-66-
The one's place, ten's place and hundred's place of this parameter are respectively used to select
the corresponding curve of AI1, AI2 and AI3. Any of the five curves can be selected for AI1, AI2 and AI3.
The DLB1 provides two AI terminals as standard. AI3x is provided by an optional extension card.
P4.34
Setting for AI less than
minimum input
One’s
place
Setting for AI1 less than minimum input
000
☆
Minimum value
0
0.0%
1
Ten’s place
Setting for AI2 less than minimum input
Minimum value
0
0.0%
1
Hundred’s
place
Setting for AI3 less than minimum input
Minimum value
0
0.0%
1
This parameter is used to determine the corresponding setting when the analog input voltage is less
than the minimum value. The unit's digit, ten's digit and hundred's digit of this parameter respectively
correspond to the setting for AI2, AI2 and AI3.
If the value of a certain digit is 0, when analog input voltage is less than the minimum input, the
corresponding setting of the minimum input (F4-14, F4-19, F4-24) is used.
If the value of a certain digit is 1, when analog input voltage is less than the minimum input, the
corresponding value of this analog input is 0.0%
P4.35
DI1 delay time
0.0s~3600.0s
0.0s
★
P4.36
DI2 delay time
0.0s~3600.0s
0.0s
★
P4.37
DI3 delay time
0.0s~3600.0s
0.0s
★
These parameters are used to set the delay time of the Inverter when the status of DI terminals
changes.
Currently, only DI1, DI2 and DI3 support the delay time function.
P4.38
DI valid
mode
selection 1
One’s place
DI1 valid mode
00000
★
High level valid
0
Low level valid
1
Ten’s place
DI2 valid mode