-1:2010 for the rated voltage of the circuit.
· permits assembly of up to 10 modules.
ATTENTION
During the start-up process, the base unit does
not recognize the module!
If there is no communication to the module, the
module functions are not supported (current
measurements).
· Disconnect your system from the power supply
and check the condition of the bus connector
and the connection of the module to the base unit
(JanBus interface). If necessary, slide the contacts
of the module bus connector into the sockets of
the base unit bus connector (or the connected
module) so that the bus connectors (devices) are
linked.
· If necessary, restart the base unit.
· If the specified measures are unsuccessful, please
contact our support team - www.janitza.com
3.
Figure Assembly example:
UMG 801 (base unit) with module 800-CT8-A
Bus connector
contacts
DIN rail
“Current measurement” with terminal assignment connection variant
UMG 801
(Basisgerät)
JanBus-Schnittstelle
S1
S2
S1
S2
S1
S2
9
10
11 12
13 14
I
5
I
6
I
7
S1
S2
15 16
I
8
S1
S2
S1
S2
S1
S2
1
2
3
4
5
6
I
1
I
2
I
3
S1
S2
7
8
I
4
S1
S2
Verbraucher
L1
L2
L3
N
S1
S2
S1
S2
S1
S2
Verbraucher
L1
L2
L3
N
S2
S1
S2
S1
S2
S1
S2
S1
JanBus-Schnittstelle
JanBus-Schnittstelle
Modul 800-CT8-A
Strommessung
Strommessung
4
ATTENTION
Improper handling may cause damage to the
module and result in property damage!
The contacts of the bus connector (JanBus
interface) can bend or break and destroy the bus
connector!
· Never touch or manipulate the contacts of the bus
connector.
· Never use force to press the module with bus
connector contacts into the bus connector
sockets!
· When handling, transporting and storing the
module, protect the contacts of the bus connector.
Bottom latch
Bottom latch
Bus connector
sockets
Fig. “Base unit with module” assembly on DIN rail.
Fig. Module 800-CT8-A connection variant
Bus connector
sockets
JanBus
interface
JanBus inter-
face for additional
modules
End angle
End angle
5
6
Current measurement
The
module 800-CT8-A
· measures current exclusively via a current transformer.
· permits connection of current transformers with
secondary currents of ../1 and ../5 A for current
measurement inputs I1 to I8
· has a current transformer ratio of 5/5 A as the
standard setting (I1 to I8).
· does not measure DC currents.
WARNING
Risk of injury due to high currents and high
electrical voltages!
Serious personal injuries or death can occur due
to:
· Touching live exposed or stripped cores.
· Inputs of the devices, components and modules
that are dangerous to touch.
Therefore, please observe the following for your
system:
·
Before starting work, disconnect it from the
power supply!
·
Secure it against being switched back on!
·
Verify disconnection from power!
·
Ground and short circuit! Use the ground
connection points with the ground symbol for
grounding!
·
Cover or block off neighboring parts that are
under voltage!
WARNING
Electrical currents and voltages!
Open current transformers that are operated on the
secondary side (high voltage spikes) can result in
serious personal injuries or even death.
Avoid the open operation of the current trans-
formers and short-circuit unloaded transform-
ers.
INFORMATION
Recommendation:
The current transformer ratios are configured
self-explanatorily in the “device configuration”
function of the GridVis
®
software.
Dismantling
Bus connector
contacts
Screwdriver for
unlatching
Bus connector
sockets
Bottom latch
Bottom latch
ATTENTION
Handling your module too roughly may cause
damage to the module and result in property
damage!
The bus connector contacts and the bottom latches
can be damaged or broken off during dismantling of
your module.
·
Never wrench the module from the DIN rail
using force.
·
Decouple the bus connector (JanBus interface)
beforehand and carefully unlatch the bottom
latch of the module using a screwdriver!
Dismantling the module:
1. Disconnect the system from the power supply!
Secure it against being switched back on! Verify
disconnection from power! Ground and short
circuit! Cover or block off neighboring parts that
are under voltage!
2. Disconnect the wiring of your module.
3. Decouple the bus connector (JanBus interface)
of your module from the base unit and/or the
connected modules by pulling out your module.
4. Unlatch all bottom latches of your module.
Recommendation:
Use a screwdriver for this
(carefully!).
5. Remove the DIN rail from your module without
touching or damaging the bus connector
contacts.
Bus
connector
sockets
JanBus
interface
DIN rail
JanBus
interface for
additional
modules
ATTENTION
Property damage due to dismantling or decoupling
the module during operation!
Dismantling or decoupling the module while it is
communicating with the base unit can lead to damage
to your devices!
·
Disconnect your system from the power supply
before dismantling or decoupling the module!
Secure it against being turned back on! Verify
disconnection from power! Ground and short
circuit! Cover or block off neighboring parts that
are under voltage!
Technical data
General information
Net weight
(with plug terminals)
Approx. 220 g (0.49 lb)
Device dimensions
approx. w = 73 mm (2.87 in),
h = 90 mm (3.54 in),
d = 76 mm (2.99 in)
Installation position
discretionary
Mounting/assembly -
suitable DIN rails -
35 mm (1.38 in)
· TS 35/7.5 according to EN 60715
· TS 35/10
· TS 35/15 x 1.5
Protection class
IP20
Operating temperature
-10 °C (14 °F) .. +55 °C (131 °F)
Impact resistance
IK07 according to IEC 62262
Current measurement
module 800-CT8-A
Rated current
5 A
Channels
8 (2x4)
· 2 systems (L1, L2, L3, N)
· Individual channels
Metering range
0 .. 6 Arms
Crest factor
2 (based on 6 Arms)
Overload for 1 s
120 A (sinusoidal)
Resolution
0.1 mA (color graphic display 0.01A)
Overvoltage category
300 V CATII
Rated surge voltage
2,5 kV
Power consumption
approx. 0.2 VA (Ri = 5 m
Ω
)
Sampling frequency
8.3 kHz
Frequency of the
power frequency
40 Hz .. 70 Hz
Harmonics
1 .. 9. (only odd)
Transport and storage
The following information applies to devices which are
transported and stored in the original packaging
Free fall
1 m (39.37 in)
Temperature
K55
-25 °C (-13 °F) up to +70 °C (158 °F)
Relative humidity
5 to 95% at 25 °C (77 °F)
without condensation
Ambient conditions during operation, see base unit
Interface and energy supply
JanBus (proprietary)
Via bus connector
Item no. 33.03.378
Fig.: Module 800-CT8-A
INFORMATION
· Detailed technical data for the module
can be found in the user manual.
· Technical data for the base unit and
information on the procedure in the event
of errors can be found in the usage infor-
mation for your base unit.
Terminal connection capacity - Module 800-CT8-A
Connectable conductors.
Only one conductor can be connected per terminal.
Single core, multi-core,
fine-stranded
0.2 - 2.5 mm
2
, AWG 26-12
Cable end sleeve (not insulated)
· recommended stripping length
0.2 - 2.5 mm
2
, AWG 26-12
· 10 mm (0.3937 in)
Cable end sleeve (insulated) *
· recommended stripping
length **
0.2 - 2.5 mm
2
, AWG 26-12
· 12 mm
(≤1,5 mm
2
), 10 mm (>1.5 mm
2
) /
0.47 in (≤1.5 mm
2
), 0.39 in (>1.5 mm
2
)
Cable end sleeve
Length of the contact sleeve ** 8 - 12 mm (0.31 - 0.47 in)
Tightening torque screw
flange
0.2 Nm (1.77 lbf in)
*
... Applies to wire end sleeves with a maximum outer diameter of the
plastic collar up to 4.5 mm (0.18 in).
**
.. Depending on the type of cable end sleeves used (cable end sleeve
manufacturer).