Briza 12 - STAND ALONE / BUILT-IN - MANUAL - 9 juni 2020, 15:12

ROUTINE MAINTENANCE

Every 6 months: Check the condition of the coil and condensate drain:

If necessary:
– 

  remove any dirt from the coil surface
– 

  remove dust using an air compressor
– 

  wash with water and brush gently
– 

  dry by using compressed air
– 

  keep the condensate drain free from any obstructions that may prevent normal water flow

Bleed air from the system.

1.  start the circulation pump and open the supply valve for a few minutes.
2.  stop the circulation pump.
3.  loosen the vent screw on the inlet collector and bleed the air.
4.  repeat steps 1 to 3 until there is no more air escaping the system

ELECTRICAL CIRCUIT

The following steps are recommended to perform maintenance on the electrical circuit:

– 

  check the unit’s power consumption using a clip-on meter and compare the reading with the values 

shown in the documentation;

– 

  inspect the electrical contacts for corrosion and loose wires.
 

11.2.  

11.3.  

Summary of Contents for BRIZA 12

Page 1: ...BRIZA 12 STAND ALONE BUILT IN INSTALLATION INSTRUCTIONS BRIZA12 WALL AND CEILING...

Page 2: ...22 DECLARATION OF CONFORMITY JAGA N V Verbindingslaan 16 B 3590 declares under its sole responsibility that the product to which this declaration relates is in conformity with the following standards...

Page 3: ...duct before during or after product installation maintenance has been carried out by unauthorized people maintenance has been carried out by someone other thanJaga access to the unit has been restrict...

Page 4: ...lations Do not leave the packaging within reach of children INSTALLATION installation must be carried out by certified technicians Incorrect installation could cause product failure a reduced performa...

Page 5: ...ned to function as a fan coil for both heating and cooling applications any other use is strictly forbidden Installing the unit in an explosive environment is prohibited Decommissioning When the unit...

Page 6: ...eiling built in Electrical connection Secondary drain pan Option for ceiling built in Condensate drain pan standard for wall model Tangential fan The direction of the air flow is determined by the pos...

Page 7: ...7 1 DIMENSIONS WALL MOUNTED MODEL 7 1 1 Installation in a wall recess Briza 038 Briza 052 7 1 2 Wall mounting Briza 041 Briza 055 L CM BRIZA 038 BRIZA 052 19 27 39 47 BRIZA 041 BRIZA 055 29 37 49 57...

Page 8: ...a 052 7 3 BUILT IN MODEL WITH AIR OUTLET CORNER PIECE 1 3 C H B 1 2 min 5 min 5 min 5 min 5 min 5 min 5 B H max 99 max 99 9 9 7 4 7 4 min 3 H B 9 max 99 1 2 5 min 3 C H B 9 max 99 1 2 5 7 4 7 4 max 99...

Page 9: ...Y BULB TEMPERATURE F 69 8 F 73 4 F 77 0 F 80 6 F 84 2 F 87 8 F RH 40 37 4 F 37 4 F 37 4 F 37 4 F 37 4 F 39 2 F 50 37 4 F 37 4 F 37 4 F 37 4 F 39 2 F 42 8 F 60 37 4 F 37 4 F 39 2 F 39 2 F 42 8 F 46 4 F...

Page 10: ...on and a water drain near the lower connec tion it is recommended to bleed air from the coil before operation The type of wall determines what type of screw or plug should be used For installation on...

Page 11: ...on OPTION secondary drain pan for Briza Built In Ceiling BRIZA H38 ref 5127 00010001 BRIZA H52 ref 5127 00010002 Ceiling 15 2 8 5 29 32 1 7 64 2 128 95 3 5 29 5 21 5 25 32 5 3 64 3 47 64 1 3 16 1 31 3...

Page 12: ...st be installed make sure that the power supply covers the total load of all units connected plus a margin of 10 to cover the start up power if the unit is mounted on a metal surface the ground connec...

Page 13: ...nstall the grill The direction of the airflow is determined by the orientation of the grille Only for Briza Ceiling with enclosure fasten the grill by the security clips Units with enclosure Position...

Page 14: ...ER maintenance must be carried out by qualified technicians do not insert sharp objects into the supply and return grilles the unit has sharp edges use gloves during maintenance DANGER Always use the...

Page 15: ...water flow Bleed air from the system 1 start the circulation pump and open the supply valve for a few minutes 2 stop the circulation pump 3 loosen the vent screw on the inlet collector and bleed the a...

Page 16: ...r complaints please contact your supplier or installer The copyright of these instructions is the property of Jaga DISSASSEMBLY INSTRUCTIONS SAFEGUARD THE ENVIROMENT Jaga cares about protecting the en...

Reviews: