Issue: 01.07.2020
Page 15
Installation
Drainage
The drain fitting is aluminum alloy with a 3/4” BSP male thread. A locknut and an aluminium
washer are supplied to secure to the
drain pan. The locknut only requires hand tightening and then pinching up with a spanner. Do not over tighten or the threads may
strip from the nut and also damage the tray. To fit the drain fitting, remove the drip tray (unscrew the seven screws that secure
it), locate the fitting then refit the tray. The correct way to fit the drain fitting to the drain pan with aluminium washer and
locknut can be seen in the diagram below.
A minimum suggested size of drain from the
indoor unit is 20mm or 3/4”. This can be either copper or plastic. Flexible hose is not
recommended as it can easily kink causing a blockage and water to back up in the unit.
Important Note:
The evaporator drain pan fitting is supplied loose and must be fitted on site. It is attached to the
indoor unit fan guard with a cable tie. Correct fitting is vital to ensure leak
–
free operation. The lock
nut on the drain fitting
must
be fitted the right way around; otherwise it will not tighten against the
drip tray. One side of the nut has an angled recess
–
this must be facing towards the drip tray. The
fitting does not require any sealant but a small amount of silicon sealant can be applied between the
flared face of the fitting and the drip tray if so desired.
1 DRAIN FITTING
2 DRAIN PAN
3 ALUMINIUM WASHER
4 LOCKNUT
1
2
3
4
Summary of Contents for BSCU-30-M1
Page 1: ...CELLAR PLUS CELLAR COOLER RANGE ISSUE 01 07 2020 CELLAR COOLER RANGE TECHNICAL MANUAL ...
Page 8: ...Issue 01 07 2020 Page 8 Installation Quick Guide Piping Single System Twin System ...
Page 24: ...Issue 01 07 2020 Page 24 Drawings Dimensional drawings Indoor Unit 80E ...
Page 26: ...Issue 01 07 2020 Page 26 Drawings Dimensional drawings Outdoor Units BSCU 40 M1 M3 ...
Page 33: ...Issue 01 07 2020 Page 33 Certification ...
Page 34: ...Issue 01 07 2020 Page 34 THIS PAGE IS LEFT BLANK INTENTIONALLY ...