Single UPS installation
Installation method: refer to Fig1.
Use screw driver to tear down four screws.
Opening front panel, namely seeing downside distribution box of power switch.
Refer to Fig12
、
13.
Fig12
SWITCH:BYPASS mode and AUTO mode transfer.
SW1:city input switch SW2:bypass switch SW3:battery input switch
Fig13
First into the distribution inlet and outlet hole of the output/input and batteries
group power wire, after that assembly connection.
Caution: Don’t connection to 380V, test take place fault, for the single phase input
UPS belong to 2X0V system, when movering or again connection, be sure to
again carry on according to more than step.
(
3
)
Connection wire option
Compare with rated value of input current and cross section of input power wire.
Cable 1
TYPE
Three-phase input
current(max)
Three-phase input cable
Sez.(mm
2
)
Wire Sep.
10KVA 63A
16
mm
2
OT16-6
15KVA 95A
20
mm
2
OT16-8
20KVA 128A
25mm
2
OT25-10
Compare with rated value of output current and cross section of output power wire.
Cable 2
TYPE
Output current(max)
Output cable Sez.(mm
2
) Wire
Sep.
10KVA 45A
10
mm
2
OT10-6
15KVA 75A
16
mm
2
OT16-8
20KVA 90A
20mm
2
OT20-10