OPERATION AND MAINTENANCE MANUAL 

12-2015

 

 

 
 

2.6 MANUFACTURE AND ACCEPTANCE 

 

The  standpoint  hydrants  are  accepted  and  produced  in  accordance  with:  PN-EN  1074-6:2005  (Valves  for 

water  supply.  Fitness  for  purpose  requirements  and  appropriate  verification  tests)  and  PN-EN  12266-1:2012 
(Industrial  valves.  Testing  of  metallic  valves).  All  hydrants  (100%)  are  subject  to  tightness  testing.  The  tests 
include external body tightness and closing tightness. 
 
 

2.7 MARKINGS 

 
The standpoint hydrants are marked in accordance with:   PN-EN-19: 2005, PN-EN-1074-6: 2009 

markings on the front and back walls of the body chamber. The marking contains the following data: 

- nominal diameter  

 

 

 

 

 

 

 

 

- nominal pressure  

 

 

 

 

 

 

 

 

- type of body material 
- manufacturer trade mark  
- direction of medium flow. 

The location on the valve specified in the documentation features the nameplate which contains the 

following data:   

 - manufacturer's company name and logo 

 

 

 

- product serial number 
- sealing temperature grade 
- the Polish Building Mark "B" and/or the CE mark (as applicable) 
- product type 

 

 

3 PROTECTION, STORAGE & TRANSPORT 

 
 

3.1 PROTECTIVE COATINGS 

 

All inner and outer cast-iron surfaces and column pipes are protected with electro-deposited epoxy coat. The 

coat has been approved for contact with foodstuffs. 
The anti-corrosion coating layer minimum thickness is 250

µ

m, with UV protection. 

The casting surface is pre-treated for epoxy coating in accordance with the relevant technical documentation and 
standard PN-EN ISO 12944-5: 2009. 
The fastening bolts for external hydrant's part, if other than stainless steel grade 1.4301, should 
have corrosion protection in the form of coat, e.g. Fe/Zn5. 
 
 

3.2 PACKAGING 

 

The standpoint hydrants are placed in plastic film sleeves and additionally wrapped with stretch wrap when 

placed on pallets. 

 

 
 

3.3 STORAGE 

 
 

Hydrants should be stored in covered areas. 

  

Summary of Contents for 8010

Page 1: ...President of Factory JAFAR S A Failure to comply with the guidelines and instructions in this Operation and Maintenance Manual releases the manufacturer from all obligations liability and guarantee Du...

Page 2: ...RIPTION 3 2 2 MATERIALS 4 2 3 DIMENSIONS 5 2 4 STANDARDS 7 2 5 ORDERING REGULATIONS 7 2 6 MANUFACTURE AND ACCEPTANCE 8 2 7 MARKINGS 8 3 PROTECTION STORAGE TRANSPORT 8 3 1 PROTECTIVE COATINGS 8 3 2 PAC...

Page 3: ...hydrant s foot is placed on the ground above water supply network s pipe The valve chamber contains a closing component a poppet valve connected to the outlet in the upper part of the hydrant using a...

Page 4: ...Material Reference standard 1 Body Cast iron EN GJS 400 15 PN EN1563 2012 2 Bonnet Cast iron EN GJS 400 15 PN EN1563 2012 3 Dome Cast iron EN GJS 400 15 PN EN1563 2012 4 Decorative ring Cast iron EN G...

Page 5: ...OPERATION AND MAINTENANCE MANUAL 12 2015 5 2 3 DIMENSIONS TYPE 8001 DN mm 3 4 1000 1250 1500 RD 1800 2000 2250 2500 L 2800 Detail A Detail B...

Page 6: ...OPERATION AND MAINTENANCE MANUAL 12 2015 6 TYPE 8010 DN RD H H1 H2 Weight inch kg 1000 1930 35 1250 2180 39 1600 2430 43 1800 2730 47 3 4 885 600 mm Detail A Detail B...

Page 7: ...2001 ISO general purpose metric screw threads Tolerances Principles and basic data PN ISO 2903 1996 Trapezoid ISO metric threads Tolerances PN EN ISO 4762 2006 Hexagon socket headcap screws PN EN ISO...

Page 8: ...ures the nameplate which contains the following data manufacturer s company name and logo product serial number sealing temperature grade the Polish Building Mark B and or the CE mark as applicable pr...

Page 9: ...OPERATION AND MAINTENANCE MANUAL 12 2015 9 3 4 TRANSPORT Transport the hydrants using sheltered vehicles...

Page 10: ...ons A hydrant assembled and adjusted by the manufacturer is ready for installation in the system Any dismantling of the hydrant components may result in loss of tightness 4 2 INSTALLATION INSTRUCTIONS...

Page 11: ...e regulations defining the need for water for social uses The diagram above shows the installation method for standpost hydrant the installation method largely depends on the applied rules based on lo...

Page 12: ...ecommendations for installation of water systems and devices installed in water supply stations and other facilities apply Misuse of this product is prohibited 5 GUARANTEE CONDITIONS The manufacturer...

Reviews: