Chapter 3 Installation instructions
3.1 Installation Notice
1) The installation of JP9960 series products must be performed in compliance with the
electrical code by professional personnel.
2) Install the UPS in a clean and stable environment that is free of vibration, dust, high
humidity, flammable gas, and flammable liquid or caustic substance.
3) To ensure normal UPS performance, ambient temperature should range between 0-
40.If temperature exceeds 40
℃
,
maximum load should be decreased progressively
by 12% of the rated amount along with every increase of temperature by 5
℃
. The
maximum ambient temperature for normal UPS performance should not exceed 50
℃
.
4) It is suggested that battery pack should work within a temperature range from15
℃
to 25
℃
.
5) Altitude for normal UPS function should not exceed 1000m. Should UPS be intended
for application above 1000m, progressive decrease of rated output should be
applied as Listed in the following chart:
Altitude(m)
1000
1500
2000
2500
3000
3500
4000
4500
5000
Derating
coefficient
100%
95%
91%
86%
82%
78%
74%
70%
67%
3.2 Installation space
JP9960 20K/30K/40K series utilizes forced fan cooling and installation spot should
make allowance for ventilation. Meanwhile, inside maintenance should be carried out
from the front side and therefore maintenance space should also be considered in
advance.
Refer to the following figure for installation space: