JAGA NV | BRIZA RAD 055/041 | MANUAL | 5 JULI 2021, 14:29 | V.01
C. AUTO-CHANGE-OVER
4⁰C
2⁰C
2⁰C
4⁰C
Only in combination with a suitable heat
pump and thermostat head for heating
and cooling
Configuration code : DPC.BRC3 / DPC.BRC4 / DPC.BRC6
Only DPC.BRC4 /
DPC.BRC6
The device automatically enters the cooling mode as soon as the water temperature is 4°C lower
than the room temperature. If the water temperature is less than 2°C lower than the room tempera-
ture, the device will automatically switch to standby.
The device automatically enters the heating mode as soon as the water temperature is 4°C
higher than the room temperature. If the water temperature is less than 1°C higher than the room
temperature, the device will automatically switch to standby.
24 V +
GND
1
2P
MODE
[C]
C.1. FACTORY SETTINGS
C.1.1. Without control panel
- DPC.BRC3
The unit automatically enters the desired operating mode ( or standby) based on the water and room
temperature. (
,
of standby).
Auto-change-over. The unit starts as soon as the water temperature > 28 ̊C.
Auto-change-over. The unit starts as soon as the water temperature < 18 ̊C.
The unit is in standby.
1 Speed . The unit runs at the set speed.