-99-
Coast to stop
0
Stop according to stop mode
1
Continue to run
2
Thous
and's
place
Load becoming 0 (30= E. ULF)
Coast to stop
0
Stop according to stop mode
1
Continue to run at 7% of rated motor
frequencyand resume to the set
frequency if the loadrecovers
2
Ten
thous
and's
place
PID feedback lost duringrunning
(31= E.PID)
Coast to stop
0
Stop according to stop mode
1
Continue to run
2
P9.50
Fault protection action
selection 4
One’s
place
Speed deviation too large (42=
E.SdL)
000
00
☆
Coast to stop
0
Stop according to stop mode
1
Continue to run
2
Ten’s
place
Motor over speed (43= E.oSF)
Coast to stop
0
Stop according to stop mode
1
Continue to run
2
Hundr
ed’s
place
Initial position fault (51= E.PoSF)
Coast to stop
0
Stop according to stop mode
1
Continue to run
2
If "Coast to stop" is selected, the Inverter displays E.**** and directly stops.
If "Stop according to the stop mode" is selected, the Inverter displays A.**** and
stopsaccording to the stop mode. After stop, the Inverter displays E.****.