44
JAGA NV | BRIZA 12 - JFCC | MANUEL | 2023.03.06 | V.5.2
B. 0 - 10V BMS WITH WATER- AND ROOM TEMPERATURE MONITORING
(AUTO-CHANGE-OVER)
Configuration code : FCC.BRC42 / FCC.BRC62 / FCC.BRC64
4⁰C
1⁰C
1⁰C
2⁰C
Standby mode
Only in combination with a suitable heat
pump and control valve for heating and
cooling
The device automatically enters cooling mode when the water temperature is 2
°
C/4°F below the room temperature. If
the differential between room and water temperature is less than 1
°
C/2°F, the device will automatically switch to standby.
The unit is in standby. The unit automatically starts a new cycle if the preset temperature is reached.
The device automatically enters heating mode when the water temperature is 4
°
C/7°F above the room temperature.
If the differential between room and water temperature is less than 1
°
C/2°F higher than the room temperature, the
device will automatically switch to standby.
strain relief
strain relief
POWER 45W
INPUT: 110-240VAC
OUTPUT: 24V
N L
15120045
GND
GND
GND
GND
NTC1
V.H.
V.C.
0-10V
0-10V
0-10V +24V
GND 0-10V 24V
GND
24V
GND
24V
+24V RC
IN/OUT
GND
Tsens 1
CONTROL PANEL
I2C
RS485 A/B
CO2
PC / RF
THERMOSTATE 1
DIPSWITCH
Tsens 2
Tsens 3
Tsens 4
JAGA
1
2
3
4
5
6
7
8
ON
(230V - 50Hz)
[C]
[B]
[D]
MODE
[F]
[I]
[A]
[G]
[H]
4-pipe
4-pipe
POWER 45W
INPUT: 110-240VAC
OUTPUT: 24V
N L
15120045
GND
GND
GND
GND
NTC1
V.H.
V.C.
0-10V
0-10V
0-10V +24V
GND 0-10V 24V
GND
24V
GND
24V
+24V RC
IN/OUT
GND
Tsens 1
CONTROL PANEL
I2C
RS485 A/B
CO2
PC / RF
THERMOSTATE 1
DIPSWITCH
Tsens 2
Tsens 3
Tsens 4
JAGA
1
2
3
4
5
6
7
8
ON
(230V - 50Hz)
[C]
[D]
MODE
[F]
[I]
[A]
[H]
2-pipe