9    chimney

To assure proper operation of the Combiflame, the chimney and the flue gas connection have to fit 

to the requirements of the boiler. If you like to connect the boiler to an existing chimney, ask your 

chimney cleaner for permission. The flue gas system has to be conform to  EN 18160 and your local 

terms.

At all modes of operation the natural draft of the chimney measured at the flue gas connector of 

the boiler has to be above 10 Pa. A draft regulator is required. The regulator has to be adjusted to 

15 Pa. Natural draft above 18 Pa has to prevented. No part of the flue gas system is allowed to be 

more tighten than the flue gas connector of the boiler. Janfire advises a cross-section for the flue 

gas system from 180 mm. The flue gas system should be as tight, as short and should have as few 

angles as possible. 

If you like to run the Combiflame as an additional boiler to an existing heating system, a separate 

flue gas system for each boiler is required. Ask you local authorities for permission if you like to 

connect the Combiflame and a second boiler to the same chimney. 

Any data which are necessary for the design of the flue gas system can be 

fount in chapter 4. No part of the flue gas system is allowed to be more tighten 

than the flue gas connector of the boiler.

!

A draft regulator is required. This regulator is not part of the purchased parts 

package.

9.1   

Adjustment of draft

Before setting the Combiflame into operation check the draft. The draft has to be measured in the 

flue gas pipe about 0.5 m behind the boiler. 

If the boiler and the chimney are cold, 10 Pa to 15 Pa natural draft are required. Start the burner 

and let it run on the boilers maximum power level for at least 15 min. Now check the draft again. In 

this mode of operation not more than 18 Pa natural draft are allowed. If the draft is higher than 18Pa 

adjust the required draft regulator.  

10  Connection of thermal safety relief valve / thermal safety 

relief switch 

The  Combiflame  is  equipped  with  a  weld  thermal  relief  heat  exchanger.  This  heat  exchanger 

prevents the Combiflame from overheating for example during an electric power failure. It has to 

be connected to the domestic cold water supply by a thermal safety relief valve. The thermal safety 

relief valve has to open at 95°C. The assembly of the thermal safety relief valve has to be conform 

to EN 303-5 clause 4.1.5.11.3. The valve must be placed in the cold water supply. It is not allowed 

to have any other valve in front of or behind the safety relief valve.  

The following must be considered: 

Summary of Contents for Combiflame

Page 1: ...Janfire pelletsw rme swedish quality Janfire Combiflame Boiler for wood pellets log and brown coal manual...

Page 2: ...lever on the right side of the boiler After the opening of the flap you have to wait a couple of seconds before you may open the front door 2 Warranty terms The warranty will only be issued on faults...

Page 3: ...n or dirt in the hydraulic system Advanced claims are excluded especially any claim for damages if they are not founded by law If a warranty claim was not justified we will bring our costs to account...

Page 4: ...d this manual Purchased parts package Boiler Combiflame including the catalytic converter four adjustable feet ash pit grill for operation with log pellet burner NH thermal controller for the draft fl...

Page 5: ...23 24 25 26 27 28 connector female screw thread for thermal relief valve flue gas connector muffle 1 for backflow pellet burner thermostat safety relief switch main switch therm relif heat exchanger...

Page 6: ...rn temperature C 55 flue gas average temperature mass flow cross section of flue gas connector average CO2 level in flue gas at nominal heat output average CO level 13 O2 at nominal heat output C g s...

Page 7: ...ief heat exchanger The Combiflame has a welded thermal safety relief heat exchanger The thermal safety relief heat exchanger may not be used as a domestic hot water supply This heat exchanger has to b...

Page 8: ...the maximal operation time adjustable in burner menu a fault message will appear in the display of the burner This case normally happens at the first start running or if you run out of pellets The in...

Page 9: ...ong to the state of the art and work Ask local authorities before installation The heating room has to be conform to the local fire protection requirements If a ventilating system is installed make su...

Page 10: ...r falls below the triggered temperature the burner will start again This kind of regulation is very inefficient and uncomfortable 8 2 2 Modulating operation The burner can be equipped with a modulatio...

Page 11: ...em can be fount in chapter 4 No part of the flue gas system is allowed to be more tighten than the flue gas connector of the boiler A draft regulator is required This regulator is not part of the purc...

Page 12: ...ic cold water supply But it is allowed to operate the boiler with pellets in this case The Combiflame is equipped with a built in thermal safety relief switch conform with EN 303 5 clause 3 21 In case...

Page 13: ...ust them again if necessary 5 Connect the plugs of the burner according to the electric plan The electric connection has to be made according to the local terms by an expert The hose between the auger...

Page 14: ...he connection between burner and auger system and the modulation sensor Open the screw hooks and remove the burner 6 Make sure that the burner and the hose will be stored properly The draft flap has t...

Page 15: ...Start and adjust the burner as said in the manual Make sure that the ash pit is empty and the main heat exchanger and the catalytic converter are clean Do not open any door of the boiler during operat...

Page 16: ...m thick bed of glow Than put the briquette on top of the glow There should be a distance from about 5 cm between the briquettes 3 The front grill has to be covered by the delivered cover sheet start u...

Page 17: ...the front door until you have opened the start up flap by pulling the lever on the right side of the boiler After the opening of the flap you have to wait a couple of seconds before you may open the f...

Page 18: ...an the main heat exchanger an the flue gas system every month cleaning of the grill Never use a vacuum cleaner to clean the grill There is a high risk of fire because of remaining glow Open the bottom...

Page 19: ...mney too 17 Advice to averting of a danger To reduce risk you have to follow all instructions of this manual everytime you use this boiler autumn and spring The natural draft of the chimney depends on...

Page 20: ...door of the boiler has to be kept close Wear fire proved glows any time you open a door during heating Do not open the front door until you have opened the start up flap by pulling the lever on the ri...

Page 21: ...Janfire pelletsw rme swedish quality...

Reviews: