Page 27
Symptom
Problem
Possible Solution
One button on the Four
Function Remote does not
operate.
Check programming first. If
the Four Function Remote
is programmed correctly, the
button may be shorted.
NOTE
If dip switch 1
(CLEANER) is on, button #
on the Four Function Remote
will not operate when in spa
mode
unless
this button is
programmed to a circuit other
than Aux 1.
Replace the Four Function Remote. Use MENU,
REVIEW, SPA SWITCH to check programming.
Pool cleaner booster pump
turns on without the filter pump
being on, and can run with the
spa on.
System is not recognizing DIP
switch #1 is on.
NOTE
Before turning on any
DIP switches, first turn off all
equipment. Do not program
any auxiliaries until all DIP
switches are set.
Turn off all equipment buttons, then turn off
power to the system, finally turn off, then on, DIP
switch #1. Turn on power and test system.
System comes on at times that
are not programmed.
Phantom programs.
At the PDA press MENU, then scroll to REVIEW.
Make note of all programs (the Four Function
Remote setting, labels, and temperature
settings) then turn off all DIP switches and go to
the PDA. CLEAR MEMORY, reprogram and try
system again.
Heater will not fire. Heater LED
will not light in "Service Mode".
Water temperature sensor not
installed or defective.
Check water temperature sensor.
LCD screen display stays on
startup screen.
No communication between
PDA Handheld Remote and
Power Center J-box.
Change the Frequency Channel. See Section