Page 14
ENGLISH
Jandy
®
Pro Series TruClear
™
Chlorine Generating System
|
Installation & Operation Manual
Figure 4.
Wiring Diagram
Use Copper Conductors Only – Rated for 90°C Minimum
Pool Pump
TO EARTH
BONDING POINT
POOL PUMP CONTROL
240 VAC
CIRCUIT BREAKER
PANEL
TO CELL
GROUND
LINE 1
LINE 2
BLK
GRN
LOAD 2
LOAD 1
GROUND (CHASSIS)
RED
TO EARTH
BONDING POINT
ENGLISH
POWER PACK
1.
Wire power pack to pool pump power source using
3.3 mm
2
(12 AWG) insulated wire and conduit. Wire
the power pack to the LOAD side of the fi lter pump
or the LOAD side of the pool pump timer relay so
that the chlorinator can only come on when the pool
pump comes on (see Figure 4).
2.
Remove the electrical mounting plate that feeds the
power cable to the power pack.
3.
Feed the power cable through the mounting plate.
4.
Connect the conduit to the mounting plate.
5.
Make the wire connections. Note: The green wire
should be connected to the ground point.
WARNING
Select field conductor size appropriately, taking into
consideration length of circuit and in accordance with
applicable installation codes. The ground conductor
must be minimum 12 AWG.
6.
Place all of the wire connections and cables inside
the power pack and secure the electrical mounting
plate tightly.
7.
Plug the cell into the Power Pack.
3.6 Bonding
The National Electric Code
®
(NEC
®
in the United States)
or the Canadian Electric Code (CEC in Canada) requires
pool equipment to be bonded to each other. Check your
local codes to determine if the NEC or CEC and/or other
local installation codes are enforced by the Authority
Having Jurisdiction (AHJ in the United States) or the
local competent authorities in Canada. A solid, copper
8.37 mm
2
(8 AWG) wire is recommended, per the NEC
and CEC, for bonding the power pack to a permanent
bonding connection that is acceptable to the local AHJ or
the local competent authorities in Canada.. Refer to your
locally enforced codes for the acceptable bonding wire
gauge. Attach the bonding point located on the bottom